YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

PDF preview unavailable. Download the PDF instead.

yc3 techguide
YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
R-454B - 1.5 nominal ton to 5 nominal ton

York International Corporation, 5005 York Drive, Norman, OK 73069
2025-01-15

6523450-YTG-C-0125 Supersedes: 6523450-YTG-B-0924

Johnson Controls Ducted Systems

2

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Contents
ContentsDescription........................................................................................................................................................ 5 Certification....................................................................................................................................................... 5 Warranty summary.......................................................................................................................................... 5 Features............................................................................................................................................................. 6 Nomenclature................................................................................................................................................... 7 Physical and electrical data............................................................................................................................. 8
Physical and electrical data notes........................................................................................................9 Dimensions....................................................................................................................................................... 9
Illustration of dimensions...................................................................................................................10 Dimensions data notes....................................................................................................................... 10 System charge table.......................................................................................................................................10 System charge A-coil data notes........................................................................................................11 Charging.......................................................................................................................................................... 12 Applications and accessories........................................................................................................................ 12 Sound power rating....................................................................................................................................... 13 Mechanical specifications..............................................................................................................................14 Typical installation..........................................................................................................................................16 Alternative installation clearances............................................................................................................... 17 Performance data - 1.5 ton........................................................................................................................... 18 Cooling performance data - 1.5 ton.................................................................................................. 18 Performance data - 2 ton.............................................................................................................................. 19 Cooling performance data - 2 ton..................................................................................................... 19 Performance data - 2.5 ton........................................................................................................................... 20 Cooling performance data - 2.5 ton.................................................................................................. 20 Performance data - 3 ton.............................................................................................................................. 21 Cooling performance data - 3 ton..................................................................................................... 21 Performance data - 3.5 ton........................................................................................................................... 22 Cooling performance data - 3.5 ton.................................................................................................. 22 Performance data - 4 ton.............................................................................................................................. 23 Cooling performance data - 4 ton..................................................................................................... 23 Performance data - 5 ton.............................................................................................................................. 24 Cooling performance data - 5 ton..................................................................................................... 24 Third-party trademarks................................................................................................................................. 24

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

3

Johnson Controls Ducted Systems

4

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Description
The YC3 models are part of our successful 13.4 SEER2 Regional Minimum Efficiency product line available in the northern United States and Canada. These outdoor units are specifically designed to be matched with our residential indoor coils, furnaces, and air handlers to provide a complete system solution.
Figure 1: Installation map

Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.simplygettingthejobdone.com and www.york.com. Additional rating information can be found at www.ahridirectory.org. This document is only for distribution use - it is not to be used at point of retail sale.
Certification
Warranty summary
Standard 5-year limited parts warranty. Standard 10-year limited compressor warranty. Extended 10-year limited parts warranty when product is registered online within 90 days of purchase for replacement or closing for new home construction. The warranty does not apply to R-22 models, three-phase models, or internet sales. Refer to the limited warranty certificate in the User's Information Manual for details.

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

5

Johnson Controls Ducted Systems

Features
· Small footprint - Minimum footprint for easier handling, transportation, and installation.
· Easier installation - Independent panels provide quick access for unit setup. Installation time is reduced by easy power and control wiring access. Select indoor matches with factory-mounted TXVs are available for quicker system installation. The filter-drier is shipped loose for installation in the field. The unit is factory-charged for 15 ft refrigeration piping. The small base dimension and reduced unit clearances make for easier retrofits.
· Accessible information - QR code on unit provides quick access to technical documents and warranty information.
· Durable finish - The coated steel wire fan guard, coated external fasteners, and pre-treated G90-equivalent galvanized steel chassis components resist corrosion and rust creep. Modern Mist colored powdercoat paint further protects external panels.
· Quality coils - The high efficiency microchannel aluminum coil is manufactured using an improved material system, providing reliable performance and small unit size.
· Rugged coil protection - Coils are protected from mechanical damage by a proven stamped steel coil guard design.
· Protected compressor - Compressors are protected internally by a high-pressure relief valve and a temperature sensor, and externally by the system high-pressure switch.
· Reliable operation - Ball bearing fan motors provide superior performance in extreme temperatures.
· Environmentally friendly - CFC-free R-454B refrigerant delivers environmentally friendly performance with zero ozone depletion.
· Top discharge - Warm air is blown up, away from the structure and any landscaping, allowing compact location on multi-unit applications.
· Low operating sound levels - Developed using CFD and FEA tools, the sturdy cabinet and top design provides sound performance of 77 dBA or lower. Compatible accessories for further sound reduction are also available.
· Better service access - Diagonal base valves with open access for low-loss fittings, single panel access to the electrical controls, swing out control box for full corner access, and removable fan guard allow easy access for unit maintenance.
· Agency listed - Safety certified by CSA to UL 60335-2-40/CSA C22.2. Performance certified to ANSI/AHRI Standard 210/240 in accordance with the Unitary Small Equipment certification program.

6

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Nomenclature

Table 1: Nomenclature for AC and HP R-454B units

Number 1 2 3
4, 5
6 7 8 9 10 11

Category Brand Product type Nominal series efficiency
Nominal unit capacity (MBH)
Refrigerant Voltage (voltage-phase-hertz) Control strategy Factory option Generation Style letter (minor revision)

Option Y X R C H 3 4 5 6 7 8 9 V X Z 18 24 30 36 42 48 60 D E 2 3 4 5 C B S W 1 2 1 2 A B

Table 2: Model nomenclature example

Number

1

2

3

4, 5

6

7

Option

Y

C

3

18

E

2

Description YORK Private brand OTC AC HP 13.4 SEER2 LGWP 14.3 SEER2 LGWP 15.2 SEER2 LGWP 16 SEER2 LGWP 17 SEER2 LGWP 18 SEER2 LGWP 19 SEER2 LGWP 20/21 SEER2 (DOE ccHP) 22/23 SEER2 24+ SEER2 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 5 ton TBC R-454B 208/230-1-60 208/230-3-60 460-3-60 575-3-60 Communicating Wireless (communicating) Standard (conventional) Wireless (conventional) Standard (no options) Future use First generation Second generation Style A Style B

8

9

10

11

S

1

1

A

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

7

Johnson Controls Ducted Systems

Physical and electrical data

Table 3: Physical and electrical data

Outdoor unit model YC318E2S11

Unit supply voltage

Normal voltage

range1 (V)

Minimum circuit

9.1

ampacity (A)

Maximum overcurrent 15

device2 (A)

Minimum overcurrent 15

device3 (A)

Compressor type4

Rotary

Compressor rated

6.7

load

Compressor locked 33.0

rotor

Crankcase heater

No

Factory external

No

discharge muffler

HS kit required with No

TXV5

HS kit part number 22006

(S1-2SA067*****)

Fan diameter (in.)

