Installation Guide: Variable Frequency Drive Conversion TR1 to TR170 for RTAC Condenser Fans

Models: 120 to 500 ton (RTAC)

Drives: DRV03113, DRV03114

⚠️ WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

April 2020

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

  • WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
  • CAUTION: Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
  • NOTICE: Indicates a situation that could result in equipment or property-damage only accidents.

WARNING: Proper Field Wiring and Grounding Required!

Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

WARNING: Personal Protective Equipment (PPE) Required!

Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

  • Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
  • When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
  • If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

⚠️ WARNING

Follow EHS Policies! Failure to follow instructions below could result in death or serious injury.

  • All Trane personnel must follow the company's Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
  • Non-Trane personnel should always follow local regulations.

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

  • TR170 VFD Program Parameters section is moved to Set the VFD Programming Parameters chapter.
  • Updated Modify Parameters section.
  • Updated Reset Parameters Back to Factory Defaults section.

General Information

About This Manual

The step-by-step instructions outlined in this manual describe the procedures required to successfully retrofit a Trane TR1 variable frequency drive (VFD) on RTAC™ air-cooled chillers to a Trane TR170 VFD. Drives are required for low and wide ambient operation. The Trane TR1 VFD was originally installed for RTAC design sequences W0 through 1C. An affected RTAC will have two, three, or four condenser fan drives. The number of drives will match the number of compressors. For example, a three-compressor RTAC will have three condenser fan drives.

The installation instructions in this manual are divided into three general topic areas:

  • Removal of existing TR1 VFD.
  • Installation of replacement TR170 VFD.
  • TR170 programming of parameters.

Follow start-up and troubleshooting procedures outlined in the service manuals of the unit and/ or the literature that is included with this TR170 control.

Tools Required

Very few tools are required to perform this installation. A service technician with a well-stocked tool chest should have the right tools to perform the job.

Materials Required

Two TR170 drives are available. Select the correct drive replacement kit based on the existing unit voltage as shown in the following table.

Unit Voltage Drive Part Number Drive Description
200/60/3
230/60/3
DRV03113 DRIVE; TR170 1.5HP 208VAC
380/60/3
400/50/3
460/60/3
575/60/3
DRV03114 DRIVE; TR170 1.5HP 460VAC

In addition to the drives, some field provided material will be required. A partial list of material is provided here to help you plan ahead and to avoid material shortages at the job site.

  • Wire, #16 AWG--Control wire will be required to make the connections between components.
  • Wire markers will be required to identify field wiring.
  • Wire nuts and splicers may be required if splicing wires in the control panel.
  • Cable ties help to "clean up" wiring runs.
  • The blanket heater used with the Trane TR1 drive is sized incorrectly for use with a Trane TR170 drive. The part number for the TR170 blanket heater is HTR16716.
  • Four-compressor units and circuit 1 of three-compressor units use a single LLID relay to enable both drives on a circuit. RTAC designs incorporating TR1 VFDs use a paralleled enable signals to start the drives. This configuration is not applicable to the TR170 drives. An additional relay with the following minimum specifications is required: 2 pole, normally open, 24-VDC contacts, and 120-VAC coil. Relay RLY00636 and socket BAS00154 are recommended.

Removing the Existing VFD and Components

This section describes the procedure used to remove a Trane TR1 VFD from its panel assembly in the RTAC fan control panels.

Programming parameters are supplied with the VFD that must be set based on unit specifications. See "TR170 VFD Program Parameters," p. 10.

⚠️ WARNING: Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer's literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

For additional information regarding the safe discharge of capacitors, see PROD-SVB06x-EN or PROD-SVB06x-FR.

