Comfort-Aire Century MXP48/60C1A Series Submittal Data
Air Handler Heat Pump System
General Information
Location: | Approval: | ||
---|---|---|---|
Engineer: | Date: | ||
Submitted to: | Construction: | ||
Submitted by: | Unit #: | ||
Reference: | Drawing #: |
Indoor Unit Specifications
Dimension (W×D×H) | 21.61 x 21.50 x 27.80 inches (549×546×706 mm) |
---|---|
Package (W×D×H) | 31.69 x 25.59 x 26.57 inches (805×650×675 mm) |
Net/Gross Weight | 44/52 lbs (43.9/52.2 kg) |
Outdoor Unit Specifications
Compressor Type | ROTARY |
---|---|
Compressor Model | KTQ420D1UMU |
Refrigerant | R454B |
Refrigerant Oil Charge(mL) | 1400 |
Refrigerant Oil | VG74 |
Outdoor Air Flow (Max) (CFM) | 3,037 (MXP48/60C1A), 4,503 (MXP48/60D1A) |
Outdoor Noise Level (dBA) | 65 (MXP48/60C1A), 63 (MXP48/60D1A) |
Dimension (W×D×H) | 38.58 x 16.34 x 38.39 inches (980×415×975 mm) for MXP48/60C1A 37.48 x 16.34 x 52.48 inches (952×415×1,333 mm) for MXP48/60D1A |
Package (W×D×H) | 45.08 x 19.68 x 42.52 inches (1,145×500×1,080 mm) for MXP48/60C1A 43.11 x 16.34 x 58.27 inches (1,095×415×1,480 mm) for MXP48/60D1A |
Net/Gross Weight | 187.17/218.48 lbs (84.9/99.1 kg) for MXP48/60C1A 212.30/244.49 lbs (96.3/110.9 kg) for MXP48/60D1A |
Efficiency
Cooling | Heating | |
---|---|---|
SEER2 | 15.3 (MXP48/60C1A), 15.6 (MXP48/60D1A) | HSPF2-4 / |
EER2 | 9.8 | COP / |
Performance of Cooling
Cooling (Btu/hr) | |
---|---|
Rated Capacity | 44,000 (MXP48/60C1A), 52,000 (MXP48/60D1A) |
Min/Max Capacity | 17,600~52,000 (MXP48/60C1A) 20,400~56,000 (MXP48/60D1A) |
Moisture Removal (L/h) | 6.31 (MXP48/60C1A) 8.1 (MXP48/60D1A) |
Standard Operating Range (°F/°C) | -13~122 (-25~50) |
Rated Cooling Conditions: | Indoor: 80°F DB/67°F WB Outdoor: 95°F DB/75°F WB |
Performance of Heating
Heating (Btu/hr) | |
---|---|
1. @ 47°F Rated | / |
2. @ 47°F Min/Max Capacity | / |
3. @ 17°F Rated | / |
4. @ 5°F Rated: Capacity / COP | / |
5. @ 5°F Max: Capacity | / |
Standard Operating Range (°F/°C) | / |
1. Rated Heating Conditions: | Indoor: 70°F DB/60°F WB Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions: | Indoor: 70°F DB/60°F WB Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency | Indoor: 70°F DB/60°F WB Outdoor: 5°F DB/5°F WB |
Electrical
Indoor Power Supply | 24V,60Hz, 1Ph |
---|---|
Indoor MCA 115V/(208/230V) | / |
Indoor MOP | / |
Outdoor Power Supply | 208/230,60Hz, 1Ph |
Outdoor MCA | 36 (MXP48/60C1A) 37 (MXP48/60D1A) |
Outdoor MOP | 40 |
Communication Wiring | AWG 20-2 |
Compressor RLA | 27 (MXP48/60C1A) 27.5 (MXP48/60D1A) |
Outdoor Fan Motor RLA | 2.4 |
Outdoor Fan Motor W | / |
Indoor Fan Motor RLA | / |
Indoor Fan Motor W | / |
System Power Input @ Cooling (W) | 4,490(1,510~5,500) (MXP48/60C1A) 5,306(1,530~5,960) (MXP48/60D1A) |
System Power Input @ Heating (W) | / |
MCA: Min. circuit amps (A) | |
RLA: Rated load amps (A) | |
MOCP: Max. over current protection (A) | |
W: Fan motor rated output (W) |
Piping
Throttle type(Indoor) | EXV |
---|---|
Throttle type(Outdoor) | / |
Liquid Size | 9.52mm(3/8in) |
Gas Size | 19mm(3/4in) |
Max. Piping Length(ft/m) | 246(75) |
Max. Height Difference(ft/m) | 98(30) |
Max. Pre-charged Length(ft/m) | 24.6(7.5) |
Refrigerant Pre-charged Amount(oz/kg) | 141.10(4.00) (MXP48/60C1A) 169.32(4.80) (MXP48/60D1A) |
Additional Charge of Refrigerant((oz/ft)/(g/m)) | 0.7(65) |
Connection Method | Flared |
Indoor Unit Dimensions Table
Model/Dimensions | MXP18/24B1A | MXP18/24A1A | MXP24/36A1A | MXP24/36B1A | MXP24/36C1A | MXP48/60C1A | MXP48/60D1A | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
inch | mm | inch | mm | inch | mm | inch | mm | inch | mm | inch | mm | inch | mm | |
A Model Height | 18 | 457 | 18 | 457 | 23-5/16 | 592 | 23-9/16 | 599 | 24 | 611 | 24 | 611 | 28 | 711 |