18

Fan motor type

PSC

Fan motor rated HP 1/12

Fan motor rated load 0.64

(A)

Fan motor nominal 1000

RPM

Fan motor nominal 1900

CFM

Coil face area (sq. ft.) 9.74

Coil rows deep

1

Coil fins per inch

23

Liquid refrigerant

3/8

piping outdoor unit

(field installed)

Vapor refrigerant

3/4

piping outdoor unit

(field installed)6

Unit charge7 (lb-oz) 2-6

Charge (oz/ft)

0.57

Operating weight (lb) 120

YC324E2S11
12.7 20
15
Rotary 9.6 53.0 No No No
22006 18 PSC 1/8 0.70 1100 2150 12.47 1 23 3/8
3/4
2-12 0.57 135

YC330E2S11 YC336E2S11 YC342E2S11 208/230 V, 1 phase, 60 Hz 187--252

16.3

18.2

19.2

25

30

30

20

20

20

Scroll 12.5
67.0
No No
No

Scroll 13.5
82.5
No No
No

Scroll 14.3
95.0
No No
No

10106
18 PSC 1/8 0.70
1100
2150
13.84 1 23 3/8

10106
18 PSC 1/4 1.33
1100
2575
13.84 1 23 3/8

10106
22 PSC 1/4 1.30
850
3275
17.31 1 23 3/8

3/4

3/4

7/8

2-13

2-14

2-15

0.57

0.57

0.60

140

140

195

YC348E2S11
29.3 50
30
Scroll 22.4 126.0 No No No
10106 24 PSC 1/4 1.30 850 3500 18.70 1 23 3/8
7/8
3-4 0.60 210

YC360E2S11
30.9 50
35
Scroll 23.7 157.0 No No No
10106 26 PSC 1/4 1.30 850 4300 23.33 1 23 3/8
1 1/8
3-10 0.67 230

8

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Physical and electrical data notes

NOTICE

If an indoor metering device other than S1-1TVM5A1 is used on rotary compressor models, factory hard start kit S1-2SA06722006 is required.

1. Rated in accordance with AHRI Standard 110-2012, utilization range A.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. Rotary compressor models are limited to an equivalent length of refrigerant piping of 100 ft with no exceptions.
5. Refer to the Hard Start Kit Accessory Installation Manual for the hard start kit part number for each model. The hard start kit is a field-installed accessory.
6. For applications with non-standard vapor line sizes, see Applications and accessories.
7. The unit charge is correct for the outdoor unit, smallest matched indoor unit, and 15 ft of refrigerant tubing. For tubing lengths other than 15 ft, add or subtract the amount of refrigerant, using the difference in actual refrigeration piping length (not the equivalent length) multiplied by the per foot value.
 The adapter fitting must be field installed for the required 1 1/8 in. refrigeration piping.

Dimensions

Table 4: Dimensions

Unit model

Dimensions (in.)

YC318E2S11 YC324E2S11 YC330E2S11 YC336E2S11 YC342E2S11 YC348E2S11 YC360E2S11

A 26 3/4 33 1/4 36 1/4 36 1/4 36 1/4 33 1/4 36 1/4

B 24 24 24 24 29 1/4 35 1/4 38

C 24 24 24 24 29 1/4 31 3/4 34 1/4

Refrigerant connection service valve

size (in.)

Liquid

Vapor

3/8

3/4

3/8

3/4

3/8

3/4

3/8

3/4

3/8

7/8

3/8

7/8

3/8

7/8

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

9

Johnson Controls Ducted Systems

Illustration of dimensions
Figure 2: Unit dimensions

Dimensions data notes
 The adapter fitting must be field-installed for the required 1 1/8 in. refrigeration piping. · All dimensions are in inches and are subject to change without notice. · The overall height is from the bottom of the base pan to the top of the fan guard. · The overall length and width include screw heads.

System charge table

Table 5: System charge table

Outdoor unit model Required metering device1,2 Indoor coil model3,4,5 CT(F,M)24B**B CT(F,M)30C**C CT(F,M)36C**D CT(F,M)48D**F CT(F,M)60C**H CT(F,M,U)18A**A CT(F,M,U)24A**B CT(F,M,U)30B**C CT(F,M,U)36B**D CT(F,M,U)48C**F CT(F,M,U)60C**G CT(F,M,U)60D**G CT(F,M,U)60D**H CTF18B**A CTF30A**D CTF36B**E CTF42C**E CTM42C**E

YC318E2S11 5A1
6 -- -- -- -- 4 6 -- -- -- -- -- -- 4 -- -- -- --

YC324E2S11 5A1
5 6 -- -- -- -- 5 6 -- -- -- -- -- -- -- -- -- --

YC330E2S11 YC336E2S11 YC342E2S11

5A1

5C1

5C1

Additional charge (oz)

--

--

--

6

--

--

13

12

--

--

--

17

--

--

--

--

--

--

--

--

--

6

--

--

13

12

--

--

--

17

--

--

--

--

--

--

--

--

--

--

--

--

13

--

--

--

14

--

--

14

14

--

14

--

YC348E2S11 5C1
-- -- -- 12 -- -- -- -- -- 12 16 16 -- -- -- -- -- --

YC360E2S11 5C1
-- -- -- -- 23 -- -- -- -- -- 19 19 23 -- -- -- -- --

10

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Table 5: System charge table

Outdoor unit model Required metering device1,2 Indoor coil model3,4,5 JHC18B**B JHC24B**C JHC36(B,C)**D JHC42(C,D)**F JHC48(C,D)**G JHC60(C,D)**H JHE18B**B JHE24B**C JHE30B**D JHE36(B,C)**D JHE42C**F JHE48(C,D)**G JHE60(C,D)**H