  1. Turn off power to the machine, water pumps, and any field provided control power.
  2. Secure all disconnect switches following lockout/tagout safety procedures.
  3. Open the control panel doors and verify all power has been removed.
  4. Record the following information from the condenser fan motor nameplate. This information will be needed during drive configuration:
    • Motor Power
    • Motor Voltage
    • Motor Frequency
    • Motor Current
    • Motor Nominal Speed
  5. Verify the condenser fan motor is inverter duty rated. Inverter duty motors provide a more robust system when combined with variable speed drives. In the event the condenser fan is not inverter duty rated, contact the local Trane Parts Center with the unit model number or serial number for replacement options.
  6. Locate the existing TR1 VFD unit enclosure for RTAC units as shown in the following figures.

Figure 1. RTAC Panel Configuration

A diagram showing the layout of components within an RTAC control panel, labeled "RTAC CONTROL PANEL 1". It includes various numbered connection points (e.g., 1K12, 1T56, 1029) and indicates the location of the "Low Ambient Option Condenser Fan VFD".

Figure 2. Typical RTAC 200 ton panel illustration and low ambient option VFD location

A photographic illustration showing the interior of an RTAC unit's control panel, highlighting the location of the "Low Ambient Option Condenser Fan VFD" within the larger electrical assembly.

  1. Disconnect power supply wires from VFD connection points 91, 92, 93, 95 (L1, L2, L3, GND respectively).
  2. Disconnect output power wires from VFD connection points 96, 97, 98, 99 (T1, T2, T3, GND respectively).
  3. Disconnect all control wires from the TR1 VFD itself and note the connection point numbers.
Drive Connection Description Drive Designator
1U28 1U29 2U28 2U29
12 +24 VDC 151A 151B 651A 651B
18 Digital Input (RUN) 152A 152B 652A 652B
53 Analog Input 0-10 (Speed Command) 119A 122A 122A(a) or 619A(b) 622A
55 Common 128A 129A 129A(a) or 628A(b) 629A
1 Relay 1 [0] Common 121A 123A 123A(a) or 620A(b) 623A
3 Relay 1 [0] Normally Closed (Alarm) 120A 124A 124A(a) or 621A(b) 624A

(a) Two-compressor applications (b) Three and four-compressor applications

  • The blanket heater used with the Trane TR1 drive is sized incorrectly for use with a Trane TR170 drive. Disconnect the heater wires at 1TB7-3,4 or 2TB7-3,4.
  • Locate and remove the four (4) fasteners securing the TR1 drive to its back panel after all cables and power supply wiring have been disconnected.
  • Remove existing drive and heater blanket.

Installing TR170 VFD and Components

Remove Trane TR170 drive from the box, verify the VFD model number, and complete the following procedures.

Install the TR170 Drive

  1. Attach the new drive heater, HTR16716, to the side of the new drive. If another drive is present in the panel, the heater should be placed on the side of the drive that will not face the other drive. The heater has adhesive pre-applied to one side. Remove the protective film from the heater and press it against the side of the drive.
  2. Hold the drive up to the back plate and mark the mounting hole locations on the backplate. The Trane TR170 drive has a mounting hole pattern different than the original drive.
  3. Drill a 3/16" hole at each marked location. Be careful to protect other electrical components from metal shavings and clean all metal shavings from the enclosure when drilling is completed.
  4. Line up the TR170 on the mounting hole-pattern and fasten the drive with the fasteners retained from the original drive to the back panel.

Wire the Power Supply and Controls to the TR170

The TR1 and TR170 have the same connection point numbers, however, a four-compressor unit or circuit 1 of a three-compressor unit requires an additional relay. These units will require the unit schematics to be marked up or replaced. Schematics document numbers may be found in "Wiring Diagram Matrix," p. 20. Print a copy from e-Library (if accessible) or contact the local Trane representative to obtain a copy.

  1. Reconnect power supply wires to VFD connection points 91, 92, 93, 95 (L1, L2, L3, GND respectively) and output power wires to VFD connection points 96, 97, 98, 99 (T1, T2, T3, GND respectively).
  2. Reconnect all control wires to the TR170 VFD according to the connection point numbers noted during TR1 removal. The TR1 and TR170 have the same connection point numbers. (See the "Typical Control Wires" table in the manual for common control wires and their connection point numbers.)
  3. Connect the new drive blanket heater wiring to 1TB7-3,4 or 2TB7-3,4.

