Installation Instructions

Variable Frequency Drive Conversion TR1 to TR200

Commercial Self Contained Signature and Modular Series Units

Model Numbers: Units with factory installed VFDs and units with VFD or VFD with bypass options: S**F 20 to 110 tons, S**G 30 to 35 tons

This document applies to service offering applications only.

SAFETY WARNING: Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

Advisory Definitions:

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

Proper Field Wiring and Grounding Required!

Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

Personal Protective Equipment (PPE) Required!

Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

Follow EHS Policies!

Failure to follow instructions below could result in death or serious injury.

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

Document updated to reflect Service Offering number.

General Information

The instructions in this manual describe procedures required to successfully retrofit a TR1 on 20 ton to 110 ton Signature Series and 20 ton to 35 ton Modular Series Commercial Self Contained (CSC) units to a Trane TR200 VFD drive. For help selecting the proper parts for this work, refer to General Service Bulletin, VFD Selection List for TR1 to TR200 (PART-SVB25*-EN).

The instructions in this manual are divided into the following sections:

Follow start-up and troubleshooting procedures outlined in the Installation, Operation, and Maintenance manuals and/or the literature included with the TR200 VFD.

Tools Required

Removal and Replacement for S**F Units

  1. Locate the existing TR1 VFD in the VFD panel on the right, front side of the CSC unit. The VFD is mounted inside this panel on a back panel. The replacement actions will consist of disconnecting wiring, removing the VFD and back panel, installing a replacement back panel, installing the new VFD, and reconnecting the wiring.
  2. Confirm power is removed from the unit. See Figure 1, p. 6, Figure 2, p. 6, and Figure 3, p. 7 for typical wiring diagrams for power and control signals for units with and without bypass. Table 1, p. 7 lists typical control and power wires to be disconnected. Disconnect the wires and record the wire numbers as a reference to be used when reconnecting the new VFD. Units without bypass will not have all wires connected.

WARNING: Hazardous Voltage w/Capacitors! Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN or PROD-SVB06*-FR.

Figure 1 Description: Typical power and control wiring for S**F units without bypass.

Figure 2 Description: Typical power wiring for S**F units with bypass.

Figure 3 Description: Typical control wiring for S**F units with bypass.

Table 1: Typical wires for S**F units

VFD ConnectionDescriptionWire Number
91-L1Phase A line input
92-L2Phase B line input
93-L3Phase C line input
99-PEGND
96-UPhase A VFD output
97-VPhase B VFD output
98-WPhase C VFD output
53 A INSpeed reference
55 COM A INSpeed reference common
Chassis GndSpeed reference shield
12+24V
13+24V
18Run/stop
27Coasting stop
KeypadKeypad
01Aux relay
02Aux relay

3. Disconnect the power and control wires from the VFD.

WARNING: Heavy Objects! Failure to follow instructions below could result in unit dropping which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.

  1. After all wiring has been disconnected, attach a lifting device to the VFD to support it during removal. The weight of the VFDs varies from 40 to 175 lbs. Follow safe procedures for lifting and removing the VFD and back panel assembly. Locate the six nuts holding the VFD back panel to the enclosure and remove the nuts. Save the nuts for use during mounting of the new TR200. Remove the VFD and back panel assembly.
  2. Locate the new TR200 VFD and verify the part number for the replacement is correct. Refer to General Service Bulletin, VFD Selection List for TR1 to TR200 (PART-SVB25*-EN).
  3. Locate the new back panel in the kit. From the back of the panel, install the four screws and lock washers supplied in the kit into the threaded holes of the adapter panel that align with the mounting points on the TR200 drive.
  4. Install the replacement panel in the CSC cabinet and secure to the six mounting studs with the nuts removed from the TR1 panel.
  5. Weights of the replacement VFDs varies between 20 and 140 lbs. Verify the weight of the TR200 VFD prior to lifting. Using proper lifting procedures, lift the TR200 into the enclosure. Attach the TR200 drive to the replacement panel with the four KEPS nuts supplied in the kit.
  6. Remove the TR1 VFD Local Control Panel (LCP) from the VFD enclosure door.
  7. Install the TR200 keypad in the cutout on the enclosure door using Figure 4, p. 8 as a guide.

Figure 4 Description: Typical control wiring for S**F units with bypass.

11. Reconnect the wiring to the TR200. The connection points on the TR200 VFD are the same as the connection points on the TR1 VFD although the locations of the terminals may be different.

Removal and Replacement for S**G Without Bypass

  1. Locate the existing TR1 VFD. It will most likely be mounted on a wall near the CSC unit. The replacement actions will consist of disconnecting wiring, removing the VFD and back panel, installing a replacement back panel, installing the new VFD, and reconnecting the wiring. The bypass components and enclosure will remain in place.
  2. Confirm power is removed from the unit. See Figure 5, p. 9 and Figure 6, p. 9 for typical wiring diagrams for power and control signals for units without bypass. Table 2, p. 9 lists typical control and power wires to be disconnected. Disconnect the wires and record the wire numbers as a reference to be used when reconnecting the new VFD.

