BACnet™ Communication Interface for Chiller (BCI-C)
Integration Guide
for RTWD/RTUD, RTHD, RTAC, and CGAM
Overview
The BACnet™ Communication Interface for Chillers (BCI-C) is comprised of a Tracer™ UC400 controller with interface software. It is a non-programmable communications module that allows heating, ventilation, and air-conditioning (HVAC) equipment to communicate on a BACnet communications network.
This guide provides:
- A brief overview of the BACnet protocol
- An explanation of the BCI-C device rotary switches and LEDs
- Data point configuration property definitions
- Tables listing object data points
- Additional resources
- A glossary of terms
Note: Users of this guide should have basic knowledge of BACnet protocol. For more detailed information about this protocol, visit the company web site listed under "Additional Resources," p. 25.
BACnet Protocol
The Building Automation and Control Network (BACnet and ANSI/ASHRAE Standard 135-2004) protocol is a standard that allows building automation systems or components from different manufacturers to share information and control functions. BACnet provides building owners the capability to connect various types of building control systems or subsystems together for a variety of reasons. In addition, multiple vendors can use this protocol to share information for monitoring and supervisory control between systems and devices in a multi-vendor interconnected system.
The BACnet protocol identifies standard objects (data points) called BACnet objects. Each object has a defined list of properties that provide information about that object. BACnet also defines a number of standard application services that are used to access data and manipulate these objects and provides a client/server communication between devices. For more information on BACnet protocol, refer to "Additional Resources," p. 25.
BACnet Testing Laboratory (BTL) Certification
The BCI-C supports the BACnet communication protocol and has been designed to meet the requirements of the application-specific control profile. For more details, refer to the BTL web site at www.bacnetassociation.org.
Rotary Switches and LEDs
This section provides information about the BCI-C rotary switches and LED displays.
Rotary Switches
There are three rotary switches on the front of the BCI-C device that are used to define a three-digit address when the BCI-C is installed on a BACnet communications network. The three-digit address setting is the BACnet MAC address.
Note: All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet.
Figure 1. Setting rotary switches
[Diagram showing rotary switches and their settings before and after adjustment]
Important: Each device on the BACnet/MSTP link must have a unique rotary switch setting, otherwise, communication problems will occur.
[Illustration of a screwdriver being used to set rotary switches]
Note: For details on setting the baud rate, BACnet Device ID, and units of measure, refer to the section, Configuring the BCI-C in the BACnet Communication Interface (BCI-C) Field Kit Installation Guide, RF-SVN02.
LEDs Description, Behavior, and Troubleshooting
There are 15 LEDs on the front of the BCI-C unit. However, LEDs BO1 through BO9 are not used for the BCI-C controller. Figure 2 shows the locations of each LED. The following table provides a description of each LED activity, an indication or troubleshooting tips for each, and any notes.
Figure 2. LED locations
[Diagram showing the locations of LEDs on the BCI-C unit]
LED Name | Activities | Indication or Troubleshooting Tip (Denoted in Bullets) | Notes |
---|---|---|---|
Marquee LED | Shows solid green when the unit is powered and no problems exist | Indicates normal operation | |
Marquee LED | Shows solid red when the unit is powered, but represents low power or a malfunction |
|
|
Marquee LED | Shows blinking red when an alarm exists | Alarm; when an alarm is triggered, for example, when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2 | |
LED not lit | Indicates power is OFF or there is a malfunction |
|
|