Installing the Drive On a Four-Compressor Unit or Circuit 1 of a Three-Compressor Unit (RTAC)

If you are installing the drive on a four-compressor unit or circuit 1 of a three-compressor unit, an addition relay is required.

  1. Mount this relay and base on the controls backplate.
  2. Label the relay 1K9 if installed in control panel 1 or 2K9 if installed in control panel 2.
  3. Make the wiring modifications presented in the following table:
Table 3. Intermediate relay wiring
Wire Number Description of New Function Control Panel 1 Control Panel 2
Original Connections New Connections Original Connections New Connections
151A +24 VDC 1U28-12 to 1TB6-6 1U28-12 to 1K9-1 2U28-12 to 2TB6-6 2U28-12 to 2K9-1
152A Digital Input (RUN) 1U28-18 to 1TB6-7 1U28-18 to 1K9-2 2U28-18 to 2TB6-7 2U28-18 to 2K9-2
151B +24 VDC 1U29-12 to 1TB6-6 1U29-12 to 1K9-3 2U29-12 to 2TB6-6 2U29-12 to 2K9-3
152B Digital Input (RUN) 1U29-18 to 1TB6-7 1U29-18 to 1K9-4 2U29-18 to 2TB6-7 2U29-18 to 2K9-4
151C Control Power Hot 1U15-J2-12 to 1TB6-6 1U15-J2-12 to 1TB5-3 (Node 62) 2U15-J2-12 to 2TB6-6 2U15-J2-12 to 2TB5-3 (Node 562)
152C Fan Run Signal 1U15-J2-10 to 1TB6-7 1U15-J2-10 to 2K9-Coil 2U15-J2-10 to 2TB6-7 2U15-J2-10 to 2K9-Coil
Field Provided Control Power Neutral 1K9-Coil to 1TB5-12(Node 63) 2K9-Coil to 2TB5-12(Node 563)

TR170 VFD Program Parameters

Drives are shipped with generic settings. These settings must be updated to reflect the drive application. The following table defines the parameters that must be modified for the Trane TR170 drives used in condenser fan applications on RTAC products.

Important: Pressing the "MENU" button once will enter the drive parameter wizard. DO NOT use the parameter wizard. The parameter wizard does not access all the required parameters and may cause drive errors. Pressing the "MENU" button twice will allow access to all parameters. ALWAYS use this method.

Table 4. TR170 VFD Drive Parameters
Parameter Number Parameter Description RTAC Setting Units
0-03 Regional Settings North America for 60 Hz, International for 50 Hz --
0-06 Grid Type Depends on Grid Type --
0-40 [Hand on] Key on LCP Disable (0) --
1-20 Motor Power (Motor Specific) kW
1-22 Motor Voltage (Motor Specific) V
1-23 Motor Frequency (Motor Specific) Hz
1-24 Motor Current (Motor Specific) A
1-25 Motor Nominal Speed (Motor Specific) RPM
1-71 Start Delay 3 s
1-72 Start Function DC Hold (0) --
1-73 Flying Start Enabled (1) --
1-82 Min Speed for Function at Stop [Hz] 0.1 Hz
1-90 Motor Thermal Protection ETR Trip 1 (4) --
2-00 DC Hold/Motor Preheat Current Default Value %
2-02 DC Braking Time Default Value s
2-10 Brake Function Off (0) --
3-03 Maximum Reference 50/60* --
3-16 Reference 2 Source No function (0) --
3-17 Reference 3 Source No function (0) --
3-41 Ramp 1 Ramp Up Time 5 s
3-42 Ramp 1 Ramp Down Time 20 s
4-10 Motor Speed Direction Clockwise (0) --
4-12 Motor Speed Low Limit [Hz] 3 Hz
4-14 Motor Speed High Limit [Hz] 50/60* Hz
4-18 Current Limit If p122 = 380V then 115 Else 125 %
5-12 Terminal 27 Digital Input No operation (0) --
5-40 Function Relay Alarm (9) --
6-10 Terminal 53 Low Voltage 0 V
6-14 Terminal 53 Low Ref./Feedb. Value 0 --
6-15 Terminal 53 High Ref./Feedb. Value 50/60* --
14-01 Switching Frequency 5 kHz
14-12 Function at Mains Imbalance De-rate (3) --
14-20 Reset Mode Auto Reset x10 (10) --
14-21 Automatic Restart Time 30 s
14-50 RFI Filter Off (0) --

