YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
yc3 techguideYORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
R-454B - 1.5 nominal ton to 5 nominal ton
York International Corporation, 5005 York Drive, Norman, OK 73069
2025-01-15
6523450-YTG-C-0125 Supersedes: 6523450-YTG-B-0924
Johnson Controls Ducted Systems
2
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Contents
ContentsDescription........................................................................................................................................................ 5 Certification....................................................................................................................................................... 5 Warranty summary.......................................................................................................................................... 5 Features............................................................................................................................................................. 6 Nomenclature................................................................................................................................................... 7 Physical and electrical data............................................................................................................................. 8
Physical and electrical data notes........................................................................................................9 Dimensions....................................................................................................................................................... 9
Illustration of dimensions...................................................................................................................10 Dimensions data notes....................................................................................................................... 10 System charge table.......................................................................................................................................10 System charge A-coil data notes........................................................................................................11 Charging.......................................................................................................................................................... 12 Applications and accessories........................................................................................................................ 12 Sound power rating....................................................................................................................................... 13 Mechanical specifications..............................................................................................................................14 Typical installation..........................................................................................................................................16 Alternative installation clearances............................................................................................................... 17 Performance data - 1.5 ton........................................................................................................................... 18 Cooling performance data - 1.5 ton.................................................................................................. 18 Performance data - 2 ton.............................................................................................................................. 19 Cooling performance data - 2 ton..................................................................................................... 19 Performance data - 2.5 ton........................................................................................................................... 20 Cooling performance data - 2.5 ton.................................................................................................. 20 Performance data - 3 ton.............................................................................................................................. 21 Cooling performance data - 3 ton..................................................................................................... 21 Performance data - 3.5 ton........................................................................................................................... 22 Cooling performance data - 3.5 ton.................................................................................................. 22 Performance data - 4 ton.............................................................................................................................. 23 Cooling performance data - 4 ton..................................................................................................... 23 Performance data - 5 ton.............................................................................................................................. 24 Cooling performance data - 5 ton..................................................................................................... 24 Third-party trademarks................................................................................................................................. 24
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
3
Johnson Controls Ducted Systems
4
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Description
The YC3 models are part of our successful 13.4 SEER2 Regional Minimum Efficiency product line available in the northern United States and Canada. These outdoor units are specifically designed to be matched with our residential indoor coils, furnaces, and air handlers to provide a complete system solution.
Figure 1: Installation map
Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.simplygettingthejobdone.com and www.york.com. Additional rating information can be found at www.ahridirectory.org. This document is only for distribution use - it is not to be used at point of retail sale.
Certification
Warranty summary
Standard 5-year limited parts warranty. Standard 10-year limited compressor warranty. Extended 10-year limited parts warranty when product is registered online within 90 days of purchase for replacement or closing for new home construction. The warranty does not apply to R-22 models, three-phase models, or internet sales. Refer to the limited warranty certificate in the User's Information Manual for details.
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
5
Johnson Controls Ducted Systems
Features
· Small footprint - Minimum footprint for easier handling, transportation, and installation.
· Easier installation - Independent panels provide quick access for unit setup. Installation time is reduced by easy power and control wiring access. Select indoor matches with factory-mounted TXVs are available for quicker system installation. The filter-drier is shipped loose for installation in the field. The unit is factory-charged for 15 ft refrigeration piping. The small base dimension and reduced unit clearances make for easier retrofits.
· Accessible information - QR code on unit provides quick access to technical documents and warranty information.
· Durable finish - The coated steel wire fan guard, coated external fasteners, and pre-treated G90-equivalent galvanized steel chassis components resist corrosion and rust creep. Modern Mist colored powdercoat paint further protects external panels.
· Quality coils - The high efficiency microchannel aluminum coil is manufactured using an improved material system, providing reliable performance and small unit size.
· Rugged coil protection - Coils are protected from mechanical damage by a proven stamped steel coil guard design.
· Protected compressor - Compressors are protected internally by a high-pressure relief valve and a temperature sensor, and externally by the system high-pressure switch.
· Reliable operation - Ball bearing fan motors provide superior performance in extreme temperatures.
· Environmentally friendly - CFC-free R-454B refrigerant delivers environmentally friendly performance with zero ozone depletion.
· Top discharge - Warm air is blown up, away from the structure and any landscaping, allowing compact location on multi-unit applications.
· Low operating sound levels - Developed using CFD and FEA tools, the sturdy cabinet and top design provides sound performance of 77 dBA or lower. Compatible accessories for further sound reduction are also available.
· Better service access - Diagonal base valves with open access for low-loss fittings, single panel access to the electrical controls, swing out control box for full corner access, and removable fan guard allow easy access for unit maintenance.
· Agency listed - Safety certified by CSA to UL 60335-2-40/CSA C22.2. Performance certified to ANSI/AHRI Standard 210/240 in accordance with the Unitary Small Equipment certification program.
6
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Nomenclature
Table 1: Nomenclature for AC and HP R-454B units
Number 1 2 3
4, 5
6 7 8 9 10 11
Category Brand Product type Nominal series efficiency
Nominal unit capacity (MBH)
Refrigerant Voltage (voltage-phase-hertz) Control strategy Factory option Generation Style letter (minor revision)
Option Y X R C H 3 4 5 6 7 8 9 V X Z 18 24 30 36 42 48 60 D E 2 3 4 5 C B S W 1 2 1 2 A B
Table 2: Model nomenclature example
Number
1
2
3
4, 5
6
7
Option
Y
C
3
18
E
2
Description YORK Private brand OTC AC HP 13.4 SEER2 LGWP 14.3 SEER2 LGWP 15.2 SEER2 LGWP 16 SEER2 LGWP 17 SEER2 LGWP 18 SEER2 LGWP 19 SEER2 LGWP 20/21 SEER2 (DOE ccHP) 22/23 SEER2 24+ SEER2 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 5 ton TBC R-454B 208/230-1-60 208/230-3-60 460-3-60 575-3-60 Communicating Wireless (communicating) Standard (conventional) Wireless (conventional) Standard (no options) Future use First generation Second generation Style A Style B
8
9
10
11
S
1
1
A
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
7
Johnson Controls Ducted Systems
Physical and electrical data
Table 3: Physical and electrical data
Outdoor unit model YC318E2S11
Unit supply voltage
Normal voltage
range1 (V)
Minimum circuit
9.1
ampacity (A)
Maximum overcurrent 15
device2 (A)
Minimum overcurrent 15
device3 (A)
Compressor type4
Rotary
Compressor rated
6.7
load
Compressor locked 33.0
rotor
Crankcase heater
No
Factory external
No
discharge muffler
HS kit required with No
TXV5
HS kit part number 22006
(S1-2SA067*****)
Fan diameter (in.)