YC318E2S11 5A1
6 -- -- -- -- -- 6 -- -- -- -- -- --

YC324E2S11 5A1
-- 6 -- -- -- -- -- 6 -- -- -- -- --

YC330E2S11 YC336E2S11 YC342E2S11

5A1

5C1

5C1

Additional charge (oz)

--

--

--

--

--

--

13

12

--

--

--

17

--

--

--

--

--

--

--

--

--

--

--

--

13

--

--

13

12

--

--

--

17

--

--

--

--

--

--

YC348E2S11 5C1
-- -- -- -- 16 -- -- -- -- -- -- 16 --

YC360E2S11 5C1
-- -- -- -- -- 23 -- -- -- -- -- -- 23

System charge A-coil data notes
1. For applications requiring a TXV, use S1-1TVM*** series kit. 2. Use a TXV kit with these indoor units to obtain system performance. 3. Systems matched with furnaces or air handlers not equipped with blower-off delays may
require blower time delay. 4. Do not use CTF, CTU, or CXF coils in horizontal applications. CTM coils can be used in horizontal,
upflow, or downflow applications. 5. Charge adders shown above do not indicate that coils are rated for every application. See the
Performance data tables for actual performance for specified system matches. Obtain certified system ratings from http://www.ahridirectory.org.

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

11

Johnson Controls Ducted Systems

Charging
1. Check the factory unit charge listed on the unit nameplate to verify the refrigerant charge for the outdoor unit, the smallest matched indoor unit, and the 15 ft of interconnecting refrigeration piping.
2. Verify the indoor metering device and additional charge required for the specific matched indoor unit in the system using the System charge table.
3. Add additional charge for the amount of interconnecting refrigeration piping greater than 15 ft at the rate specified in the Physical and electrical data table.
4. For installations requiring additional charge, weigh in refrigerant for the specific matching indoor unit and actual refrigeration piping length.
5. After weighing in the charge adders for the matched indoor unit and refrigeration piping, verify the system operation against the temperatures and pressures in the charging chart for the outdoor unit. Locate the charging charts on the outdoor unit and in the Service Data Application Guide at www.simplygettingthejobdone.com. Follow the subcool or superheat charging procedure in the Installation Manual according to the type of indoor metering device in the system, and allow 10 min after each charge adjustment for the system operation to stabilize. Record the charge adjustment made to match the charging chart.
6. Permanently stamp the unit nameplate with the total system charge defined as follows: total system charge = base charge (as shipped) + charge adder for matched indoor unit + charge adder for actual refrigeration piping length + charge adjustments to match the charging chart.

Applications and accessories

Refer to the Price Manual for specific model numbers.

Table 6: Standard application limits

Standard application limits

Maximum refrigeration piping equivalent length

Outdoor ambient temperature limits

Cooling operation

Maximum DB

Minimum DB

80 ft
125°F 55°F

Note: For low ambient and long refrigeration piping applications, see the accessories listed below.
Non-standard refrigeration piping applications: For installations with reduced diameter or long refrigeration piping, refer to the current version of the Piping Application Guide P/N 247077, available in the Application Bulletins section at www.simplygettingthejobdone.com.
OD unit anti-short cycle kit (10 Pack) (S1-2TD08700124BK): A time delay that prevents rapid compressor restarting as a result of power interruption, limit switch operation, or thermostat resetting. Not required for AC models with factory electronic controls.
Standard low ambient control kit (S1-2LA06700424): Allows the use of air conditioning at low outdoor ambient temperatures down to +20°F (-7°C). For use with all R-454B single-stage AC models.
Advanced low ambient control kit (S1-2LA04701024): Contains the necessary components and controls to allow cooling operation down to -20°F (-29°C). For use with some R-454B single-stage AC and HP models. This accessory can only be applied to models that contain a PSC outdoor fan motor.

12

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Low pressure switch kit (S1-2PS06700524): Provides field installed low pressure (loss of charge) protection. Not required for AC models with factory electronic controls.
High ambient outdoor fan motor (S1-FHM****HT): Class F 70°C motor to allow cooling operation up to 160ºF air entering the outdoor coil. For use with all R-454B single-stage AC models containing R-454B refrigerant only.
Start assist kit (S1-2SA067*****): Provides increased compressor starting torque for areas with low supply voltage. Required for units with reciprocating compressors when applied with indoor TXV, and for all units when applied with long linesets or low ambient kits. May be factory installed on select AC units. See the Physical and electrical data table. Refer to the Price Pages or Source 1 SmartSearch for the correct kit for each application.
Compressor crankcase heater kit (S1-025-*****-***): A wrap-around electrical resistance heater that warms the compressor sump, reducing the chance of liquid slugging on startup. Required on all long lineset and low ambient applications. Refer to the Price Pages or Source 1 SmartSearch for the correct part for each application.
Anchor bracket kit (S1-1HK0601): Firmly anchors unit to pad or support structure. When correctly installed, approved for ground-mounted or roof-mounted applications.
Indoor TXV kit (S1-1TVM***): Thermal expansion valves precisely meter refrigerant for optimum performance over a wide range of conditions. See the System charge table or refer to the Price Pages or Source 1 Smart Search for the TXV part number for each AC model.
Winter cover kit (S1-CCVRE***): Custom fit winter cover protects AC outdoor unit from debris during the off-season. Remove before unit operation. Refer to the Price Pages or Source 1 SmartSearch for the correct cover for each application.
Touch-up paint (S1-5130153****): Color matched aerosol paint for touching up unit chassis and panels. Refer to the Price Pages or Source 1 SmartSearch for the correct color for each application.
Compressor sound blanket (S1-01007xxx000): A field installed dense foam cover that provides 2 dBA sound level reduction. Refer to the Price Pages or Source 1 SmartSearch for the correct blanket for each application.
Thermostat: Compatible thermostat controls are available through accessory sourcing. For optimum performance, these outdoor units are fully compatible with our residential HxTM Touch Screen Thermostat available through Source 1. For more information, refer to the Thermostats & Controllers section at www.simplygettingthejobdone.com.