Note: *60 or 50Hz for Pueblo Production, 50Hz for Charmes production. Otherwise, set for maximum speed rating of motor/fan.

Table 5. TR170 VFD Drive Parameters

The following table defines the complete set of parameters for the TR170 VFD drives used in condenser fan applications on low ambient option IPAK II products.

Parameter Number Parameter Description Ipak II Setting Units
0-03 Regional Settings North America for 60 Hz, International for 50 Hz --
0-06 Grid Type Depends on Grid Type --
0-40 [Hand on] Key on LCP Disable (0) --
1-20 Motor Power 1.1 (8) (Motor Specific) kW
1-22 Motor Voltage 460 (Motor Specific) V
1-23 Motor Frequency 60 (Motor Specific) Hz
1-24 Motor Current 2.7 (Motor Specific) A
1-25 Motor Nominal Speed 1140 (Motor Specific) RPM
1-71 Start Delay Default Value s
1-72 Start Function Default Value --
1-73 Flying Start Enabled (1) --
1-82 Min Speed for Function at Stop [Hz] 0.1 Hz
1-90 Motor Thermal Protection ETR Trip 1 (4) --
2-00 DC Hold/Motor Preheat Current 0 %
2-02 DC Braking Time 0 s
2-10 Brake Function AC Brake is active (2) --
3-03 Maximum Reference 60 --
3-16 Reference 2 Source No function (0) --
3-17 Reference 3 Source No function (0) --
3-41 Ramp 1 Ramp Up Time 10 s
3-42 Ramp 1 Ramp Down Time 10 s
4-10 Motor Speed Direction Clockwise (0) --
4-12 Motor Speed Low Limit [Hz] 22 Hz
4-14 Motor Speed High Limit [Hz] 60 Hz
4-18 Current Limit 137 %
5-12 Terminal 27 Digital Input Coast and reset inverse (3) --
5-40 Function Relay Default Value --
6-10 Terminal 53 Low Voltage 0 V
6-14 Terminal 53 Low Ref./Feedb. Value 22 --
6-15 Terminal 53 High Ref./Feedb. Value 60 --
14-01 Switching Frequency 5 kHz
14-12 Function at Mains Imbalance De-rate (3) --
14-20 Reset Mode Auto reset x3 (3) --
14-21 Automatic Restart Time 5 s
14-50 RFI Filter Off (0) --

Note: *60 or 50Hz for Pueblo Production, 50Hz for Charmes production. Otherwise, set for maximum speed rating of motor/fan.

Table 6. TR170 VFD Drive Parameters

The following table defines the complete set of parameters for the TR170 VFD drives used in condenser fan applications on CGAM products.