Link and IMC | TX blinks green | Blinks at the data transfer rate when the unit transfers data to other devices on the link | TX LED: Regardless of connectivity or not, this LED will constantly blink as it continually looks for devices to communicate to. |
Link and IMC | RX blinks yellow | Blinks at the data transfer rate when the unit receives data from other devices on the link | |
Link and IMC | LED not lit |
|
LED not lit: Determine if, for example, a Tracer™ SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller. Also determine if the communication status shows down all of the time. |
Service | Shows solid green | Indicates controller is operating normally, or TechView is in Binding View and commanding to the BCI-C to turn On the LED | Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID. |
Service | Blinks green | Indicates controller is not accessing application software | What is Boot Code? When the UC400 is placed into boot code, the system will not run any applications such as trending, scheduling, and TGP2 runtime. |
Service | LED not lit | Restore; using TU service tool | |
Binary 01 to Binary 09 | LED not lit | Not Used |
BACnet Data Points and Configuration Property Definitions
The BCI-C device allows certain models of Trane chillers with CH530 controls to communicate with BACnet systems and devices using BACnet MS/TP. This section includes information about:
- BACnet protocol implementation conformance statement (PICS)
- Object types: descriptions and configuration (refer to Table 2, p. 12)
- BACnet protocol: data link layers, device address binding, networking options, and character sets
- Object data points and configurations
BACnet Protocol Implementation Conformance Statement (PICS)
Standardized Device Profile (Annex L)
Profile Description | Supported Profile |
---|---|
BACnet Advanced Application Controller (B-AAC) | ✔️ |
BACnet Application Specific Controller (B-ASC) | ✔️ |
BACnet Building Controller (B-BC) | ✔️ |
BACnet Operator Workstation (B-OWS) | |
BACnet Smart Actuator (B-SA) | |
BACnet Smart Sensor (B-SS) |
Interoperability Building Blocks (Annex K)
Data Sharing Description | Supported BIBB |
---|---|
Data Sharing-COV-B (DS-COV-B) | ✔️ |
Data Sharing-ReadProperty-A (DS-RP-A) | ✔️ |
Data Sharing-ReadProperty-B (DS-RP-B) | ✔️ |
Data Sharing-ReadPropertyMultiple-B (DS-RPM-B) | ✔️ |
Data Sharing-WriteProperty-A (DS-WP-A) | ✔️ |
Data Sharing-WriteProperty-B (DS-WP-B) | ✔️ |
Data Sharing-WriteProperty Multiple-B (DS-WPM-B) | ✔️ |
Alarm and Event Management Description | Supported BIBB |
Alarm and Event-ACKI-B (AE-ACK-B) | ✔️ |
Alarm and Event-Alarm Summary-B (AE-ASUM-B) | ✔️ |
Alarm and Event-Enrollment Summary-B (AE-ESUM-B) | ✔️ |
Alarm and Event-Information-B (AE-INFO-B) | ✔️ |
Alarm and Event-Notification Internal-B (AE-N-I-B) | ✔️ |
Trending Description | Supported BIBB |
---|---|
Trending-Automated Trend Retrieval-B (T-ATR-B) | ✔️ |
Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B) | ✔️ |
Device Management Description | Supported BIBB |
Device Management-Backup and Restore-B (DM-BR-B) | ✔️ |
Device Management-Device Communication Control-B (DM-DCC-B) | ✔️ |
Device Management-Dynamic Device Binding-A (DM-DDB-A) | ✔️ |
Device Management-Dynamic Device Binding-B (DM-DDB-B) | ✔️ |
Device Management-Dynamic Object Binding-B (DM-DOB-B) | ✔️ |
Device Management-List Manipulation-B (DM-LM-B) | ✔️ |
Device Management-Object Creation and Deletion-B (DM-OCD-B) | ✔️ |
Device Management-Private Transfer-A (DM-PT-A) | ✔️ |
Device Management-Private Transfer-B (DM-PT-B) | ✔️ |
Device Management-Reinitialize Device-B (DM-RD-B) | ✔️ |
Device Management-TimeSynchronization-B (DM-TS-B) | ✔️ |
Segmentation Capability
Segmentation Description | Supported Segment |
---|---|
Segmented Requests/ Window Size: 1 | ✔️ |
Segmented Responses/ Window Size: 1 | ✔️ |
Object Types
Object Type | Required Properties Read | Properties Written(a) | Optional Properties Read | Ability to Create | Ability to Delete |
---|---|---|---|---|---|
Analog Input |
|
|
|
Yes | Yes, only user created objects |
Analog Output |