18
Fan motor type
PSC
Fan motor rated HP 1/12
Fan motor rated load 0.64
(A)
Fan motor nominal 1000
RPM
Fan motor nominal 1900
CFM
Coil face area (sq. ft.) 9.74
Coil rows deep
1
Coil fins per inch
23
Liquid refrigerant
3/8
piping outdoor unit
(field installed)
Vapor refrigerant
3/4
piping outdoor unit
(field installed)6
Unit charge7 (lb-oz) 2-6
Charge (oz/ft)
0.57
Operating weight (lb) 120
YC324E2S11
12.7 20
15
Rotary 9.6 53.0 No No No
22006 18 PSC 1/8 0.70 1100 2150 12.47 1 23 3/8
3/4
2-12 0.57 135
YC330E2S11 YC336E2S11 YC342E2S11 208/230 V, 1 phase, 60 Hz 187--252
16.3
18.2
19.2
25
30
30
20
20
20
Scroll 12.5
67.0
No No
No
Scroll 13.5
82.5
No No
No
Scroll 14.3
95.0
No No
No
10106
18 PSC 1/8 0.70
1100
2150
13.84 1 23 3/8
10106
18 PSC 1/4 1.33
1100
2575
13.84 1 23 3/8
10106
22 PSC 1/4 1.30
850
3275
17.31 1 23 3/8
3/4
3/4
7/8
2-13
2-14
2-15
0.57
0.57
0.60
140
140
195
YC348E2S11
29.3 50
30
Scroll 22.4 126.0 No No No
10106 24 PSC 1/4 1.30 850 3500 18.70 1 23 3/8
7/8
3-4 0.60 210
YC360E2S11
30.9 50
35
Scroll 23.7 157.0 No No No
10106 26 PSC 1/4 1.30 850 4300 23.33 1 23 3/8
1 1/8
3-10 0.67 230
8
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Physical and electrical data notes
NOTICE
If an indoor metering device other than S1-1TVM5A1 is used on rotary compressor models, factory hard start kit S1-2SA06722006 is required.
1. Rated in accordance with AHRI Standard 110-2012, utilization range A.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. Rotary compressor models are limited to an equivalent length of refrigerant piping of 100 ft with no exceptions.
5. Refer to the Hard Start Kit Accessory Installation Manual for the hard start kit part number for each model. The hard start kit is a field-installed accessory.
6. For applications with non-standard vapor line sizes, see Applications and accessories.
7. The unit charge is correct for the outdoor unit, smallest matched indoor unit, and 15 ft of refrigerant tubing. For tubing lengths other than 15 ft, add or subtract the amount of refrigerant, using the difference in actual refrigeration piping length (not the equivalent length) multiplied by the per foot value.
The adapter fitting must be field installed for the required 1 1/8 in. refrigeration piping.
Dimensions
Table 4: Dimensions
Unit model
Dimensions (in.)
YC318E2S11 YC324E2S11 YC330E2S11 YC336E2S11 YC342E2S11 YC348E2S11 YC360E2S11
A 26 3/4 33 1/4 36 1/4 36 1/4 36 1/4 33 1/4 36 1/4
B 24 24 24 24 29 1/4 35 1/4 38
C 24 24 24 24 29 1/4 31 3/4 34 1/4
Refrigerant connection service valve
size (in.)
Liquid
Vapor
3/8
3/4
3/8
3/4
3/8
3/4
3/8
3/4
3/8
7/8
3/8
7/8
3/8
7/8
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
9
Johnson Controls Ducted Systems
Illustration of dimensions
Figure 2: Unit dimensions
Dimensions data notes
The adapter fitting must be field-installed for the required 1 1/8 in. refrigeration piping. · All dimensions are in inches and are subject to change without notice. · The overall height is from the bottom of the base pan to the top of the fan guard. · The overall length and width include screw heads.
System charge table
Table 5: System charge table
Outdoor unit model Required metering device1,2 Indoor coil model3,4,5 CT(F,M)24B**B CT(F,M)30C**C CT(F,M)36C**D CT(F,M)48D**F CT(F,M)60C**H CT(F,M,U)18A**A CT(F,M,U)24A**B CT(F,M,U)30B**C CT(F,M,U)36B**D CT(F,M,U)48C**F CT(F,M,U)60C**G CT(F,M,U)60D**G CT(F,M,U)60D**H CTF18B**A CTF30A**D CTF36B**E CTF42C**E CTM42C**E
YC318E2S11 5A1
6 -- -- -- -- 4 6 -- -- -- -- -- -- 4 -- -- -- --
YC324E2S11 5A1
5 6 -- -- -- -- 5 6 -- -- -- -- -- -- -- -- -- --
YC330E2S11 YC336E2S11 YC342E2S11
5A1
5C1
5C1
Additional charge (oz)
--
--
--
6
--
--
13
12
--
--
--
17
--
--
--
--
--
--
--
--
--
6
--
--
13
12
--
--
--
17
--
--
--
--
--
--
--
--
--
--
--
--
13
--
--
--
14
--
--
14
14
--
14
--
YC348E2S11 5C1
-- -- -- 12 -- -- -- -- -- 12 16 16 -- -- -- -- -- --
YC360E2S11 5C1
-- -- -- -- 23 -- -- -- -- -- 19 19 23 -- -- -- -- --
10
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Table 5: System charge table
Outdoor unit model Required metering device1,2 Indoor coil model3,4,5 JHC18B**B JHC24B**C JHC36(B,C)**D JHC42(C,D)**F JHC48(C,D)**G JHC60(C,D)**H JHE18B**B JHE24B**C JHE30B**D JHE36(B,C)**D JHE42C**F JHE48(C,D)**G JHE60(C,D)**H
YC318E2S11 5A1
6 -- -- -- -- -- 6 -- -- -- -- -- --
YC324E2S11 5A1
-- 6 -- -- -- -- -- 6 -- -- -- -- --
YC330E2S11 YC336E2S11 YC342E2S11
5A1
5C1
5C1
Additional charge (oz)
--
--
--
--
--
--
13
12
--
--
--
17
--
--
--
--
--
--
--
--
--
--
--
--
13
--
--
13
12
--
--
--
17
--
--
--
--
--
--
YC348E2S11 5C1
-- -- -- -- 16 -- -- -- -- -- -- 16 --
YC360E2S11 5C1
-- -- -- -- -- 23 -- -- -- -- -- -- 23
System charge A-coil data notes
1. For applications requiring a TXV, use S1-1TVM*** series kit. 2. Use a TXV kit with these indoor units to obtain system performance. 3. Systems matched with furnaces or air handlers not equipped with blower-off delays may
require blower time delay. 4. Do not use CTF, CTU, or CXF coils in horizontal applications. CTM coils can be used in horizontal,
upflow, or downflow applications. 5. Charge adders shown above do not indicate that coils are rated for every application. See the
Performance data tables for actual performance for specified system matches. Obtain certified system ratings from http://www.ahridirectory.org.