WARNING: Hazardous Voltage w/Capacitors! Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN or PROD-SVB06*-FR.

Figure 5 Description: Typical power wiring for S**G units without bypass.

Figure 6 Description: Typical control wiring for S**G units without bypass.

Table 2: Typical wires for S**G units without bypass

VFD ConnectionDescriptionWire Number
91-L1Phase A line input
92-L2Phase B line input
93-L3Phase C line input
99-PEGND
96-UPhase A VFD output
97-VPhase B VFD output
98-WPhase C VFD output
53 A INSpeed reference
55 COM A INSpeed reference common
Chassis GndSpeed reference shield
12+24V
18Run/stop
27Coasting stop
KeypadKeypad

3. Disconnect the power and control wires from the VFD.

WARNING: Heavy Objects! Failure to follow instructions below could result in unit dropping which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.

  1. After all wiring has been disconnected, attach a lifting device to the VFD to support it during removal. The weight of the VFDs varies from 40 to 175 lbs. Follow safe procedures for lifting and removing the VFD and back panel assembly. Locate the hardware holding the VFD to its back panel and remove the hardware. Save the hardware for use during mounting of the new VFD. Remove the VFD.
  2. Locate the new TR200 VFD and verify the part number for the replacement is correct. Refer to General Service Bulletin, VFD Selection List for TR1 to TR200 (PART-SVB25*-EN).
  3. Locate the new back panel in the kit. From the back of the panel, install the four screws and lock washers supplied in the kit into the threaded holes of the adapter panel that align with the mounting points on the TR200 drive.
  4. Attach the adapter panel to the VFD assembly mounted on the wall and secure to the existing mounting points using the TR1 mounting hardware.
  5. Weights of the replacement VFDs varies between 51 and 99 lbs. Verify the weight of the VFD prior to lifting. Using proper lifting procedures lift the TR200 VFD into position. Attach the TR200 drive to the replacement panel with the four KEPS nuts supplied in the kit.
  6. Reconnect the wiring to the TR200. The connection points on the TR200 VFD are the same as the connection points on the TR1 VFD although the location of the terminals may be different.

Removal and Replacement for S**G With Bypass

  1. Locate the existing TR1 VFD and bypass assembly. The VFD will be replaced; all components inside and wiring to/from the bypass enclosure will not be changed.
  2. Confirm power is removed from the unit. Disconnect the power and control wires from the VFD. See Figure 7, p. 11 and Figure 8, p. 12 for typical wiring diagrams for power and control signals that connect to the VFD. Table 3, p. 12 lists typical control and power wires to be disconnected. Disconnect the wires and record the wire numbers as a reference to be used when reconnecting the new VFD.

WARNING: Hazardous Voltage w/Capacitors! Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN or PROD-SVB06*-FR.

Figure 7 Description: Typical power wiring for S**G units with bypass.

Figure 8 Description: Typical control wiring for S**G units with bypass.

Table 3: Typical wires for S**G units with bypass

VFD ConnectionDescriptionWire Number
91-L1Phase A line input
92-L2Phase B line input
93-L3Phase C line input
99-PEGND
96-UPhase A VFD output
97-VPhase B VFD output
98-WPhase C VFD output
53 A INSpeed reference
55 COM A INSpeed reference common
Chassis GndSpeed reference shield
12+24V
18Run/stop
27Coasting stop
KeypadKeypad

3. Remove the three sheet metal parts (front cover, cover support bracket, and angle bracket) enclosing the wire below the TR1 drive. Save the hardware used to attach the angle bracket to the side of the bypass enclosure.

WARNING: Heavy Objects! Failure to follow instructions below could result in unit dropping which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.

  1. After all wiring has been disconnected and the wire cover parts have been removed, attach lifting device to VFD to support it during removal. The weight of the VFDs varies from 40 to 175 lbs. Follow safe procedures for lifting and removing the VFD and back panel assembly. Locate the screws holding the VFD to its back panel and remove the screws. Save the screws for use during mounting of the new VFD. Remove the VFD.
  2. Locate the new TR200 VFD kit and verify the part number for the replacement is correct. Refer to General Service Bulletin, VFD Selection List for TR1 to TR200 (PART-SVB25*-EN).
  3. From the back of the panel, install the four screws and lock washers supplied in the kit into the threaded holes of the drive adapter panel that align with the mounting points on the TR200 drive.
  4. Attach the adapter panel to the bypass panel and secure with the hardware removed from the TR1 drive.
  5. Weights of the replacement VFDs varies between 14 and 175 lbs. Verify the weight of the VFD prior to lifting. Using proper lifting procedures lift the TR200 VFD into position. Attach the TR200 drive to the adapter panel with the four KEPS nuts supplied in the kit.
  6. For TR200 drives below 11 amps, install the conduit adapter plate supplied in the kit over the rectangular hole on the side of the bypass enclosure using the screws removed original angle bracket. Insert three of the flexible conduit connectors supplied in the kit into the conduit adapter cover. Attach the remaining conduit connectors into the TR200 drive. Trim the flexible conduit supplied in the kit to reach between the connectors. Attach on end of the three flexible conduits tubes to the connectors on the bypass enclosure and route the input, output and control wiring through separate tubes. Attach the tubes to the connectors on the TR200 drive.
  7. For TR200 drives above 11 amps, install the replacement wire cover sheet metal parts supplied in the kit using the 3 to 32 thread rolling screws supplied in the kit.
  8. Reconnect the wiring to the TR200. The connection points on the TR200 VFD are the same as the connection points on the TR1 VFD although the location of the terminals may be different.