B Model Width | 17-1/2 | 445 | 14-1/2 | 368 | 14-1/2 | 368 | 17-1/2 | 445 | 21 | 534 | 21 | 534 | 24-1/2 | 622 |
C Supply Air Opening Width | 16-3/16 | 411 | 13-1/4 | 336 | 13-1/4 | 336 | 16-3/16 | 411 | 19-3/4 | 502 | 19-3/4 | 502 | 23-1/4 | 591 |
D Return Air Opening Width | 14-5/16 | 380 | 11-15/16 | 303 | 11-15/16 | 303 | 14-15/16 | 380 | 19-1/2 | 498 | 19-1/2 | 498 | 23-1/8 | 587 |
E Condensate Drains Height | 1-7/16 | 38 | 1-7/16 | 38 | 1-7/16 | 38 | 1-7/16 | 38 | 2-3/16 | 55 | 2-3/16 | 55 | 2-3/16 | 55 |
F Liquid Line Height | 11-3/8 | 290 | 11-3/8 | 290 | 17-5/16 | 455 | 16-3/8 | 417 | 17-1/2 | 445 | 17-1/2 | 445 | 21-7/16 | 545 |
Features
- Multi-position installation: horizontal (left or right), vertical (up or down)
- Aluminum Coil
- R454B refrigerant sensor
- Easy Maintenance
- Multiple control options available:
- Two-way communication wired controller with built-in WiFi: 120N(X6W)
- Third-Party 24V Thermostat
Installation Instructions for Outdoor Unit
Ensure adequate clearance around the outdoor unit for proper operation and maintenance:
- 20 inches (500mm) or more clearance is required on the front and sides of the unit if these areas are clear.
- 20 inches (500mm) or more clearance is required on any 2 sides (left, right, and rear) of the unit if these areas are clear.
- 4 inches (100mm) or more clearance is required on the remaining sides.
- 14 inches (350mm) or more clearance is required at the rear of the unit.
Related Documents
![]() |
ComfortAire Century MXP48/60D1A Air Handler Heat Pump System Submittal Data Submittal data for the ComfortAire Century MXP48/60D1A series air handler heat pump systems, including specifications, dimensions, and performance data for both indoor and outdoor units. |
![]() |
Comfort-Aire Century Cased Coil Owner's & Installation Manual Comprehensive owner's and installation manual for the Comfort-Aire Century Cased Coil, covering safety precautions, parts, maintenance, troubleshooting, and installation guidelines. |
![]() |
Comfort-Aire VCD-Series Cold Weather Heat Pump - Specifications and Features Detailed information on the Comfort-Aire VCD-Series cold-climate air source heat pump, including features, technical specifications, and dimensional drawings for various models. |
![]() |
Comfort Aire VHP18CA-1 4-Way Cassette Heat Pump System: Submittal Data and Specifications Detailed submittal data, specifications, performance metrics, and installation guidelines for the Comfort Aire Century VHP18CA-1 4-Way Cassette Heat Pump System. |
![]() |
Comfort Aire Century CXP1560SA-1 Air Handler Heat Pump System Submittal Data Submittal data for the Comfort Aire Century CXP1560SA-1 Air Handler Heat Pump System, including specifications for cooling, heating, electrical, piping, and dimensions. |
![]() |
Comfort-Aire Century Air Handler Heat Pump System Submittal Data CXP1518SA-1 Submittal data for the Comfort-Aire Century Air Handler Heat Pump System, model CXP1518SA-1, detailing specifications for cooling, heating, electrical, and piping, along with indoor and outdoor unit dimensions and installation clearances. |
![]() |
ComfortAire Century CXP1548SA-1 Air Handler Heat Pump System Submittal Data This document provides submittal data for the ComfortAire Century CXP1548SA-1 Air Handler Heat Pump System, including detailed specifications, performance data, dimensions, and electrical information. |
![]() |
Comfort-Aire Century SWP30S1A Wall Mount Air Handler PSC Motor Parts List Official parts list for the Comfort-Aire Century SWP30S1A Wall Mount Air Handler with PSC Motor. Details components, part codes, and quantities for servicing and maintenance. |