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
11
Johnson Controls Ducted Systems
Charging
1. Check the factory unit charge listed on the unit nameplate to verify the refrigerant charge for the outdoor unit, the smallest matched indoor unit, and the 15 ft of interconnecting refrigeration piping.
2. Verify the indoor metering device and additional charge required for the specific matched indoor unit in the system using the System charge table.
3. Add additional charge for the amount of interconnecting refrigeration piping greater than 15 ft at the rate specified in the Physical and electrical data table.
4. For installations requiring additional charge, weigh in refrigerant for the specific matching indoor unit and actual refrigeration piping length.
5. After weighing in the charge adders for the matched indoor unit and refrigeration piping, verify the system operation against the temperatures and pressures in the charging chart for the outdoor unit. Locate the charging charts on the outdoor unit and in the Service Data Application Guide at www.simplygettingthejobdone.com. Follow the subcool or superheat charging procedure in the Installation Manual according to the type of indoor metering device in the system, and allow 10 min after each charge adjustment for the system operation to stabilize. Record the charge adjustment made to match the charging chart.
6. Permanently stamp the unit nameplate with the total system charge defined as follows: total system charge = base charge (as shipped) + charge adder for matched indoor unit + charge adder for actual refrigeration piping length + charge adjustments to match the charging chart.
Applications and accessories
Refer to the Price Manual for specific model numbers.
Table 6: Standard application limits
Standard application limits
Maximum refrigeration piping equivalent length
Outdoor ambient temperature limits
Cooling operation
Maximum DB
Minimum DB
80 ft
125°F 55°F
Note: For low ambient and long refrigeration piping applications, see the accessories listed below.
Non-standard refrigeration piping applications: For installations with reduced diameter or long refrigeration piping, refer to the current version of the Piping Application Guide P/N 247077, available in the Application Bulletins section at www.simplygettingthejobdone.com.
OD unit anti-short cycle kit (10 Pack) (S1-2TD08700124BK): A time delay that prevents rapid compressor restarting as a result of power interruption, limit switch operation, or thermostat resetting. Not required for AC models with factory electronic controls.
Standard low ambient control kit (S1-2LA06700424): Allows the use of air conditioning at low outdoor ambient temperatures down to +20°F (-7°C). For use with all R-454B single-stage AC models.
Advanced low ambient control kit (S1-2LA04701024): Contains the necessary components and controls to allow cooling operation down to -20°F (-29°C). For use with some R-454B single-stage AC and HP models. This accessory can only be applied to models that contain a PSC outdoor fan motor.
12
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Low pressure switch kit (S1-2PS06700524): Provides field installed low pressure (loss of charge) protection. Not required for AC models with factory electronic controls.
High ambient outdoor fan motor (S1-FHM****HT): Class F 70°C motor to allow cooling operation up to 160ºF air entering the outdoor coil. For use with all R-454B single-stage AC models containing R-454B refrigerant only.
Start assist kit (S1-2SA067*****): Provides increased compressor starting torque for areas with low supply voltage. Required for units with reciprocating compressors when applied with indoor TXV, and for all units when applied with long linesets or low ambient kits. May be factory installed on select AC units. See the Physical and electrical data table. Refer to the Price Pages or Source 1 SmartSearch for the correct kit for each application.
Compressor crankcase heater kit (S1-025-*****-***): A wrap-around electrical resistance heater that warms the compressor sump, reducing the chance of liquid slugging on startup. Required on all long lineset and low ambient applications. Refer to the Price Pages or Source 1 SmartSearch for the correct part for each application.
Anchor bracket kit (S1-1HK0601): Firmly anchors unit to pad or support structure. When correctly installed, approved for ground-mounted or roof-mounted applications.
Indoor TXV kit (S1-1TVM***): Thermal expansion valves precisely meter refrigerant for optimum performance over a wide range of conditions. See the System charge table or refer to the Price Pages or Source 1 Smart Search for the TXV part number for each AC model.
Winter cover kit (S1-CCVRE***): Custom fit winter cover protects AC outdoor unit from debris during the off-season. Remove before unit operation. Refer to the Price Pages or Source 1 SmartSearch for the correct cover for each application.
Touch-up paint (S1-5130153****): Color matched aerosol paint for touching up unit chassis and panels. Refer to the Price Pages or Source 1 SmartSearch for the correct color for each application.
Compressor sound blanket (S1-01007xxx000): A field installed dense foam cover that provides 2 dBA sound level reduction. Refer to the Price Pages or Source 1 SmartSearch for the correct blanket for each application.
Thermostat: Compatible thermostat controls are available through accessory sourcing. For optimum performance, these outdoor units are fully compatible with our residential HxTM Touch Screen Thermostat available through Source 1. For more information, refer to the Thermostats & Controllers section at www.simplygettingthejobdone.com.