|
|
|
Yes | Yes, only user created objects |
Analog Value |
|
|
|
Yes | Yes, only user created objects |
Binary Input |
|
|
|
Yes | Yes, only user created objects |
Binary Output |
|
|
|
Yes | Yes, only user created objects |
Binary Value |
|
|
|
Yes | Yes, only user created objects |
Device |
|
|
|
None | None |
Event Enrollment |
|
|
|
Yes | Yes, only user created objects |
Multistate Input |
|
|
|
Yes | Yes, only user created objects |
Multistate Output |
|
|
|
Yes | Yes, only user created objects |
Multistate Value |
|
|
|
Yes | Yes, only user created objects |
Notification Class |
|
|
None | Yes | Yes, only user created objects |
Trend |
|
|
|
Yes | Yes, only user created objects |
BACnet Protocol
Data Link Layer Options
Data Link Layer Description | Supported |
---|---|
ANSI/ATA 878.1, 2.5 Mb ARCNET (Clause 8) | |
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), Baud Rate(s) | |
BACnet IP, (Annex J) | |
BACnet IP, (Annex J), Foreign Device | |
ISO 8802-3, Ethernet (Clause 7) (10Base2, 10Base5, 10BaseT, Fiber) | |
LonTalk, (Clause 11), Medium | |
MS/TP Master (Clause 9), Baud Rate(s): 9600, 19200, 38400, 76800, and 115200 @1.5% Nominal Baud Rate | ✔️ |
MS/TP Slave (Clause 9), Baud Rate(s) | |
Other | |
Point-to-Point, EIA 232 (Clause 10), Baud Rate(s): 9600, 19200, 38400 | |
Point-to-Point, Modem (Clause 10), Baud Rate(s): 9600, 19200, 38400 |
Device Address Binding
Device Address Binding | Supported? |
---|---|
Static Device Binding Supported | ✔️ |
Networking Options
Networking Descriptions | Supported Option |
---|---|
Annex H, BACnet Tunneling | |
BACnet/IP Broadcast Management Device (BBMD) | |
Does the BBMD Support Registrations by Foreign Devices? | |
Router |
Character Sets
Indicates support for multiple characters sets, but does not imply that all character sets are supported simultaneously. Maximum supported string length is 64 bytes (any character set).
Character Set Descriptions | Supported |
---|---|
ANSI X3.4 | |
IBM/Microsoft DBCS | |
ISO 10646 (UCS-4) | ✔️ |
ISO 10646 (UCS2) | ✔️ |
ISO 8859-1 | ✔️ |
JIS C 6226 |
Object and Diagnostic Data Points and Corresponding Chiller Models
For quick reference, the following tables are listed and sorted two different ways. Tables 3 through 9 are listed by input/output type and sorted by object identifier. These tables provide the user with the units type for each object type. Table 9, p. 22 is sorted by object name and provides a complete list of object names, types, values/ranges, and descriptions. Not all points are available to the user. The available data points are defined during self-configuration and are dependent on the type of equipment. Listed at the bottom of tables 3 through 8 are specific footnotes that correspond to either specific chiller models or object states that are identified by a larger dot or boldface text.
Note: The last four columns in each table identifies which chiller model corresponds with each object name.
Table 3. Analog Output
Object Identifier | Object Name | Description | Dimensionality | Valid Range | Relinq Default | RTWD/RTUD | RTHD | RTAC | CGAM |
---|---|---|---|---|---|---|---|---|---|
Analog Output 1 | Chilled Water Setpoint | Desired leaving water temperature if chiller is in cooling mode. | Temperature | 0°F to 75°F (-17.8°C to 23.8°C) | 44°F (6.7°C) | • | • | • | |
Analog Output 2 | Current Limit Setpoint | Sets the maximum capacity that the chiller can use. | Percent | 0% to 120% | 100% | • | • | • | |
Analog Output 3 | Demand Limit Setpoint | Sets the maximum capacity that the chiller can use. | Percent | 0% to 120% | 100% | • | • | • | |
Analog Output 4 | Hot Water Setpoint | Desired leaving water temperature if chiller is in heating mode. | Temperature | 80°F to 140°F (26.7°C to 60°C) | 120°F (48.9°C) | (a) | (a) | (a) | (b) |
Analog Output 5 | Base Loading Setpoint | Capacity level to which the chiller should control when base loading is active. | Percent | 0% to 100% | 50% | • | • | • | • |
(a) Leaving condenser water temperature control.
(b) Hot water control with heat pumps in heating mode.