Parameter Number Parameter Description CGAM Setting Units
0-03 Regional Settings North America for 60 Hz, International for 50 Hz --
0-06 Grid Type Depends on Grid Type --
0-40 [Hand on] Key on LCP Disable (0) --
1-20 Motor Power (Motor Specific) kW
1-22 Motor Voltage (Motor Specific) V
1-23 Motor Frequency (Motor Specific) Hz
1-24 Motor Current (Motor Specific) A
1-25 Motor Nominal Speed (Motor Specific) RPM
1-71 Start Delay 3 s
1-72 Start Function DC Hold (0) --
1-73 Flying Start Default Value --
1-82 Min Speed for Function at Stop [Hz] 0.1 Hz
1-90 Motor Thermal Protection ETR Trip 1 (4) --
2-00 DC Hold/Motor Preheat Current Default Value %
2-02 DC Braking Time Default Value s
2-10 Brake Function Off (0) --
3-03 Maximum Reference 50/60 --
3-16 Reference 2 Source No function (0) --
3-17 Reference 3 Source No function (0) --
3-41 Ramp 1 Ramp Up Time 5 s
3-42 Ramp 1 Ramp Down Time 20 s
4-10 Motor Speed Direction Clockwise (0) --
4-12 Motor Speed Low Limit [Hz] 5/6 Hz
4-14 Motor Speed High Limit [Hz] 50/60 Hz
4-18 Current Limit If p122 = 460V then 115 Else 110 %
5-12 Terminal 27 Digital Input No operation (0) --
5-40 Function Relay Alarm (9) --
6-10 Terminal 53 Low Voltage 1 V
6-14 Terminal 53 Low Ref./Feedb. Value 5/6 --
6-15 Terminal 53 High Ref./Feedb. Value 50/60 --
14-01 Switching Frequency 5 kHz
14-12 Function at Mains Imbalance De-rate (3) --
14-20 Reset Mode Auto Reset x10 (10) --
14-21 Automatic Restart Time 30 s

Note: *60 or 50Hz for Pueblo Production, 50Hz for Charmes production. Otherwise, set for maximum speed rating of motor/fan.

Set the VFD Programming Parameters

Complete the following tasks to set and verify the TR170 parameters listed in the tables in "TR170 VFD Program Parameters," p. 15 section.

Power Up the VFD

  1. When all components have been mounted and wired, close all electrical enclosures.
  2. Restore machine power.
  3. Place the unit in "STOP" to prevent unintended operation.
  4. Open the cover or door over the drive and verify the drive has powered up. The drive cooling fan may be operating, even if the unit is in standby mode.

⚠️ WARNING: PPE for Arc/Flash Required!

Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.

Reset Parameters Back to Factory Defaults

Note: In the event the drive parameters are inaccessible or the drive display fails, a "hard reset" may be accomplished by holding "OK" and "Menu" buttons while cycling the drive power.

To reset all programming parameters back to the factory defaults:

  1. Go to parameter 14–22 Operation Mode.
  2. Press OK.
  3. Select 2 "Initialization".
  4. Press OK.
  5. Cut off the main supply and wait until the display turns off.
  6. Reconnect the main supply.
  7. Ensure parameter 14–22 Operation Mode has reverted back to "Normal Operation".

Notes:

  • Step 5 resets the drive to the default factory settings. The program parameters listed in Table 7, p. 16, Table 8, p. 17 and Table 9, p. 18 will need to be verified or changed as described in the previous Modify Parameters procedure.
  • Some of the parameters listed in the Table are motor specific. Due to various motors and efficiencies available, use only the values stamped on the specific motor nameplate. Do not use the Unit nameplate values.
  • A backup copy of the current setup may be saved to the LCP before changing parameters or resetting the drive. See LCP Copy in the VFD Operating Instructions for details.

Modify Parameters

Please refer to BAS-SVP16*-EN (TR150 and TR170 Programming Guide), or the most recent version, for complete programming information.

Notes:

  • Pressing the "MENU" button once will enter the drive parameter wizard. The parameter wizard does not access all the required parameters.
  • To access ALL parameters, press the "MENU" button twice.
  • The parameters are set by different levels. Click OK to access Level 1 and Level 2.
  • The default setting for Parameter 5-12 is Coast inverse which will cause a drive error on Products that do not need that function. Verify Parameter 5-12 is set per Table 7, p. 16, Table 8, p. 17 and Table 9, p. 18 for the given Product you are installing the drive into (parameter 5-12 will be set to either Coast Inverse or No Function depending on your Product). Products that utilize the Coast inverse function will have a control wire going to terminal 27 on the drive.