Sound power rating
Table 7: Sound power data cooling octave band sound power level (db re. 1-pW)
Outdoor unit Power level (Hz)
dBA
SQI
model
63
125
250
500
1000
2000
4000
8000
YC318E2S11 74
69
63
66
65
61
57
54
73
19.1
YC324E2S11 72
73
65
68
65
66
68
59
74
19.0
YC330E2S11 75
71
65
69
64
61
57
60
73
19.1
YC336E2S11 72
73
68
70
68
66
60
64
74
19.0
YC342E2S11 68
73
70
73
67
64
61
59
76
19.1
YC348E2S11 68
70
70
70
69
63
61
61
76
19.2
YC360E2S11 70
73
72
71
71
66
64
64
77
19.1
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
13
Johnson Controls Ducted Systems
Mechanical specifications
Manufacture and certifications
· Units shall be assembled at a facility with an ISO 9001:2015-certified Quality Management System.
· Units shall be certified by CSA to UL 60335-2-40/CSA C22.2 and performance certified to ANSI/ AHRI Standard 210/240.
· Units shall be sound tested according to ANSI/AHRI Standard 270. · Certified matched system ratings shall be available for download from the AHRI online directory
at www.ahridirectory.org. Unit application
· Units shall be approved for cooling operation between 55ºF and 125°F without modification. · Units shall be approved for linesets up to 80 ft equivalent length without modification. · Units shall be approved for installation within 6 in. of a flat vertical wall without modification,
according to the instructions in the technical literature. · Units shall be designed to 77 dBA or less to minimize sound pollution. Unit access
· Units shall have a removable fan guard that can be removed independently of the top for interior access through the top of the unit without damaging the coil.
· Units shall have two removable stamped steel coil guards for exterior coil access. · Units shall have a separate compartment for electrical controls that can be accessed without
disturbing the unit airflow. · Units shall have a blockoff panel that can be removed to provide interior unit access through
the side of the unit. · Units shall have a removable blockoff panel and a swing away removable electrical panel that
provides sufficient interior unit access for removing the compressor through the side of the unit. Unit construction
· Units shall be shipped completely wired, piped, and assembled. Wiring pigtails shall be provided for field control wiring connections. Service valves shall be provided for field refrigerant line connections.
· Units shall be factory leak checked, run tested, and shipped with a holding charge of R-454B refrigerant.
· Unit cabinet components shall be G90 equivalent steel finished with powder-coat paint rated at a minimum of 500 h under ASTM B117 testing.
· Unit base pan shall be stamped G90 equivalent steel finished with powder-coat paint rated at a minimum of 500 h under ASTM B117 testing.
· Units shall have a single corner post opposite the electrical control box and two independently removable steel coil guard panels to optimize cabinet strength and serviceability.
· Units shall have L-shaped stamped sheet metal coil guards with punched and extruded slots for maximum panel durability and stiffness.
· Unit base valves shall be mounted diagonally on the unit base pan with service ports that provide sufficient clearance for low-loss hose fittings.
· Units shall be constructed with a high-pressure switch for system protection. · Units shall be constructed with all badging and labels applied at the factory.
14
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Unit components
· Compressor shall be hermetic with internal electrical overload protection and internal overpressure protection.
· Compressor shall be mounted on rubber vibration isolators that do not require the removal of transportation clips or brackets.
· Outdoor fan shall be direct drive with vertical air discharge for low sound levels. · Outdoor fan motor shall be totally enclosed with permanently lubricated ball bearings motors
approved for vertical shaft applications. · Outdoor coil shall be air cooled and have zinc-coated aluminum microchannel construction for
small size and low weight. Unit warranties
· Unit manufacturer shall provide a 10-year compressor warranty without a requirement for unit registration.
· Unit manufacturer shall provide a 5-year parts warranty without a requirement for unit registration.
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
15
Johnson Controls Ducted Systems
Typical installation
Figure 3: Typical installation
CAUTION
Care must be taken to prevent ice from damaging the unit. Damage may occur from ice falling onto unit from a sloped roof or from a vertical drip line due to a partial overhang.
Figure 4: Typical installation
16
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Alternative installation clearances
Figure 5: Alternative installation clearances
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
17
Johnson Controls Ducted Systems
Performance data - 1.5 ton
See the following tables for performance data for the YC318E2S11 unit.
Cooling performance data - 1.5 ton
Table 8: Cooling performance data - 1.5 ton
Air temperature entering Indoor CFM
450
600
750
outdoor unit (°F)
Indoor dry bulb 80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
(°F)
Indoor wet bulb 57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
(°F)
55
Total capacity
16.5 17.9 17.9 19.4 21.0 18.4 19.2 19.2 20.9 22.5 19.6 20.1 20.0 22.0 23.9
55
Sensible capacity 16.4 14.6 12.5 12.2 9.7 18.3 17.3 14.5 14.1 11.0 19.5 19.4 16.3 15.9 12.4
55
kW
0.99 0.97 0.97 0.95 0.92 1.03 1.02 1.02 1.00 0.98 1.07 1.07 1.07 1.05 1.03
65
Total capacity
17.6 16.1 17.6 19.3 21.2 18.4 17.5 18.5 20.3 22.3 18.9 18.6 19.0 20.9 22.9
65
Sensible capacity 12.5 16.1 14.6 12.5 10.4 14.0 17.5 16.6 14.0 11.3 15.2 18.5 18.2 15.2 12.1
65
kW
1.09 1.10 1.09 1.07 1.05 1.15 1.15 1.15 1.12 1.10 1.21 1.22 1.21 1.18 1.16
75
Total capacity
16.9 15.7 16.9 18.6 20.5 17.7 17.0 17.7 19.5 21.4 18.1 18.0 18.1 20.0 22.0
75
Sensible capacity 12.3 15.6 14.4 12.3 10.2 13.8 17.0 16.4 13.8 11.1 15.0 17.9 17.9 15.0 11.8
75
kW
1.22 1.22 1.22 1.21 1.18 1.28 1.28 1.27 1.26 1.25 1.34 1.34 1.34 1.32 1.31
85
Total capacity
16.2 15.1 16.2 17.9 19.7 16.9 16.5 16.9 18.6 20.5 17.3 17.3 17.4 19.0 20.9
85
Sensible capacity 12.0 15.1 14.1 12.0 9.9 13.4 16.4 16.1 13.5 10.8 14.7 17.3 17.3 14.7 11.5
85
kW
1.34 1.34 1.34 1.33 1.33 1.40 1.40 1.40 1.40 1.39 1.48 1.48 1.48 1.46 1.45
95
Total capacity
15.5 14.6 15.5 17.1 18.9 16.1 15.8 16.2 17.8 19.6 16.4 16.6 16.7 18.2 20.0
95
Sensible capacity 11.6 14.5 13.7 11.7 9.6 13.0 15.8 15.6 13.1 10.5 14.2 16.6 16.6 14.3 11.2
95
kW
1.48 1.46 1.48 1.48 1.49 1.55 1.55 1.55 1.55 1.55 1.62 1.62 1.62 1.62 1.62
105
Total capacity
14.8 14.1 14.8 16.3 18.0 15.3 15.2 15.3 17.0 18.7 15.6 16.0 16.0 17.3 19.1
105
Sensible capacity 11.3 14.0 13.4 11.4 9.3 12.7 15.2 15.1 12.8 10.2 13.9 16.0 16.0 14.0 10.9
105
kW
1.62 1.61 1.62 1.63 1.64 1.69 1.69 1.69 1.70 1.71 1.77 1.77 1.77 1.78 1.79
115
Total capacity
13.6 13.2 13.7 15.0 16.4 14.4 14.5 14.6 16.0 17.6 15.0 15.4 15.7 16.7 18.7
115
Sensible capacity 10.8 13.2 12.9 10.5 8.2 12.5 14.4 14.6 12.4 9.5 14.1 15.4 15.6 14.3 11.0
115
kW
1.78 1.77 1.78 1.80 1.81 1.85 1.85 1.85 1.87 1.89 1.92 1.93 1.93 1.94 1.96
18
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Performance data - 2 ton
See the following tables for performance data for the YC324E2S11 unit.