Table 4. Analog Input
Object Identifier | Object Name | Description | Dimensionality | RTWD/RTUD | RTHD | RTAC | CGAM |
---|---|---|---|---|---|---|---|
Analog Input, 1 | Active Cool/Heat Setpoint | Active chiller water or hot water setpoint. | Temperature | • | • | • | • |
Analog Input, 2 | Active Current Limit Setpoint | Active capacity current limit setpoint. | Percent | • | • | • | |
Analog Input, 3 | Active Demand Limit Setpoint | Active demand limit setpoint. | Percent | • | • | • | |
Analog Input 4 | Active Base Loading Setpoint | Value of base loading setpoint currently being used by the chiller. | Percent | • | • | • | • |
Analog Input, 5 | Actual Running Capacity | Level of capacity that the chiller is currently running at. | Percent | • | • | • | • |
Analog Input, 6 | Evaporator Refrigerant Pressure- Ckt1 | Circuit 1 evaporator refrigerant pressure. | Pressure | • | • | • | |
Analog Input, 7 | Suction Pressure- Ckt 1 | Circuit 1 suction pressure. | Pressure | • | • | • | |
Analog Input, 8 | Suction Pressure- Ckt 1 | Circuit 1 suction pressure. | Pressure | • | • | • | |
Analog Input, 9 | Evaporator Refrigerant Pressure- Ckt 2 | Circuit 2 evaporator refrigerant pressure. | Pressure | • | • | • | |
Analog Input, 10 | Suction Pressure- Ckt 2 | Circuit 2 suction pressure. | Pressure | • | • | • | |
Analog Input, 11 | Suction Pressure- Ckt 2 | Circuit 2 suction pressure. | Pressure | • | • | • | |
Analog Input, 12 | Evaporator Saturated Refrigerant Temperature- Ckt 1 | Circuit 1 evaporator refrigerant temperature. | Temperature | • | • | • | |
Analog Input, 13 | Suction Saturated Refrigerant Temperature- Ckt 1 | Circuit 1 suction refrigerant temperature. | Temperature | • | • | • | |
Analog Input, 14 | Evaporator Saturated Refrigerant Temperature- Ckt 2 | Circuit 2 evaporator refrigerant temperature. | Temperature | • | • | • | |
Analog Input, 15 | Suction Saturated Refrigerant Temperature- Ckt 2 | Circuit 2 suction refrigerant temperature. | Temperature | • | • | • | |
Analog Input, 16 | Condenser Refrigerant Pressure- Ckt 1 | Circuit 1 condenser refrigerant pressure. | Pressure | • | • | • | |
Analog Input, 17 | Discharge Pressure- Ckt 1 | Circuit 1 discharge pressure. | Pressure | • | • | • | |
Analog Input, 18 | Condenser Refrigerant Pressure- Ckt 2 | Circuit 2 condenser refrigerant pressure. | Pressure | • | • | • | |
Analog Input, 19 | Discharge Pressure- Ckt 2 | Circuit 2 discharge pressure. | Pressure | • | • | • | |
Analog Input, 20 | Condenser Saturated Refrigerant Temperature- Ckt 1 | Circuit 1 condenser refrigerant temperature. | Temperature | • | • | • | |
Analog Input, 21 | Discharge Saturated Refrigerant Temperature- Ckt 1 | Circuit 1 discharge refrigerant temperature. | Temperature | • | • | • | |
Analog Input, 22 | Condenser Saturated Refrigerant Temperature- Ckt 2 | Circuit 2 condenser refrigerant temperature. | Temperature | • | • | • | |
Analog Input, 23 | Discharge Saturated Refrigerant Temperature- Ckt 2 | Circuit 2 discharge refrigerant temperature. | Temperature | • | • | • | |
Analog Input, 24 | Unit Power Consumption | The power being consumed by the chiller. | Power | (a) | (a) | (a) | (a) |
Analog Input, 25 | Local Atmospheric Pressure | Local atmospheric pressure. | Pressure | • | • | • | • |
Analog Input, 26 | Starts- Compressor 1A | Number of starts for compressor 1A. | • | • | • | • | |
Analog Input, 27 | Starts- Compressor 1B | Number of starts for compressor 1B. | • | • | • | • | |