Perform the following steps to modify each parameter:

  1. On the first power up of the drive, a parameter wizard may appear. Press the Back button to leave the wizard screen.
  2. Press the Main Menu button. (Press the Back button if the main menu does not display.)
  3. Use the Up and Down buttons to find the parameter menu group (first part of parameter number).
  4. Press OK.
  5. Use the Up and Down buttons to select the correct parameter sub-group, indicated by the first digit of the second part of the parameter number.
  6. Press OK.
  7. Use the Up and Down buttons to select the specific parameter.
  8. Press OK.
  9. Use the navigation buttons to move to a different digit within a parameter setting. The highlighted area indicates the digit selected for modification.
  10. Use the Up and Down buttons to adjust the digit.
  11. Press Cancel to disregard the change, or press OK to accept the change and enter the new setting.
  12. Repeat steps 1 through 11 for each menu selection setting in the parameters table.
  13. After verifying that the VFD(s) are operating properly, press the STOP key at the Human Interface Module to stop the unit operation.
  14. Follow the applicable steps in the "Final Unit Checkout" section in the unit Installation, Operation, Maintenance Manual (IOM) to return the unit to its normal operating mode.

Note: If a problem with a VFD occurs, ensure that the programmed parameters listed for condenser fan VFD (see the Table 7, p. 16, Table 8, p. 17 and Table 9, p. 18) have been set before replacing the drive.

Copying Parameters to Multiple Drives

If you are installing multiple drives, the drive LCP (local control panel) can be used to copy parameters from one drive to another. This method can save time and reduce errors.

Uploading Data to the LCP

  1. Go to 0-50 LCP copy.
  2. Press OK.
  3. Select All from LCP.
  4. Press OK.
  5. A progress bar shows the uploading process
  6. Press Hand on to return to normal operation.

Remove the LCP from the configured drive and install it on the unconfigured drive.

Downloading Data from the LCP

  1. Go to 0-50 LCP copy
  2. Press OK
  3. Select All from LCP
  4. Press OK.
  5. A progress bar shows the uploading process
  6. Press Hand on to return to normal operation.