Cooling performance data - 2 ton
Table 9: Cooling performance data - 2 ton
Air temperature entering Indoor CFM
600
800
1000
outdoor unit (°F)
Indoor dry bulb 80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
(°F)
Indoor wet bulb 57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
(°F)
55
Total capacity
21.7 23.4 23.4 25.3 27.4 24.1 24.6 24.7 26.6 28.7 25.5 25.1 25.1 27.0 29.0
55
Sensible capacity 21.7 19.1 16.3 15.9 12.7 24.1 22.3 18.7 18.1 13.8 25.4 24.9 20.7 20.0 14.7
55
kW
1.28 1.25 1.26 1.22 1.19 1.33 1.32 1.32 1.28 1.24 1.39 1.39 1.39 1.35 1.31
65
Total capacity
22.6 21.1 22.7 24.8 27.3 23.6 22.8 23.6 25.9 28.5 24.2 24.1 24.1 26.6 29.2
65
Sensible capacity 16.2 21.0 19.1 16.1 13.1 18.2 22.8 21.8 18.1 14.4 19.9 24.1 24.0 19.8 15.4
65
kW
1.41 1.42 1.41 1.38 1.35 1.48 1.49 1.48 1.45 1.42 1.56 1.56 1.56 1.53 1.50
75
Total capacity
21.9 20.6 21.9 24.0 26.4 22.8 22.3 22.8 25.1 27.5 23.2 23.5 23.5 25.7 28.2
75
Sensible capacity 16.0 20.5 18.9 16.0 13.0 18.0 22.3 21.5 18.0 14.2 19.7 23.4 23.4 19.8 15.3
75
kW
1.56 1.57 1.56 1.55 1.53 1.65 1.65 1.64 1.63 1.61 1.74 1.73 1.73 1.72 1.70
85
Total capacity
21.0 20.0 21.0 23.1 25.4 21.8 21.6 21.9 24.0 26.4 22.1 22.7 22.7 24.6 26.9
85
Sensible capacity 15.7 19.9 18.6 15.7 12.7 17.7 21.6 21.2 17.8 14.0 19.4 22.7 22.7 19.5 15.0
85
kW
1.74 1.73 1.74 1.73 1.72 1.82 1.82 1.82 1.82 1.81 1.91 1.91 1.91 1.90 1.89
95
Total capacity
20.1 19.3 20.1 22.2 24.4 20.8 20.9 20.9 23.0 25.3 21.2 21.9 21.9 23.4 25.8
95
Sensible capacity 15.3 19.2 18.1 15.3 12.3 17.3 20.8 20.8 17.4 13.6 19.0 21.9 21.9 19.1 14.6
95
kW
1.91 1.90 1.91 1.91 1.91 2.00 2.00 2.00 2.00 2.00 2.09 2.09 2.09 2.09 2.09
105
Total capacity
19.0 18.3 19.0 20.9 23.0 19.6 19.8 19.8 21.6 23.8 19.9 20.8 20.8 21.9 24.2
105
Sensible capacity 14.6 18.3 17.5 14.6 11.4 16.6 19.8 19.8 16.6 12.7 18.4 20.8 20.8 18.4 13.8
105
kW
2.08 2.07 2.08 2.09 2.10 2.17 2.17 2.17 2.19 2.20 2.27 2.27 2.27 2.28 2.29
115
Total capacity
18.0 17.9 17.9 19.3 20.7 18.8 19.5 19.1 20.0 21.2 19.2 20.8 20.3 20.2 20.7
115
Sensible capacity 13.9 17.8 16.8 13.4 9.8 16.3 19.5 19.1 15.8 11.1 18.5 20.8 20.3 17.9 12.0
115
kW
2.25 2.24 2.25 2.28 2.31 2.36 2.36 2.37 2.39 2.42 2.46 2.46 2.47 2.49 2.51
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
19
Johnson Controls Ducted Systems
Performance data - 2.5 ton
See the following tables for performance data for the YC330E2S11 unit.