TR200 VFD Programming Information

The following parameters must be programmed into the VFD prior to operation. Refer to Installation and Operation - TR200 (BAS-SVX19*-EN) for complete programming information and instructions on how to navigate the TR200 local control panel menus.

Table 4: CSC special VFD parameter settings

ParameterDescriptionTrane setting
0-01Language[22] English US
0-03Regional settings[1] North America
0-22Display line 1.3 small[1611] Power [hp]
1-21Motor power [HP]Reference motor nameplate HP
1-22Motor voltageReference motor nameplate voltage
1-24Motor currentReference motor nameplate FLA
1-25Motor nominal speedReference motor nameplate rated speed
1-73Flying start[1] Enabled
3-41Ramp 1 ramp-up time30 Sec.
3-42Ramp 1 ramp-down time30 Sec.
4-12Motor speed low limit [Hz]22 Hz
5-12Terminal 27, digital input[2] Coast inverse
6-14Terminal 53 low ref./ feedb. value22 Hz
14-01Switching frequencySet to max per X code drawing
14-12Function at mains imbalance[3] Derate
14-60Function at over temperature[1] Derate
14-21Automatic restart time3 Sec.
Models: TR200 Variable Frequency Drive, TR200, Variable Frequency Drive, Frequency Drive, Drive

File Info : application/pdf, 16 Pages, 1.65MB

PDF preview unavailable. Download the PDF instead.

SO-SVN020A-EN 08312023

References

Acrobat Distiller 23.0 (Windows)

Related Documents

PreviewTrane IntelliPak Commercial Self-Contained Programming Guide
A comprehensive programming guide for Trane IntelliPak Commercial Self-Contained units, covering Signature Series (20-110 Ton) and Modular Series (20-35 Ton). This manual details unit operation, setup, configuration, and diagnostics through the Human Interface (HI) panel.
PreviewTrane AFDK Adaptive Frequency Drive Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Trane AFDK Adaptive Frequency Drives, including Tracer AdaptiView or CH530/CH531 control systems. Covers safety warnings, environmental considerations, component identification, and troubleshooting.
PreviewTrane TR170 VFD Installation Guide for RTAC Condenser Fans
Comprehensive installation guide for replacing Trane TR1 Variable Frequency Drives (VFDs) with TR170 VFDs on RTAC™ air-cooled chillers. Covers removal, installation, wiring, and parameter programming.
PreviewTrane Integrated Variable or Multi Speed Control Drive Replacement Installer's Guide
Comprehensive installer's guide for replacing Trane Integrated Variable or Multi Speed Control Drives. Covers safety warnings, required tools and parts, terminology, step-by-step removal and installation procedures, thermal grease application, final inspection, and drive board return instructions.
PreviewTrane IntelliPak Commercial Self-Contained Modular Series Installation and Diagnostic Manual
Comprehensive guide for installing, operating, and troubleshooting Trane IntelliPak Commercial Self-Contained Modular Series units (20-35 Ton), models SCWG, SIWG, SCRG, and SIRG, 'BO' and later design sequences. Covers general information, installation procedures, control options, model number explanations, and handling.
PreviewTrane Condenser Fan Control Retrofit Installation Instructions for RTAC Chillers
Detailed installation instructions for retrofitting condenser fan controls on Trane RTAC Air-Cooled Chillers using kits CNT07650 and CNT07651. Covers general information, pre-installation steps, control panel modifications, wiring, and start-up procedures.
PreviewTrane BACnet Communication Interface 2 for IntelliPak and CSC Units Data Sheet
Product data sheet for the Trane BACnet Communication Interface 2 (BCI2-I), a module that enables heating, ventilation, and air-conditioning (HVAC) equipment, including IntelliPak and Commercial Self-contained (CSC) units, to communicate on a BACnet network. It details features, benefits, specifications, and physical dimensions.
PreviewTrane Precedent™ High Efficiency Packaged Rooftop Heat Pumps: Product Catalog
Discover the Trane Precedent™ series of high-efficiency packaged rooftop heat pumps, designed for exceptional reliability and advanced comfort control. This catalog details features, specifications, and applications for units ranging from 12.5 to 25 tons, highlighting Trane's commitment to quality and performance in commercial HVAC solutions.