Wiring Diagram Matrix

Table 10. TR170 VFD IntelliPak II™ wiring schematics and connection diagrams

Wiring Diagram Number Description
2313-0831SCHEMATIC, POWER - 90-105 TON - STANDARD WITH LOW AMBIENT
2313-0832SCHEMATIC, POWER - 90-105 TON - WITH SUPPLY VFD AND WITH LOW AMBIENT
2313-0833SCHEMATIC, POWER - 90-105 TON - WITH EXHAUST OR RETURN VFD AND WITH LOW AMBIENT
2313-0834SCHEMATIC, POWER - 90-105 TON - WITH SUPPLY AND EXHAUST OR RETURN VFD & W/ LOW AMBIENT
2313-0835SCHEMATIC, POWER - 90-105 TON - STANDARD WITH LOW AMBIENT
2313-0836SCHEMATIC, POWER - 90-105 TON - WITH SUPPLY VFD AND WITH LOW AMBIENT
2313-0837SCHEMATIC, POWER - 90-105 TON - WITH EXHAUST OR RETURN VFD AND WITH LOW AMBIENT
2313-0838SCHEMATIC, POWER - 90-105 TON - WITH SUPPLY AND EXHAUST OR RETURN VFD & W/ LOW AMBIENT
2313-0843SCHEMATIC, POWER - 120-150 TON - STANDARD WITH LOW AMBIENT
2313-0844SCHEMATIC, POWER - 120-150 TON - WITH SUPPLY VFD AND WITH LOW AMBIENT
2313-0845SCHEMATIC, POWER - 120-150 TON - WITH EXHAUST OR RETURN VFD AND WITH LOW AMBIENT
2313-0846SCHEMATIC, POWER - 120-150 TON - WITH SUPPLY AND EXHAUST OR RETURN VFD & W/LOW AMBIENT
2313-0847SCHEMATIC, POWER - 120-150 TON - STANDARD WITH LOW AMBIENT
2313-0848SCHEMATIC, POWER - 120-150 TON - WITH SUPPLY VFD AND WITH LOW AMBIENT
2313-0849SCHEMATIC, POWER - 120-150 TON - WITH EXHAUST OR RETURN VFD AND WITH LOW AMBIENT
2313-0850SCHEMATIC, POWER - 120-150 TON - WITH SUPPLY AND EXHAUST OR RETURN VFD & W/LOW AMBIENT
2313-0839SCHEMATIC, POWER - 90-105 TON - STANDARD WITH LOW AMBIENT
2313-0840SCHEMATIC, POWER - 90-105 TON - WITH SUPPLY VFD AND WITH LOW AMBIENT
2313-084190-105 TON - WITH EXHAUST OR RETURN VFD AND WITH LOW AMBIENT SCHEMATIC, POWER
2313-0842SCHEMATIC, POWER - 90-105 TON - WITH SUPPLY AND EXHAUST OR RETURN VFD & W/ LOW AMBIENT
2313-0851SCHEMATIC, POWER - 120-150 TON - STANDARD WITH LOW AMBIENT
2313-0852SCHEMATIC, POWER - 120-150 TON - WITH SUPPLY VFD AND WITH LOW AMBIENT
2313-0853SCHEMATIC, POWER - 120-150 TON - WITH EXHAUST OR RETURN VFD AND WITH LOW AMBIENT
2313-0854SCHEMATIC, POWER - 120-150 TON - WITH SUPPLY AND EXHAUST OR RETURN VFD & W/LOW AMBIENT
1213-1563CONNECTION, CONTROL BOX - 90-105T, STANDARD W/ LOW AMBIENT
1213-1564CONNECTION, CONTROL BOX - 90-105T, W/SUPPLY VFD W/ LOW AMBIENT
1213-1565CONNECTION, CONTROL BOX - 90-105T, W/EXH/RTN VFD W/ LOW AMBIENT
1213-1566CONNECTION, CONTROL BOX - 90-105T, W/SUP & EXH/RTN VFD W/ LOW AMBIENT
1213-1567CONNECTION, CONTROL BOX - 90-105T, STANDARD W/ LOW AMBIENT
1213-1568CONNECTION, CONTROL BOX - 90-105T, W/SUPPLY VFD W/ LOW AMBIENT
1213-1569CONNECTION, CONTROL BOX - 90-105T, W/EXH/RTN VFD W/ LOW AMBIENT
1213-1570CONNECTION, CONTROL BOX - 90-105T, W/SUP & EXH/RTN VFD W/ LOW AMBIENT
1213-1571CONNECTION, CONTROL BOX - 120-150T, STANDARD W/ LOW AMBIENT
1213-1572CONNECTION, CONTROL BOX - 120-150T, W/SUPPLY VFD W/ LOW AMBIENT
1213-1573CONNECTION, CONTROL BOX - 120-150T, W/EXH/RTN VFD W/ LOW AMBIENT
1213-1574CONNECTION, CONTROL BOX - 120-150T, W/SUP & EXH/RTN VFD W/ LOW AMBIENT
1213-1575CONNECTION, CONTROL BOX - 120-150T, STANDARD W/ LOW AMBIENT
1213-1576CONNECTION, CONTROL BOX - 120-150T, W/SUPPLY VFD W/ LOW AMBIENT
1213-1577CONNECTION, CONTROL BOX - 120-150T, W/EXH/RTN VFD W/ LOW AMBIENT
1213-1578CONNECTION, CONTROL BOX - 120-150T, W/SUP & EXH/RTN VFD W/ LOW AMBIENT

Note: Wiring diagrams are available via e-Library (if accessible) or contact the local Trane representative to obtain a copy.