Cooling performance data - 2.5 ton
Table 10: Cooling performance data - 2.5 ton
Air temperature entering Indoor CFM
800
1000
1200
outdoor unit (°F)
Indoor dry bulb 80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
(°F)
Indoor wet bulb 57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
(°F)
55
Total capacity
26.8 28.9 28.8 31.4 34.2 28.5 29.5 29.5 31.9 34.2 29.7 29.8 29.8 32.1 34.0
55
Sensible capacity 26.6 24.2 20.5 19.8 15.9 28.3 26.6 22.1 21.1 15.8 29.5 28.4 23.5 22.2 15.8
55
kW
1.57 1.55 1.56 1.54 1.52 1.64 1.62 1.63 1.61 1.61 1.71 1.70 1.70 1.69 1.69
65
Total capacity
27.9 25.7 27.9 30.5 33.3 28.7 27.5 28.8 31.4 34.2 29.3 28.6 29.3 32.1 34.8
65
Sensible capacity 19.6 25.5 23.3 19.5 15.7 21.3 27.3 25.5 21.2 16.7 22.7 28.5 27.5 22.6 17.5
65
kW
1.72 1.72 1.72 1.73 1.74 1.81 1.81 1.81 1.82 1.83 1.90 1.90 1.90 1.91 1.92
75
Total capacity
27.3 25.4 27.3 29.8 32.6 28.1 27.0 28.1 30.8 33.5 28.6 28.2 28.5 31.3 34.0
75
Sensible capacity 19.6 25.2 23.2 19.5 15.7 21.3 26.8 25.5 21.2 16.7 22.7 28.0 27.4 22.6 17.5
75
kW
1.93 1.92 1.93 1.94 1.95 2.02 2.02 2.02 2.03 2.05 2.11 2.11 2.11 2.13 2.14
85
Total capacity
26.5 24.9 26.5 29.0 31.8 27.2 26.4 27.2 29.9 32.6 27.7 27.5 27.5 30.4 33.1
85
Sensible capacity 19.4 24.7 23.0 19.4 15.6 21.1 26.2 25.3 21.1 16.6 22.5 27.3 27.3 22.5 17.4
85
kW
2.15 2.14 2.15 2.16 2.18 2.24 2.24 2.24 2.26 2.28 2.34 2.33 2.33 2.35 2.37
95
Total capacity
25.5 24.2 25.5 27.9 30.7 26.2 25.6 26.1 28.8 31.5 26.6 26.6 26.6 29.2 32.0
95
Sensible capacity 19.1 24.0 22.6 18.9 15.2 20.8 25.5 24.8 20.7 16.3 22.3 26.5 26.5 22.2 17.1
95
kW
2.38 2.37 2.38 2.40 2.42 2.48 2.47 2.48 2.50 2.52 2.57 2.57 2.57 2.59 2.61
105
Total capacity
23.9 23.1 23.8 26.3 28.9 24.5 24.4 24.4 27.0 29.6 24.8 25.3 25.3 27.4 30.0
105
Sensible capacity 18.4 22.9 21.9 18.3 14.4 20.2 24.2 24.2 20.1 15.5 21.7 25.2 25.2 21.7 16.4
105
kW
2.64 2.63 2.63 2.66 2.69 2.73 2.73 2.73 2.76 2.78 2.82 2.83 2.83 2.85 2.89
115
Total capacity
22.1 21.9 22.1 24.3 26.6 22.7 23.2 23.1 25.0 27.5 23.1 24.2 24.2 25.6 28.0
115
Sensible capacity 17.7 21.8 21.6 17.4 13.2 19.8 23.1 23.0 19.3 14.5 21.4 24.0 24.0 21.2 15.5
115
kW
2.95 2.96 2.95 2.97 2.99 3.04 3.05 3.05 3.07 3.10 3.13 3.13 3.14 3.17 3.22
20
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Performance data - 3 ton
See the following tables for performance data for the YC336E2S11 unit.
Cooling performance data - 3 ton
Table 11: Cooling performance data - 3 ton
Air temperature entering Indoor CFM
1000
1200
1400
outdoor unit (°F)
Indoor dry bulb 80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
(°F)
Indoor wet bulb 57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
(°F)
55
Total capacity
32.9 35.3 35.2 38.4 41.1 34.6 36.3 36.3 39.7 42.4 35.8 37.0 37.1 40.6 43.4
55
Sensible capacity 32.5 29.8 25.3 24.7 19.6 34.1 32.6 27.2 26.6 20.7 35.3 34.9 28.9 28.1 21.7
55
kW
1.94 1.95 1.95 1.95 1.96 2.03 2.04 2.04 2.04 2.05 2.12 2.13 2.14 2.14 2.15
65
Total capacity
34.5 32.3 34.6 37.6 40.9 35.4 33.9 35.3 38.5 41.7 35.9 35.1 35.8 39.1 42.4
65
Sensible capacity 24.8 31.8 29.2 24.7 20.2 26.5 33.4 31.7 26.3 21.2 28.0 34.6 33.7 27.8 22.0
65
kW
2.22 2.23 2.22 2.20 2.17 2.30 2.30 2.30 2.28 2.27 2.38 2.38 2.38 2.37 2.35
75
Total capacity
33.2 31.4 33.2 36.2 39.5 34.0 32.9 33.9 37.0 40.3 34.5 34.1 34.4 37.6 40.8
75
Sensible capacity 24.4 31.0 28.9 24.3 19.7 26.1 32.5 31.3 26.0 20.8 27.6 33.7 33.3 27.6 21.6
75
kW
2.41 2.42 2.41 2.41 2.40 2.50 2.50 2.50 2.49 2.48 2.59 2.58 2.58 2.58 2.57
85
Total capacity
31.7 30.3 31.7 34.7 37.9 32.4 31.8 32.3 35.5 38.6 32.9 32.9 32.9 36.0 39.0
85
Sensible capacity 23.8 29.9 28.4 23.8 19.2 25.6 31.4 30.8 25.5 20.2 27.2 32.4 32.5 27.1 21.1
85
kW
2.63 2.63 2.63 2.63 2.63 2.73 2.73 2.73 2.73 2.72 2.82 2.81 2.81 2.81 2.81
95
Total capacity
30.3 29.2 30.3 33.3 36.4 31.0 30.6 30.9 34.0 37.0 31.3 31.6 31.7 34.4 37.3
95
Sensible capacity 23.1 28.8 27.8 23.1 18.6 24.9 30.2 29.8 24.9 19.5 26.5 31.2 31.2 26.4 20.4
95
kW
2.93 2.93 2.93 2.94 2.94 3.02 3.02 3.02 3.02 3.03 3.11 3.11 3.11 3.11 3.12
105
Total capacity
28.7 27.9 28.7 31.6 34.5 29.3 29.2 29.3 32.2 35.0 29.7 30.2 30.2 32.5 35.4
105
Sensible capacity 22.4 27.5 26.9 22.4 17.9 24.2 28.8 28.9 24.0 18.8 25.7 29.8 29.8 25.6 19.7
105
kW
3.29 3.29 3.29 3.30 3.31 3.38 3.38 3.38 3.39 3.40 3.47 3.47 3.47 3.48 3.49
115
Total capacity
26.6 26.6 26.6 29.1 31.1 27.3 27.8 27.9 30.1 32.5 27.7 28.6 29.0 30.9 33.7
115
Sensible capacity 22.1 26.2 26.2 21.2 15.6 24.0 27.4 27.5 23.2 17.2 25.5 28.2 28.6 25.0 18.6
115
kW
3.73 3.74 3.74 3.76 3.78 3.80 3.80 3.81 3.83 3.86 3.87 3.86 3.88 3.90 3.94
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
21
Johnson Controls Ducted Systems
Performance data - 3.5 ton
See the following tables for performance data for the YC342E2S11 unit.