Analog Input, 28 | Starts- Compressor 2A | Number of starts for compressor 2A. | • | • | • | • | |
Analog Input, 29 | Starts- Compressor 2B | Number of starts for compressor 2B. | • | • | • | • | |
Analog Input, 30 | Starts- Compressor 1C | Number of starts for compressor 1C. | • | • | • | • | |
Analog Input, 31 | Starts- Compressor 2A | Number of starts for compressor 2A. | • | • | • | • | |
Analog Input, 32 | Starts- Compressor 2B | Number of starts for compressor 2B. | • | • | • | • | |
Analog Input, 33 | Starts- Compressor 2C | Number of starts for compressor 2C. | • | • | • | • | |
Analog Input, 34 | Run Time- Compressor 1A | Total run time of compressor 1A. | Time | • | • | • | |
Analog Input, 35 | Run Time- Compressor 1B | Total run time of compressor 1B. | Time | • | • | • | |
Analog Input, 36 | Run Time- Compressor 2A | Total run time of compressor 2A. | Time | • | • | • | |
Analog Input, 37 | Run Time- Compressor 2B | Total run time of compressor 2B. | Time | • | • | • | |
Analog Input, 38 | Run Time- Compressor 1C | Total run time of compressor 1C. | Time | • | • | • | |
Analog Input, 39 | Run Time- Compressor 2A | Total run time of compressor 2A. | Time | • | • | • | |
Analog Input, 40 | Run Time- Compressor 2B | Total run time of compressor 2B. | Time | • | • | • | |
Analog Input, 41 | Run Time- Compressor 2C | Total run time of compressor 2C. | Time | • | • | • | |
Analog Input, 42 | Airflow Percentage- Circuit 1 | Approximate airflow percentage of circuit 1. | Percent | • | • | • | |
Analog Input, 43 | Airflow Percentage- Circuit 2 | Approximate airflow percentage of circuit 2. | Percent | • | • | • | |
Analog Input, 44 | Evaporator Entering Water Temp | Temperature of the water entering the evaporator. | Temperature | • | • | • | • |
Analog Input, 45 | Evaporator Leaving Water Temp | Temperature of the water leaving the evaporator. | Temperature | • | • | • | |
Analog Input, 46 | Condenser Entering Water Temp | Temperature of the water entering the condenser. | Temperature | • | • | • | |
Analog Input, 47 | Condenser Leaving Water Temp | Temperature of the water leaving the condenser. | Temperature | • | • | • | |
Analog Input, 48 | High Side Oil Pressure- Compressor 1A | Pressure of the oil at the high side of compressor 1A. | Pressure | • | • | • | |
Analog Input, 49 | High Side Oil Pressure- Compressor 1B | Pressure of the oil at the high side of compressor 1B. | Pressure | • | • | • | |
Analog Input, 50 | High Side Oil Pressure- Compressor 2A | Pressure of the oil at the high side of compressor 2A. | Pressure | • | • | • | |
Analog Input, 51 | High Side Oil Pressure- Compressor 2B | Pressure of the oil at the high side of compressor 2B. | Pressure | • | • | • | |
Analog Input, 52 | Oil Temp- Compressor 1A | Temperature of the oil in compressor 1A. | Temperature | • | • | • | |
Analog Input, 52 | Oil Temp- Compressor 1B | Temperature of the oil in compressor 1B. | Temperature | • | • | • | |
Analog Input, 54 | Oil Temp- Compressor 2A | Temperature of the oil in compressor 2A. | Temperature | • | • | • | |
Analog Input, 55 | Oil Temp- Compressor 2B | Temperature of the oil in compressor 2B. | Temperature | • | • | • | |
Analog Input, 56 | Refrigerant Disch Temp- Ckt 1 | Temperature of the refrigerant being discharged from Ckt 1. | Temperature | • | • | • | |
Analog Input, 57 | Outdoor Air Temperature | Outdoor air temperature. | Temperature | • | • | • | • |