Sound power rating

Table 7: Sound power data­ cooling ­ octave band sound power level (db re. 1-pW)

Outdoor unit Power level (Hz)

dBA

SQI

model

63

125

250

500

1000

2000

4000

8000

YC318E2S11 74

69

63

66

65

61

57

54

73

19.1

YC324E2S11 72

73

65

68

65

66

68

59

74

19.0

YC330E2S11 75

71

65

69

64

61

57

60

73

19.1

YC336E2S11 72

73

68

70

68

66

60

64

74

19.0

YC342E2S11 68

73

70

73

67

64

61

59

76

19.1

YC348E2S11 68

70

70

70

69

63

61

61

76

19.2

YC360E2S11 70

73

72

71

71

66

64

64

77

19.1

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

13

Johnson Controls Ducted Systems

Mechanical specifications
Manufacture and certifications
· Units shall be assembled at a facility with an ISO 9001:2015-certified Quality Management System.
· Units shall be certified by CSA to UL 60335-2-40/CSA C22.2 and performance certified to ANSI/ AHRI Standard 210/240.
· Units shall be sound tested according to ANSI/AHRI Standard 270. · Certified matched system ratings shall be available for download from the AHRI online directory
at www.ahridirectory.org. Unit application
· Units shall be approved for cooling operation between 55ºF and 125°F without modification. · Units shall be approved for linesets up to 80 ft equivalent length without modification. · Units shall be approved for installation within 6 in. of a flat vertical wall without modification,
according to the instructions in the technical literature. · Units shall be designed to 77 dBA or less to minimize sound pollution. Unit access
· Units shall have a removable fan guard that can be removed independently of the top for interior access through the top of the unit without damaging the coil.
· Units shall have two removable stamped steel coil guards for exterior coil access. · Units shall have a separate compartment for electrical controls that can be accessed without
disturbing the unit airflow. · Units shall have a blockoff panel that can be removed to provide interior unit access through
the side of the unit. · Units shall have a removable blockoff panel and a swing away removable electrical panel that
provides sufficient interior unit access for removing the compressor through the side of the unit. Unit construction
· Units shall be shipped completely wired, piped, and assembled. Wiring pigtails shall be provided for field control wiring connections. Service valves shall be provided for field refrigerant line connections.
· Units shall be factory leak checked, run tested, and shipped with a holding charge of R-454B refrigerant.
· Unit cabinet components shall be G90 equivalent steel finished with powder-coat paint rated at a minimum of 500 h under ASTM B117 testing.
· Unit base pan shall be stamped G90 equivalent steel finished with powder-coat paint rated at a minimum of 500 h under ASTM B117 testing.
· Units shall have a single corner post opposite the electrical control box and two independently removable steel coil guard panels to optimize cabinet strength and serviceability.
· Units shall have L-shaped stamped sheet metal coil guards with punched and extruded slots for maximum panel durability and stiffness.
· Unit base valves shall be mounted diagonally on the unit base pan with service ports that provide sufficient clearance for low-loss hose fittings.
· Units shall be constructed with a high-pressure switch for system protection. · Units shall be constructed with all badging and labels applied at the factory.

14

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Unit components
· Compressor shall be hermetic with internal electrical overload protection and internal overpressure protection.
· Compressor shall be mounted on rubber vibration isolators that do not require the removal of transportation clips or brackets.
· Outdoor fan shall be direct drive with vertical air discharge for low sound levels. · Outdoor fan motor shall be totally enclosed with permanently lubricated ball bearings motors
approved for vertical shaft applications. · Outdoor coil shall be air cooled and have zinc-coated aluminum microchannel construction for
small size and low weight. Unit warranties
· Unit manufacturer shall provide a 10-year compressor warranty without a requirement for unit registration.
· Unit manufacturer shall provide a 5-year parts warranty without a requirement for unit registration.

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

15

Johnson Controls Ducted Systems

Typical installation
Figure 3: Typical installation

CAUTION
Care must be taken to prevent ice from damaging the unit. Damage may occur from ice falling onto unit from a sloped roof or from a vertical drip line due to a partial overhang.
Figure 4: Typical installation

16

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Alternative installation clearances
Figure 5: Alternative installation clearances

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

17

Johnson Controls Ducted Systems

Performance data - 1.5 ton

See the following tables for performance data for the YC318E2S11 unit.

Cooling performance data - 1.5 ton

Table 8: Cooling performance data - 1.5 ton

Air temperature entering Indoor CFM

450

600

750

outdoor unit (°F)

Indoor dry bulb 80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

(°F)

Indoor wet bulb 57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

(°F)

55

Total capacity

16.5 17.9 17.9 19.4 21.0 18.4 19.2 19.2 20.9 22.5 19.6 20.1 20.0 22.0 23.9

55

Sensible capacity 16.4 14.6 12.5 12.2 9.7 18.3 17.3 14.5 14.1 11.0 19.5 19.4 16.3 15.9 12.4

55

kW

0.99 0.97 0.97 0.95 0.92 1.03 1.02 1.02 1.00 0.98 1.07 1.07 1.07 1.05 1.03

65

Total capacity

17.6 16.1 17.6 19.3 21.2 18.4 17.5 18.5 20.3 22.3 18.9 18.6 19.0 20.9 22.9

65

Sensible capacity 12.5 16.1 14.6 12.5 10.4 14.0 17.5 16.6 14.0 11.3 15.2 18.5 18.2 15.2 12.1

65

kW

1.09 1.10 1.09 1.07 1.05 1.15 1.15 1.15 1.12 1.10 1.21 1.22 1.21 1.18 1.16

75

Total capacity

16.9 15.7 16.9 18.6 20.5 17.7 17.0 17.7 19.5 21.4 18.1 18.0 18.1 20.0 22.0

75

Sensible capacity 12.3 15.6 14.4 12.3 10.2 13.8 17.0 16.4 13.8 11.1 15.0 17.9 17.9 15.0 11.8

75

kW

1.22 1.22 1.22 1.21 1.18 1.28 1.28 1.27 1.26 1.25 1.34 1.34 1.34 1.32 1.31

85

Total capacity

16.2 15.1 16.2 17.9 19.7 16.9 16.5 16.9 18.6 20.5 17.3 17.3 17.4 19.0 20.9

85

Sensible capacity 12.0 15.1 14.1 12.0 9.9 13.4 16.4 16.1 13.5 10.8 14.7 17.3 17.3 14.7 11.5

85

kW

1.34 1.34 1.34 1.33 1.33 1.40 1.40 1.40 1.40 1.39 1.48 1.48 1.48 1.46 1.45

95

Total capacity

15.5 14.6 15.5 17.1 18.9 16.1 15.8 16.2 17.8 19.6 16.4 16.6 16.7 18.2 20.0

95

Sensible capacity 11.6 14.5 13.7 11.7 9.6 13.0 15.8 15.6 13.1 10.5 14.2 16.6 16.6 14.3 11.2