Table 11. TR170 VFD CGAM™ wiring schematics and connection diagrams

Wiring Diagram Number Description
2309-2075SCHEMATIC; CGAM, S, V, W

Note: Wiring diagrams are available via e-Library (if accessible) or contact the local Trane representative to obtain a copy.

Table 12. TR170 VFD RTAC™ wiring schematics and connection diagram

Wiring Diagram Number Description
2309-2097RTAC; 2 COMPRESSOR
2309-4621RTAC; 3 COMPRESSOR, X-LINE STARTER
2309-4622RTAC; 3 COMPRESSOR, WYE-DELTA STARTER
2309-4623RTAC; 4 COMPRESSOR, X-LINE STARTER
2309-4624RTAC; 4 COMPRESSOR, WYE-DELTA STARTER

Note: Wiring diagrams are available via e-Library (if accessible) or contact the local Trane representative to obtain a copy. See the Series R Air-Cooled Helical Rotary Liquid Chillers Wiring Manual (RTAC-SVE01*-EN) (Refer to version E or subsequent versions).

Notes

Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.

Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

BAS-SVN032B-EN 29 Apr 2020 Supersedes BAS-SVN032A-EN (November 2017) ©2020 Trane

PDF preview unavailable. Download the PDF instead.

BAS-SVN032B-EN 04292020

Related Documents

Preview Trane Condenser Fan Control Retrofit Installation Instructions
Installation instructions for the Trane Condenser Fan Control Retrofit kits CNT07652 and CNT07653 for RTAA Air-Cooled Chillers and RTAC Air-Cooled Condensers. This document provides detailed steps for replacing the variable speed drive, including safety warnings, required tools, and parameter settings.
Preview Trane Condenser Fan Control Retrofit Installation Instructions for RTAC Chillers
Detailed installation instructions for retrofitting condenser fan controls on Trane RTAC Air-Cooled Chillers using kits CNT07650 and CNT07651. Covers general information, pre-installation steps, control panel modifications, wiring, and start-up procedures.
Preview Trane Serie R RTAC: Enfriadora de Líquido de Alto Rendimiento
Descubra la enfriadora de líquido Trane RTAC Serie R, diseñada para alta fiabilidad, eficiencia energética y rendimiento superior en aplicaciones industriales y comerciales. Conozca sus características y especificaciones.
Preview Trane AFDK Adaptive Frequency Drive Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Trane AFDK Adaptive Frequency Drives, including Tracer AdaptiView or CH530/CH531 control systems. Covers safety warnings, environmental considerations, component identification, and troubleshooting.
Preview Trane RTAC Rotary Chiller Tracer AdaptiView Display Upgrade Kit Installation Instructions
This document provides detailed installation instructions for the Trane Tracer AdaptiView Display Upgrade Kit for RTAC Rotary Chillers, replacing older DynaView systems. It covers safety, required tools, step-by-step procedures, and integration options.
Preview Trane Variable Frequency Drive Installation Instructions: TR1 to TR200 Conversion
Comprehensive installation instructions for converting Trane TR1 Variable Frequency Drives (VFDs) to TR200 VFDs in Commercial Self Contained Signature and Modular Series Units. Covers S**F and S**G models.
Preview BACnet Communication Interface for Chiller (BCI-C) Integration Guide
This guide provides information on the BACnet Communication Interface for Chillers (BCI-C), a non-programmable communications module that allows HVAC equipment to communicate on a BACnet network. It covers the BACnet protocol, rotary switches and LEDs, data point definitions, and chiller model compatibility.
Preview Trane BCI2-C Installation Instructions for BACnet Communication Interface for Chillers
Comprehensive installation guide for the Trane BACnet Communication Interface for Chillers (BCI2-C), detailing setup, configuration, and integration with HVAC systems for models RTWD, RTAC, and CGAM.