Analog Input, 58 | Condenser Control Output | Percentage of condenser water flow being requested by the chiller. | Percent | • | • | • | |
Analog Input, 59 | Phase AB Voltage- Compressor 1A | Phase AB voltage, compressor 1A. | Voltage | • | • | • | |
Analog Input, 60 | Phase BC Voltage- Compressor 1A | Phase BC voltage, compressor 1A. | Voltage | • | • | • | |
Analog Input, 61 | Phase CA Voltage- Compressor 1A | Phase CA voltage, compressor 1A. | Voltage | • | • | • | |
Analog Input, 62 | Phase AB Voltage- Compressor 1B | Phase AB voltage, compressor 1B. | Voltage | • | • | • | |
Analog Input, 63 | Phase BC Voltage- Compressor 1B | Phase BC voltage, compressor 1B. | Voltage | • | • | • | |
Analog Input, 64 | Phase CA Voltage- Compressor 1B | Phase CA voltage, compressor 1B. | Voltage | • | • | • | |
Analog Input, 65 | Phase AB Voltage- Compressor 2A | Phase AB voltage, compressor 2A. | Voltage | • | • | • | |
Analog Input, 66 | Phase BC Voltage- Compressor 2A | Phase BC voltage, compressor 2A. | Voltage | • | • | • | |
Analog Input, 67 | Phase CA Voltage- Compressor 2A | Phase CA voltage, compressor 2A. | Voltage | • | • | • | |
Analog Input, 68 | Phase AB Voltage- Compressor 2B | Phase AB voltage, compressor 2B. | Voltage | • | • | • | |
Analog Input, 69 | Phase BC Voltage- Compressor 2B | Phase BC voltage, compressor 2B. | Voltage | • | • | • | |
Analog Input, 70 | Phase CA Voltage- Compressor 2B | Phase CA voltage, compressor 2B. | Voltage | • | • | • | |
Analog Input, 71 | Line 1 Current (in Amps)- Compressor 1A | Line 1 Current (in Amps)- Compressor 1A. | Current | • | • | • | |
Analog Input, 72 | Line 2 Current (in Amps)- Compressor 1A | Line 2 Current (in Amps)- Compressor 1A. | Current | • | • | • | |
Analog Input, 73 | Line 3 Current (in Amps)- Compressor 1A | Line 3 Current (in Amps)- Compressor 1A. | Current | • | • | • | |
Analog Input, 74 | Line 1 Current (in Amps)- Compressor 1B | Line 1 Current (in Amps)- Compressor 1B. | Current | • | • | • | |
Analog Input, 75 | Line 2 Current (in Amps)- Compressor 1B | Line 2 Current (in Amps)- Compressor 1B. | Current | • | • | • | |
Analog Input, 76 | Line 3 Current (in Amps)- Compressor 1B | Line 3 Current (in Amps)- Compressor 1B. | Current | • | • | • | |
Analog Input, 77 | Line 1 Current (in Amps)- Compressor 2A | Line 1 Current (in Amps)- Compressor 2A. | Current | • | • | • | |
Analog Input, 78 | Line 2 Current (in Amps)- Compressor 2A | Line 2 Current (in Amps)- Compressor 2A. | Current | • | • | • | |
Analog Input, 79 | Line 3 Current (in Amps)- Compressor 2A | Line 3 Current (in Amps)- Compressor 2A. | Current | • | • | • | |
Analog Input, 80 | Line 1 Current (in Amps)- Compressor 2B | Line 1 Current (in Amps)- Compressor 2B. | Current | • | • | • | |
Analog Input, 81 | Line 2 Current (in Amps)- Compressor 2B | Line 2 Current (in Amps)- Compressor 2B. | Current | • | • | • | |
Analog Input, 82 | Line 3 Current (in Amps)- Compressor 2B | Line 3 Current (in Amps)- Compressor 2B. | Current | • | • | • | |
Analog Input, 83 | Line 1 Current (%RLA)- Compressor 1A | Line 1 Current (%RLA)- Compressor 1A. | Percent | • | • | • | |
Analog Input, 84 | Line 2 Current (%RLA)- Compressor 1A | Line 2 Current (%RLA)- Compressor 1A. | Percent | • | • | • | |
Analog Input, 85 | Line 3 Current (%RLA)- Compressor 1A | Line 3 Current (%RLA)- Compressor 1A. | Percent | • | • | • | |
Analog Input, 86 | Line 1 Current (%RLA)- Compressor 1B | Line 1 Current (%RLA)- Compressor 1B. | Percent | • | • | • | |