95

kW

1.48 1.46 1.48 1.48 1.49 1.55 1.55 1.55 1.55 1.55 1.62 1.62 1.62 1.62 1.62

105

Total capacity

14.8 14.1 14.8 16.3 18.0 15.3 15.2 15.3 17.0 18.7 15.6 16.0 16.0 17.3 19.1

105

Sensible capacity 11.3 14.0 13.4 11.4 9.3 12.7 15.2 15.1 12.8 10.2 13.9 16.0 16.0 14.0 10.9

105

kW

1.62 1.61 1.62 1.63 1.64 1.69 1.69 1.69 1.70 1.71 1.77 1.77 1.77 1.78 1.79

115

Total capacity

13.6 13.2 13.7 15.0 16.4 14.4 14.5 14.6 16.0 17.6 15.0 15.4 15.7 16.7 18.7

115

Sensible capacity 10.8 13.2 12.9 10.5 8.2 12.5 14.4 14.6 12.4 9.5 14.1 15.4 15.6 14.3 11.0

115

kW

1.78 1.77 1.78 1.80 1.81 1.85 1.85 1.85 1.87 1.89 1.92 1.93 1.93 1.94 1.96

18

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Performance data - 2 ton

See the following tables for performance data for the YC324E2S11 unit.

Cooling performance data - 2 ton

Table 9: Cooling performance data - 2 ton

Air temperature entering Indoor CFM

600

800

1000

outdoor unit (°F)

Indoor dry bulb 80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

(°F)

Indoor wet bulb 57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

(°F)

55

Total capacity

21.7 23.4 23.4 25.3 27.4 24.1 24.6 24.7 26.6 28.7 25.5 25.1 25.1 27.0 29.0

55

Sensible capacity 21.7 19.1 16.3 15.9 12.7 24.1 22.3 18.7 18.1 13.8 25.4 24.9 20.7 20.0 14.7

55

kW

1.28 1.25 1.26 1.22 1.19 1.33 1.32 1.32 1.28 1.24 1.39 1.39 1.39 1.35 1.31

65

Total capacity

22.6 21.1 22.7 24.8 27.3 23.6 22.8 23.6 25.9 28.5 24.2 24.1 24.1 26.6 29.2

65

Sensible capacity 16.2 21.0 19.1 16.1 13.1 18.2 22.8 21.8 18.1 14.4 19.9 24.1 24.0 19.8 15.4

65

kW

1.41 1.42 1.41 1.38 1.35 1.48 1.49 1.48 1.45 1.42 1.56 1.56 1.56 1.53 1.50

75

Total capacity

21.9 20.6 21.9 24.0 26.4 22.8 22.3 22.8 25.1 27.5 23.2 23.5 23.5 25.7 28.2

75

Sensible capacity 16.0 20.5 18.9 16.0 13.0 18.0 22.3 21.5 18.0 14.2 19.7 23.4 23.4 19.8 15.3

75

kW

1.56 1.57 1.56 1.55 1.53 1.65 1.65 1.64 1.63 1.61 1.74 1.73 1.73 1.72 1.70

85

Total capacity

21.0 20.0 21.0 23.1 25.4 21.8 21.6 21.9 24.0 26.4 22.1 22.7 22.7 24.6 26.9

85

Sensible capacity 15.7 19.9 18.6 15.7 12.7 17.7 21.6 21.2 17.8 14.0 19.4 22.7 22.7 19.5 15.0

85

kW

1.74 1.73 1.74 1.73 1.72 1.82 1.82 1.82 1.82 1.81 1.91 1.91 1.91 1.90 1.89

95

Total capacity

20.1 19.3 20.1 22.2 24.4 20.8 20.9 20.9 23.0 25.3 21.2 21.9 21.9 23.4 25.8

95

Sensible capacity 15.3 19.2 18.1 15.3 12.3 17.3 20.8 20.8 17.4 13.6 19.0 21.9 21.9 19.1 14.6

95

kW

1.91 1.90 1.91 1.91 1.91 2.00 2.00 2.00 2.00 2.00 2.09 2.09 2.09 2.09 2.09

105

Total capacity

19.0 18.3 19.0 20.9 23.0 19.6 19.8 19.8 21.6 23.8 19.9 20.8 20.8 21.9 24.2

105

Sensible capacity 14.6 18.3 17.5 14.6 11.4 16.6 19.8 19.8 16.6 12.7 18.4 20.8 20.8 18.4 13.8

105

kW

2.08 2.07 2.08 2.09 2.10 2.17 2.17 2.17 2.19 2.20 2.27 2.27 2.27 2.28 2.29

115

Total capacity

18.0 17.9 17.9 19.3 20.7 18.8 19.5 19.1 20.0 21.2 19.2 20.8 20.3 20.2 20.7

115

Sensible capacity 13.9 17.8 16.8 13.4 9.8 16.3 19.5 19.1 15.8 11.1 18.5 20.8 20.3 17.9 12.0

115

kW

2.25 2.24 2.25 2.28 2.31 2.36 2.36 2.37 2.39 2.42 2.46 2.46 2.47 2.49 2.51

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

19

Johnson Controls Ducted Systems

Performance data - 2.5 ton

See the following tables for performance data for the YC330E2S11 unit.