Cooling performance data - 3.5 ton
Table 12: Cooling performance data - 3.5 ton
Air temperature entering Indoor CFM
1200
1400
1600
outdoor unit (°F)
Indoor dry bulb 80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
(°F)
Indoor wet bulb 57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
(°F)
55
Total capacity
41.3 42.8 42.8 44.2 45.3 43.1 43.8 43.8 45.6 46.1 44.6 44.3 44.4 46.7 46.7
55
Sensible capacity 41.3 37.9 32.4 30.3 22.5 43.1 40.5 34.3 32.4 23.4 44.6 42.9 35.8 34.1 24.3
55
kW
2.24 2.21 2.22 2.17 2.16 2.32 2.30 2.30 2.27 2.25 2.41 2.39 2.40 2.38 2.35
65
Total capacity
39.9 37.5 40.0 43.9 47.9 40.9 39.2 40.9 44.8 48.8 41.5 40.5 41.3 45.4 49.4
65
Sensible capacity 30.4 37.5 36.0 30.4 24.7 32.3 39.2 38.7 32.2 25.8 33.9 40.5 41.0 33.8 26.7
65
kW
2.58 2.60 2.58 2.54 2.49 2.68 2.69 2.67 2.63 2.57 2.77 2.77 2.76 2.72 2.67
75
Total capacity
38.7 36.6 38.8 42.6 46.5 39.6 38.2 39.5 43.4 47.3 40.2 39.5 39.9 43.9 47.8
75
Sensible capacity 30.0 36.6 35.9 30.1 24.2 32.0 38.2 38.4 31.9 25.3 33.7 39.5 39.9 33.5 26.2
75
kW
2.88 2.89 2.87 2.83 2.78 2.97 2.98 2.97 2.93 2.87 3.06 3.07 3.06 3.01 2.96
85
Total capacity
37.3 35.5 37.2 41.0 44.8 38.1 37.1 37.7 41.7 45.4 38.6 38.3 38.4 42.2 45.9
85
Sensible capacity 29.4 35.5 35.2 29.4 23.6 31.4 37.1 37.6 31.3 24.6 33.2 38.3 38.4 33.0 25.6
85
kW
3.16 3.17 3.15 3.12 3.08 3.26 3.27 3.26 3.21 3.16 3.35 3.35 3.35 3.31 3.26
95
Total capacity
35.7 34.3 35.7 39.3 43.0 36.4 35.8 36.1 40.0 43.7 36.7 36.8 36.9 40.4 44.1
95
Sensible capacity 28.6 34.3 34.4 28.6 22.9 30.6 35.8 36.1 30.5 23.9 32.3 36.8 36.9 32.3 24.9
95
kW
3.50 3.50 3.49 3.47 3.43 3.60 3.60 3.60 3.56 3.51 3.69 3.69 3.69 3.65 3.61
105
Total capacity
33.8 32.9 33.6 37.3 40.9 34.4 34.2 34.3 37.8 41.4 34.7 35.3 35.3 38.2 41.7
105
Sensible capacity 28.0 32.9 33.3 27.9 22.1 30.0 34.2 34.3 29.8 23.1 31.6 35.3 35.3 31.5 24.1
105
kW
3.84 3.84 3.84 3.82 3.79 3.94 3.94 3.94 3.92 3.88 4.03 4.03 4.03 4.01 3.97
115
Total capacity
32.3 32.3 31.9 34.7 36.6 33.1 34.0 33.4 35.7 38.0 33.6 35.3 34.7 36.4 39.1
115
Sensible capacity 27.6 32.3 31.9 27.0 20.1 30.2 34.0 33.4 29.2 21.6 32.1 35.3 34.7 31.1 22.7
115
kW
4.20 4.18 4.21 4.21 4.23 4.30 4.29 4.31 4.31 4.32 4.41 4.40 4.42 4.42 4.42
22
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems
Performance data - 4 ton
See the following tables for performance data for the YC348E2S11 unit.