Analog Input, 87 | Line 2 Current (%RLA)- Compressor 1B | Line 2 Current (%RLA)- Compressor 1B. | Percent | • | • | • | |
Analog Input, 88 | Line 3 Current (%RLA)- Compressor 1B | Line 3 Current (%RLA)- Compressor 1B. | Percent | • | • | • | |
Analog Input, 89 | Line 1 Current (%RLA)- Compressor 2A | Line 1 Current (%RLA)- Compressor 2A. | Percent | • | • | • | |
Analog Input, 90 | Line 2 Current (%RLA)- Compressor 2A | Line 2 Current (%RLA)- Compressor 2A. | Percent | • | • | • | |
Analog Input, 91 | Line 3 Current (%RLA)- Compressor 2A | Line 3 Current (%RLA)- Compressor 2A. | Percent | • | • | • | |
Analog Input, 92 | Line 1 Current (%RLA)- Compressor 2B | Line 1 Current (%RLA)- Compressor 2B. | Percent | • | • | • | |
Analog Input, 93 | Line 2 Current (%RLA)- Compressor 2B | Line 2 Current (%RLA)- Compressor 2B. | Percent | • | • | • | |
Analog Input, 94 | Line 3 Current (%RLA)- Compressor 2B | Line 3 Current (%RLA)- Compressor 2B. | Percent | • | • | • | |
Analog Input, 95 | Number of Circuits | Number of Circuits. | None | • | • | • | • |
Analog Input, 96 | Number of Compressors, Ckt 1 | Number of Compressors, Ckt 1. | None | • | • | • | |
Analog Input, 97 | Number of Compressors, Ckt 2 | Number of Compressors, Ckt 2. | None | • | • | • | |
Analog Input, 98 | Chiller Design Capacity | Design Capacity of the Chiller. | None | • | • | • | • |
Table 5. Multistate Output
Object Identifier | Object Name | Description | Relinq Default | Object States | RTWD/RTUD | RTHD | RTAC | CGAM |
---|---|---|---|---|---|---|---|---|
Multi-State Output, 1 | Chiller Mode Command | Mode of operation of the chiller. | 1 = Cool | 1 = HVAC Cool 2 = HVAC_Heat 3 = HVAC_Ice (a) 4 = Not Used |
• | • | • |
(a) Chiller should be selected for ice making.
Table 6. Multistate Input
BCI-C Object Identifier | Object Name | Description | Object States | RTWD/RTUD | RTHD | RTAC | CGAM |
---|---|---|---|---|---|---|---|
Multi-State Input, 1 | Running Mode | Indicates the primary running mode of the chiller. | 1 = Chiller Off 2 = Chiller in Start Mode 3 = Chiller in Run Mode 4 = Chiller in Pre-shutdown Mode 5 = Chiller in Service Mode |
• | • | • | • |
Multi-State Input, 2 | Operating Mode | Indicates the primary operating mode of the chiller. | 1 = HVAC_Cool 2 = HVAC_Heat 3 = HVAC_Ice (a) 4 = Not Used |
• | • | • | • |
Multi-State Input, 3 | MP Communication Status | Communication status. | 1 = R-22 2 = Communication 3 = Communication Lost 4 = Failed to Established 5 = Waiting to Establish |
• | • | • | • |
Multi-State Input, 4 | Refrigerant Type | Refrigerant type. | 1 = R-11 2 = R-12 3 = R-22 4 = R-123 5 R-134A 6 = R407C 7 = R-410A |
• | • | • | • |
Multi-State Input, 5 | Model Information | Indicates the model type of the chiller. | 1 = RTA 2 = CVH 3 = CVG 4 = CVR 5 = CDH 6 = RTH 7 = CGW 8 = CGA 9 = CCA 10 = RTW 11 = RTX 12 = RTU 13 = CCU 14 = CXA 15 = CGC 16 = RAU |
• | • | • | • |
Multi-State Input, 6 | Cooling Type | Cooling type of the condenser. | 1 = Water Cooled 2 = Air Cooled |
• | • | • | • |
Multi-State Input, 7 | Manufacturing Location | Location where chiller was manufactured. | 1 = Field Applied 2 = La Crosse 3 = Pueblo 4 = Charmes 5 = Rushville 6 = Macon 7 = Waco 8 = Lexington 9 = Forsyth 10 = Clarksville 11 = Penang 12 = Colchester 13 = Curitiba 14 = Taicang 15 = Taiwan 16 = Epinal 17 = Golbey |
• | • | • | • |
(a) Chiller should be selected for ice making.