Cooling performance data - 2.5 ton

Table 10: Cooling performance data - 2.5 ton

Air temperature entering Indoor CFM

800

1000

1200

outdoor unit (°F)

Indoor dry bulb 80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

(°F)

Indoor wet bulb 57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

(°F)

55

Total capacity

26.8 28.9 28.8 31.4 34.2 28.5 29.5 29.5 31.9 34.2 29.7 29.8 29.8 32.1 34.0

55

Sensible capacity 26.6 24.2 20.5 19.8 15.9 28.3 26.6 22.1 21.1 15.8 29.5 28.4 23.5 22.2 15.8

55

kW

1.57 1.55 1.56 1.54 1.52 1.64 1.62 1.63 1.61 1.61 1.71 1.70 1.70 1.69 1.69

65

Total capacity

27.9 25.7 27.9 30.5 33.3 28.7 27.5 28.8 31.4 34.2 29.3 28.6 29.3 32.1 34.8

65

Sensible capacity 19.6 25.5 23.3 19.5 15.7 21.3 27.3 25.5 21.2 16.7 22.7 28.5 27.5 22.6 17.5

65

kW

1.72 1.72 1.72 1.73 1.74 1.81 1.81 1.81 1.82 1.83 1.90 1.90 1.90 1.91 1.92

75

Total capacity

27.3 25.4 27.3 29.8 32.6 28.1 27.0 28.1 30.8 33.5 28.6 28.2 28.5 31.3 34.0

75

Sensible capacity 19.6 25.2 23.2 19.5 15.7 21.3 26.8 25.5 21.2 16.7 22.7 28.0 27.4 22.6 17.5

75

kW

1.93 1.92 1.93 1.94 1.95 2.02 2.02 2.02 2.03 2.05 2.11 2.11 2.11 2.13 2.14

85

Total capacity

26.5 24.9 26.5 29.0 31.8 27.2 26.4 27.2 29.9 32.6 27.7 27.5 27.5 30.4 33.1

85

Sensible capacity 19.4 24.7 23.0 19.4 15.6 21.1 26.2 25.3 21.1 16.6 22.5 27.3 27.3 22.5 17.4

85

kW

2.15 2.14 2.15 2.16 2.18 2.24 2.24 2.24 2.26 2.28 2.34 2.33 2.33 2.35 2.37

95

Total capacity

25.5 24.2 25.5 27.9 30.7 26.2 25.6 26.1 28.8 31.5 26.6 26.6 26.6 29.2 32.0

95

Sensible capacity 19.1 24.0 22.6 18.9 15.2 20.8 25.5 24.8 20.7 16.3 22.3 26.5 26.5 22.2 17.1

95

kW

2.38 2.37 2.38 2.40 2.42 2.48 2.47 2.48 2.50 2.52 2.57 2.57 2.57 2.59 2.61

105

Total capacity

23.9 23.1 23.8 26.3 28.9 24.5 24.4 24.4 27.0 29.6 24.8 25.3 25.3 27.4 30.0

105

Sensible capacity 18.4 22.9 21.9 18.3 14.4 20.2 24.2 24.2 20.1 15.5 21.7 25.2 25.2 21.7 16.4

105

kW

2.64 2.63 2.63 2.66 2.69 2.73 2.73 2.73 2.76 2.78 2.82 2.83 2.83 2.85 2.89

115

Total capacity

22.1 21.9 22.1 24.3 26.6 22.7 23.2 23.1 25.0 27.5 23.1 24.2 24.2 25.6 28.0

115

Sensible capacity 17.7 21.8 21.6 17.4 13.2 19.8 23.1 23.0 19.3 14.5 21.4 24.0 24.0 21.2 15.5

115

kW

2.95 2.96 2.95 2.97 2.99 3.04 3.05 3.05 3.07 3.10 3.13 3.13 3.14 3.17 3.22

20

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Performance data - 3 ton

See the following tables for performance data for the YC336E2S11 unit.

Cooling performance data - 3 ton

Table 11: Cooling performance data - 3 ton

Air temperature entering Indoor CFM

1000

1200

1400

outdoor unit (°F)

Indoor dry bulb 80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

(°F)

Indoor wet bulb 57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

(°F)

55

Total capacity

32.9 35.3 35.2 38.4 41.1 34.6 36.3 36.3 39.7 42.4 35.8 37.0 37.1 40.6 43.4

55

Sensible capacity 32.5 29.8 25.3 24.7 19.6 34.1 32.6 27.2 26.6 20.7 35.3 34.9 28.9 28.1 21.7

55

kW

1.94 1.95 1.95 1.95 1.96 2.03 2.04 2.04 2.04 2.05 2.12 2.13 2.14 2.14 2.15

65

Total capacity

34.5 32.3 34.6 37.6 40.9 35.4 33.9 35.3 38.5 41.7 35.9 35.1 35.8 39.1 42.4

65

Sensible capacity 24.8 31.8 29.2 24.7 20.2 26.5 33.4 31.7 26.3 21.2 28.0 34.6 33.7 27.8 22.0

65

kW

2.22 2.23 2.22 2.20 2.17 2.30 2.30 2.30 2.28 2.27 2.38 2.38 2.38 2.37 2.35

75

Total capacity

33.2 31.4 33.2 36.2 39.5 34.0 32.9 33.9 37.0 40.3 34.5 34.1 34.4 37.6 40.8

75

Sensible capacity 24.4 31.0 28.9 24.3 19.7 26.1 32.5 31.3 26.0 20.8 27.6 33.7 33.3 27.6 21.6

75

kW

2.41 2.42 2.41 2.41 2.40 2.50 2.50 2.50 2.49 2.48 2.59 2.58 2.58 2.58 2.57

85

Total capacity

31.7 30.3 31.7 34.7 37.9 32.4 31.8 32.3 35.5 38.6 32.9 32.9 32.9 36.0 39.0

85

Sensible capacity 23.8 29.9 28.4 23.8 19.2 25.6 31.4 30.8 25.5 20.2 27.2 32.4 32.5 27.1 21.1

85

kW

2.63 2.63 2.63 2.63 2.63 2.73 2.73 2.73 2.73 2.72 2.82 2.81 2.81 2.81 2.81

95

Total capacity

30.3 29.2 30.3 33.3 36.4 31.0 30.6 30.9 34.0 37.0 31.3 31.6 31.7 34.4 37.3

95

Sensible capacity 23.1 28.8 27.8 23.1 18.6 24.9 30.2 29.8 24.9 19.5 26.5 31.2 31.2 26.4 20.4

95

kW

2.93 2.93 2.93 2.94 2.94 3.02 3.02 3.02 3.02 3.03 3.11 3.11 3.11 3.11 3.12

105

Total capacity

28.7 27.9 28.7 31.6 34.5 29.3 29.2 29.3 32.2 35.0 29.7 30.2 30.2 32.5 35.4

105

Sensible capacity 22.4 27.5 26.9 22.4 17.9 24.2 28.8 28.9 24.0 18.8 25.7 29.8 29.8 25.6 19.7

105

kW

3.29 3.29 3.29 3.30 3.31 3.38 3.38 3.38 3.39 3.40 3.47 3.47 3.47 3.48 3.49

115

Total capacity

26.6 26.6 26.6 29.1 31.1 27.3 27.8 27.9 30.1 32.5 27.7 28.6 29.0 30.9 33.7

115

Sensible capacity 22.1 26.2 26.2 21.2 15.6 24.0 27.4 27.5 23.2 17.2 25.5 28.2 28.6 25.0 18.6

115

kW

3.73 3.74 3.74 3.76 3.78 3.80 3.80 3.81 3.83 3.86 3.87 3.86 3.88 3.90 3.94

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

21

Johnson Controls Ducted Systems

Performance data - 3.5 ton

See the following tables for performance data for the YC342E2S11 unit.