Cooling performance data - 4 ton
Table 13: Cooling performance data - 4 ton
Air temperature entering Indoor CFM
1350
1550
1750
outdoor unit (°F)
Indoor dry bulb 80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
(°F)
Indoor wet bulb 57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
(°F)
55
Total capacity
45.7 48.0 47.8 51.0 54.1 47.3 49.0 48.8 52.3 55.2 48.6 49.7 49.5 53.0 56.0
55
Sensible capacity 45.7 41.0 34.6 33.1 25.1 47.3 43.7 36.5 35.2 26.6 48.6 46.1 38.2 37.1 28.0
55
kW
2.69 2.70 2.70 2.71 2.72 2.78 2.79 2.79 2.80 2.82 2.87 2.88 2.88 2.90 2.91
65
Total capacity
46.2 43.5 46.5 50.5 54.7 47.2 45.3 47.3 51.4 55.7 47.8 46.6 47.9 52.1 56.4
65
Sensible capacity 33.8 43.5 40.2 33.6 26.8 35.7 45.3 42.9 35.4 27.9 37.3 46.6 45.1 37.0 28.8
65
kW
2.97 2.97 2.97 2.98 2.99 3.06 3.06 3.06 3.07 3.08 3.15 3.15 3.15 3.16 3.17
75
Total capacity
45.4 43.0 45.6 49.7 53.9 46.3 44.7 46.3 50.5 54.7 46.8 46.0 46.9 51.1 55.4
75
Sensible capacity 33.8 43.0 40.3 33.6 26.8 35.6 44.7 42.7 35.3 27.9 37.4 46.0 45.1 37.1 28.9
75
kW
3.29 3.28 3.29 3.30 3.31 3.38 3.37 3.38 3.39 3.40 3.47 3.47 3.47 3.48 3.49
85
Total capacity
44.3 42.1 44.2 48.3 52.6 45.0 43.6 45.0 49.2 53.4 45.4 44.9 45.4 49.7 53.9
85
Sensible capacity 33.5 42.1 39.9 33.3 26.5 35.3 43.6 42.3 35.1 27.6 36.9 44.9 44.5 36.8 28.6
85
kW
3.65 3.64 3.64 3.66 3.67 3.74 3.73 3.73 3.75 3.76 3.83 3.82 3.83 3.84 3.85
95
Total capacity
42.3 40.5 42.3 46.3 50.5 43.0 42.0 43.0 47.0 51.2 43.5 43.2 43.4 47.7 51.8
95
Sensible capacity 32.5 40.5 38.8 32.3 25.6 34.2 42.0 41.3 34.1 26.7 35.9 43.2 43.4 35.8 27.7
95
kW
4.07 4.07 4.07 4.09 4.10 4.16 4.16 4.16 4.18 4.19 4.25 4.25 4.25 4.27 4.28
105
Total capacity
40.1 38.8 40.0 43.9 47.9 40.6 40.2 40.4 44.6 48.6 41.0 41.3 41.4 45.0 49.0
105
Sensible capacity 31.6 38.8 37.9 31.4 24.7 33.4 40.2 40.3 33.2 25.8 35.1 41.3 41.4 35.0 26.8
105
kW
4.57 4.57 4.57 4.59 4.61 4.67 4.67 4.67 4.68 4.71 4.76 4.77 4.77 4.78 4.80
115
Total capacity
37.0 36.0 36.9 40.8 44.9 37.7 37.2 37.8 41.7 46.0 38.0 38.2 39.0 42.4 46.7
115
Sensible capacity 29.8 36.0 35.9 29.8 23.0 32.0 37.2 37.8 32.3 25.0 33.9 38.2 39.0 34.8 26.8
115
kW
5.23 5.26 5.23 5.22 5.20 5.30 5.32 5.31 5.30 5.29 5.40 5.39 5.40 5.37 5.37
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
23
Johnson Controls Ducted Systems
Performance data - 5 ton
See the following tables for performance data for the YC360E2S11 unit.
Cooling performance data - 5 ton
Table 14: Cooling performance data - 5 ton
Air temperature entering Indoor CFM
1525
1725
1925
outdoor unit (°F)
Indoor dry bulb 80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
(°F)
Indoor wet bulb 57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
(°F)
55
Total capacity
50.9 55.5 55.1 59.9 64.5 53.0 56.5 56.1 60.5 64.2 54.5 57.1 56.6 60.2 63.6
55
Sensible capacity 50.9 45.3 38.7 38.3 31.2 53.0 47.6 40.3 39.7 31.4 54.5 49.7 41.7 40.7 31.3
55
kW
3.25 3.26 3.27 3.28 3.29 3.34 3.36 3.36 3.37 3.39 3.43 3.44 3.45 3.46 3.48
65
Total capacity
54.0 50.3 54.3 59.0 64.0 55.0 52.0 55.4 60.1 65.1 55.8 53.4 56.2 61.0 65.9
65
Sensible capacity 38.5 50.3 45.2 38.4 31.4 40.1 52.0 47.5 40.0 32.4 41.6 53.4 49.6 41.4 33.2
65
kW
3.57 3.55 3.56 3.58 3.58 3.66 3.64 3.65 3.67 3.67 3.76 3.75 3.75 3.77 3.77
75
Total capacity
53.4 49.8 53.6 58.4 63.5 54.4 51.5 54.7 59.5 64.5 55.2 52.9 55.4 60.3 65.4
75
Sensible capacity 38.5 49.8 45.2 38.4 31.5 40.1 51.5 47.5 40.1 32.5 41.7 52.9 49.7 41.6 33.4
75
kW
3.92 3.91 3.92 3.94 3.95 4.02 4.00 4.01 4.03 4.04 4.12 4.10 4.11 4.13 4.14
85
Total capacity
52.2 49.0 52.4 57.3 62.3 53.2 50.6 53.4 58.2 63.3 54.0 52.0 54.0 59.0 64.1
85
Sensible capacity 38.1 49.0 44.8 38.2 31.2 39.8 50.6 47.2 39.8 32.2 41.4 52.0 49.4 41.3 33.1
85
kW
4.35 4.33 4.35 4.36 4.38 4.44 4.43 4.44 4.46 4.47 4.55 4.53 4.54 4.56 4.57
95
Total capacity
50.2 47.5 50.4 55.2 60.1 51.1 49.0 51.2 56.0 61.0 51.8 50.3 51.9 56.7 61.7
95
Sensible capacity 37.2 47.5 44.0 37.3 30.3 38.9 49.0 46.4 38.9 31.3 40.5 50.3 48.5 40.4 32.2
95
kW
4.86 4.84 4.85 4.89 4.90 4.96 4.94 4.96 4.98 4.99 5.05 5.04 5.05 5.07 5.08
105
Total capacity
47.3 45.6 47.5 51.9 56.6 48.0 47.1 48.1 52.6 57.5 48.5 48.3 48.7 53.2 58.0
105
Sensible capacity 36.4 45.6 43.3 36.4 29.1 38.2 47.1 45.9 38.2 30.2 39.8 48.3 48.0 39.8 31.2
105
kW
5.42 5.40 5.42 5.45 5.47 5.52 5.50 5.51 5.54 5.56 5.61 5.60 5.60 5.63 5.66
115
Total capacity
43.9 42.8 44.1 47.9 52.3 44.6 44.1 44.7 48.6 53.2 45.1 45.2 45.7 49.2 53.7
115
Sensible capacity 34.8 42.8 41.7 34.8 27.3 36.7 44.1 44.4 36.9 28.8 38.7 45.2 45.7 39.0 30.1
115
kW
6.12 6.09 6.09 6.11 6.09 6.21 6.17 6.17 6.21 6.23 6.29 6.23 6.26 6.32 6.44
Third-party trademarks
Third-Party Trademarks Notice: For information about third-party trademarks, refer to the relevant company websites.
Subject to change without notice. Published in U.S.A. Copyright © 2025 by Johnson Controls. All rights reserved. Johnson Controls Ducted Systems