Cooling performance data - 3.5 ton

Table 12: Cooling performance data - 3.5 ton

Air temperature entering Indoor CFM

1200

1400

1600

outdoor unit (°F)

Indoor dry bulb 80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

(°F)

Indoor wet bulb 57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

(°F)

55

Total capacity

41.3 42.8 42.8 44.2 45.3 43.1 43.8 43.8 45.6 46.1 44.6 44.3 44.4 46.7 46.7

55

Sensible capacity 41.3 37.9 32.4 30.3 22.5 43.1 40.5 34.3 32.4 23.4 44.6 42.9 35.8 34.1 24.3

55

kW

2.24 2.21 2.22 2.17 2.16 2.32 2.30 2.30 2.27 2.25 2.41 2.39 2.40 2.38 2.35

65

Total capacity

39.9 37.5 40.0 43.9 47.9 40.9 39.2 40.9 44.8 48.8 41.5 40.5 41.3 45.4 49.4

65

Sensible capacity 30.4 37.5 36.0 30.4 24.7 32.3 39.2 38.7 32.2 25.8 33.9 40.5 41.0 33.8 26.7

65

kW

2.58 2.60 2.58 2.54 2.49 2.68 2.69 2.67 2.63 2.57 2.77 2.77 2.76 2.72 2.67

75

Total capacity

38.7 36.6 38.8 42.6 46.5 39.6 38.2 39.5 43.4 47.3 40.2 39.5 39.9 43.9 47.8

75

Sensible capacity 30.0 36.6 35.9 30.1 24.2 32.0 38.2 38.4 31.9 25.3 33.7 39.5 39.9 33.5 26.2

75

kW

2.88 2.89 2.87 2.83 2.78 2.97 2.98 2.97 2.93 2.87 3.06 3.07 3.06 3.01 2.96

85

Total capacity

37.3 35.5 37.2 41.0 44.8 38.1 37.1 37.7 41.7 45.4 38.6 38.3 38.4 42.2 45.9

85

Sensible capacity 29.4 35.5 35.2 29.4 23.6 31.4 37.1 37.6 31.3 24.6 33.2 38.3 38.4 33.0 25.6

85

kW

3.16 3.17 3.15 3.12 3.08 3.26 3.27 3.26 3.21 3.16 3.35 3.35 3.35 3.31 3.26

95

Total capacity

35.7 34.3 35.7 39.3 43.0 36.4 35.8 36.1 40.0 43.7 36.7 36.8 36.9 40.4 44.1

95

Sensible capacity 28.6 34.3 34.4 28.6 22.9 30.6 35.8 36.1 30.5 23.9 32.3 36.8 36.9 32.3 24.9

95

kW

3.50 3.50 3.49 3.47 3.43 3.60 3.60 3.60 3.56 3.51 3.69 3.69 3.69 3.65 3.61

105

Total capacity

33.8 32.9 33.6 37.3 40.9 34.4 34.2 34.3 37.8 41.4 34.7 35.3 35.3 38.2 41.7

105

Sensible capacity 28.0 32.9 33.3 27.9 22.1 30.0 34.2 34.3 29.8 23.1 31.6 35.3 35.3 31.5 24.1

105

kW

3.84 3.84 3.84 3.82 3.79 3.94 3.94 3.94 3.92 3.88 4.03 4.03 4.03 4.01 3.97

115

Total capacity

32.3 32.3 31.9 34.7 36.6 33.1 34.0 33.4 35.7 38.0 33.6 35.3 34.7 36.4 39.1

115

Sensible capacity 27.6 32.3 31.9 27.0 20.1 30.2 34.0 33.4 29.2 21.6 32.1 35.3 34.7 31.1 22.7

115

kW

4.20 4.18 4.21 4.21 4.23 4.30 4.29 4.31 4.31 4.32 4.41 4.40 4.42 4.42 4.42

22

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

Johnson Controls Ducted Systems

Performance data - 4 ton

See the following tables for performance data for the YC348E2S11 unit.

Cooling performance data - 4 ton

Table 13: Cooling performance data - 4 ton

Air temperature entering Indoor CFM

1350

1550

1750

outdoor unit (°F)

Indoor dry bulb 80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

(°F)

Indoor wet bulb 57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

(°F)

55

Total capacity

45.7 48.0 47.8 51.0 54.1 47.3 49.0 48.8 52.3 55.2 48.6 49.7 49.5 53.0 56.0

55

Sensible capacity 45.7 41.0 34.6 33.1 25.1 47.3 43.7 36.5 35.2 26.6 48.6 46.1 38.2 37.1 28.0

55

kW

2.69 2.70 2.70 2.71 2.72 2.78 2.79 2.79 2.80 2.82 2.87 2.88 2.88 2.90 2.91

65

Total capacity

46.2 43.5 46.5 50.5 54.7 47.2 45.3 47.3 51.4 55.7 47.8 46.6 47.9 52.1 56.4

65

Sensible capacity 33.8 43.5 40.2 33.6 26.8 35.7 45.3 42.9 35.4 27.9 37.3 46.6 45.1 37.0 28.8

65

kW

2.97 2.97 2.97 2.98 2.99 3.06 3.06 3.06 3.07 3.08 3.15 3.15 3.15 3.16 3.17

75

Total capacity

45.4 43.0 45.6 49.7 53.9 46.3 44.7 46.3 50.5 54.7 46.8 46.0 46.9 51.1 55.4

75

Sensible capacity 33.8 43.0 40.3 33.6 26.8 35.6 44.7 42.7 35.3 27.9 37.4 46.0 45.1 37.1 28.9

75

kW

3.29 3.28 3.29 3.30 3.31 3.38 3.37 3.38 3.39 3.40 3.47 3.47 3.47 3.48 3.49

85

Total capacity

44.3 42.1 44.2 48.3 52.6 45.0 43.6 45.0 49.2 53.4 45.4 44.9 45.4 49.7 53.9

85

Sensible capacity 33.5 42.1 39.9 33.3 26.5 35.3 43.6 42.3 35.1 27.6 36.9 44.9 44.5 36.8 28.6

85

kW

3.65 3.64 3.64 3.66 3.67 3.74 3.73 3.73 3.75 3.76 3.83 3.82 3.83 3.84 3.85

95

Total capacity

42.3 40.5 42.3 46.3 50.5 43.0 42.0 43.0 47.0 51.2 43.5 43.2 43.4 47.7 51.8

95

Sensible capacity 32.5 40.5 38.8 32.3 25.6 34.2 42.0 41.3 34.1 26.7 35.9 43.2 43.4 35.8 27.7

95

kW

4.07 4.07 4.07 4.09 4.10 4.16 4.16 4.16 4.18 4.19 4.25 4.25 4.25 4.27 4.28

105

Total capacity

40.1 38.8 40.0 43.9 47.9 40.6 40.2 40.4 44.6 48.6 41.0 41.3 41.4 45.0 49.0

105

Sensible capacity 31.6 38.8 37.9 31.4 24.7 33.4 40.2 40.3 33.2 25.8 35.1 41.3 41.4 35.0 26.8

105

kW

4.57 4.57 4.57 4.59 4.61 4.67 4.67 4.67 4.68 4.71 4.76 4.77 4.77 4.78 4.80

115

Total capacity

37.0 36.0 36.9 40.8 44.9 37.7 37.2 37.8 41.7 46.0 38.0 38.2 39.0 42.4 46.7

115

Sensible capacity 29.8 36.0 35.9 29.8 23.0 32.0 37.2 37.8 32.3 25.0 33.9 38.2 39.0 34.8 26.8

115

kW

5.23 5.26 5.23 5.22 5.20 5.30 5.32 5.31 5.30 5.29 5.40 5.39 5.40 5.37 5.37

YORK Technical Guide: LX Series YC3 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase

23

Johnson Controls Ducted Systems

Performance data - 5 ton

See the following tables for performance data for the YC360E2S11 unit.

Cooling performance data - 5 ton

Table 14: Cooling performance data - 5 ton

Air temperature entering Indoor CFM

1525

1725

1925

outdoor unit (°F)

Indoor dry bulb 80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

(°F)

Indoor wet bulb 57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

(°F)

55

Total capacity

50.9 55.5 55.1 59.9 64.5 53.0 56.5 56.1 60.5 64.2 54.5 57.1 56.6 60.2 63.6

55

Sensible capacity 50.9 45.3 38.7 38.3 31.2 53.0 47.6 40.3 39.7 31.4 54.5 49.7 41.7 40.7 31.3

55

kW

3.25 3.26 3.27 3.28 3.29 3.34 3.36 3.36 3.37 3.39 3.43 3.44 3.45 3.46 3.48

65

Total capacity

54.0 50.3 54.3 59.0 64.0 55.0 52.0 55.4 60.1 65.1 55.8 53.4 56.2 61.0 65.9

65

Sensible capacity 38.5 50.3 45.2 38.4 31.4 40.1 52.0 47.5 40.0 32.4 41.6 53.4 49.6 41.4 33.2

65

kW

3.57 3.55 3.56 3.58 3.58 3.66 3.64 3.65 3.67 3.67 3.76 3.75 3.75 3.77 3.77

75

Total capacity

53.4 49.8 53.6 58.4 63.5 54.4 51.5 54.7 59.5 64.5 55.2 52.9 55.4 60.3 65.4

75

Sensible capacity 38.5 49.8 45.2 38.4 31.5 40.1 51.5 47.5 40.1 32.5 41.7 52.9 49.7 41.6 33.4

75

kW

3.92 3.91 3.92 3.94 3.95 4.02 4.00 4.01 4.03 4.04 4.12 4.10 4.11 4.13 4.14

85

Total capacity

52.2 49.0 52.4 57.3 62.3 53.2 50.6 53.4 58.2 63.3 54.0 52.0 54.0 59.0 64.1

85

Sensible capacity 38.1 49.0 44.8 38.2 31.2 39.8 50.6 47.2 39.8 32.2 41.4 52.0 49.4 41.3 33.1

85

kW

4.35 4.33 4.35 4.36 4.38 4.44 4.43 4.44 4.46 4.47 4.55 4.53 4.54 4.56 4.57

95

Total capacity

50.2 47.5 50.4 55.2 60.1 51.1 49.0 51.2 56.0 61.0 51.8 50.3 51.9 56.7 61.7

95

Sensible capacity 37.2 47.5 44.0 37.3 30.3 38.9 49.0 46.4 38.9 31.3 40.5 50.3 48.5 40.4 32.2

95

kW

4.86 4.84 4.85 4.89 4.90 4.96 4.94 4.96 4.98 4.99 5.05 5.04 5.05 5.07 5.08

105

Total capacity

47.3 45.6 47.5 51.9 56.6 48.0 47.1 48.1 52.6 57.5 48.5 48.3 48.7 53.2 58.0

105

Sensible capacity 36.4 45.6 43.3 36.4 29.1 38.2 47.1 45.9 38.2 30.2 39.8 48.3 48.0 39.8 31.2

105

kW

5.42 5.40 5.42 5.45 5.47 5.52 5.50 5.51 5.54 5.56 5.61 5.60 5.60 5.63 5.66

115

Total capacity

43.9 42.8 44.1 47.9 52.3 44.6 44.1 44.7 48.6 53.2 45.1 45.2 45.7 49.2 53.7

115

Sensible capacity 34.8 42.8 41.7 34.8 27.3 36.7 44.1 44.4 36.9 28.8 38.7 45.2 45.7 39.0 30.1

115

kW

6.12 6.09 6.09 6.11 6.09 6.21 6.17 6.17 6.21 6.23 6.29 6.23 6.26 6.32 6.44

Third-party trademarks

Third-Party Trademarks Notice: For information about third-party trademarks, refer to the relevant company websites.


Subject to change without notice. Published in U.S.A. Copyright © 2025 by Johnson Controls. All rights reserved. Johnson Controls Ducted Systems