Table 7. Binary Output
Object Identifier | Object Name | Description | Relinq Default | Object States | RTWD/RTUD | RTHD | RTAC | CGAM |
---|---|---|---|---|---|---|---|---|
Binary Output, 1 | Chiller Auto Stop Command | Allows the chiller to run if conditions for running are met. | False | Inactive = Stop Active = Auto |
• | • | • | • |
Binary Output, 2 | Remote Diagnostic Reset Command | Resets remotely diagnostics that can be reset. | False | Inactive = No Reset Request Active = Reset Request |
• | • | • | • |
Binary Output, 3 | Base Loading Auto/On Request | Requests chiller to use base loading. | False | Inactive = Auto Active = On |
• | • | • | • |
Binary Output, 4 | Noise Reduction Request | Requests chiller to enter mode to reduce noise. | False | Inactive = Normal Active = Reduced Noise |
• | • | • | • |
Table 8. Binary Input
Object Identifier | Object Name | Description | Object States | RTWD/RTUD | RTHD | RTAC | CGAM |
---|---|---|---|---|---|---|---|
Binary Input, 23 | Alarm Present | Indicates if an alarm is active. | Inactive = No Alarm Active = Alarm |
• | • | • | • |
Binary Input, 8 | Base Loading Active | Indicates if the base loading control method is currently being used. | Inactive = Inactive Active = Active |
• | • | • | • |
Binary Input, 3 | Capacity Limited | Indicates if conditions may exist that prevent the chiller from reaching setpoint. | Inactive = Not Limited Active = Limited |
• | • | • | • |
Binary Input, 4 | Chiller Running State | Indicates if the chiller is running or stopped. | Inactive = Off Active = On |
• | • | • | • |
Binary Input, 9 | Compressor 1A Running | Indicates if compressor 1A is running. | Inactive = Off Active = Running |
• | • | • | • |
Binary Input, 10 | Compressor 1B Running | Indicates if compressor 1B is running. | Inactive = Off Active = Running |
• | • | • | • |
Binary Input, 13 | Compressor 1C Running | Indicates if compressor 1C is running. | Inactive = Off Active = Running |
• | • | • | • |
Binary Input, 11 | Compressor 2A Running | Indicates if compressor 2A is running. | Inactive = Off Active = Running |
• | • | • | • |
Binary Input, 14 | Compressor 2A Running | Indicates if compressor 2A is running. | Inactive = Off Active = Running |
• | • | • | • |
Binary Input, 12 | Compressor 2B Running | Indicates if compressor 2B is running. | Inactive = Off Active = Running |
• | • | • | • |
Binary Input, 15 | Compressor 2B Running | Indicates if compressor 2B is running. | Inactive = Off Active = Running |
• | • | • | • |
Binary Input, 16 | Compressor 2C Running | Indicates if compressor 2C is running. | Inactive = Off Active = Running |
• | • | • | • |
Binary Input, 5 | Condenser Water Flow Status | Condenser water flow status. | Inactive = No Flow Active = Flow |
• | • | • | • |
Binary Input, 19 | Condenser Water Pump Request | Indicates a request from the chiller to turn on the condenser water pump. | Inactive = Off Active = On |
• | • | • | • |
Binary Input, 21 | Defrost Mode (or in Defrost) | Indicates if one or more circuits are in a defrost mode. | Inactive = Not in Defrost Active = Defrost |
• | • | • | (a) |
Binary Input, 22 | Evaporator Water Flow Status | Indicates if water is flowing through the evaporator. | Inactive = No Flow Active = Flow |
• | • | • | • |
Binary Input, 17 | Evaporator Water Pump Request | Indicates a request from the chiller to turn on the evaporator water pump. | Inactive = Off Active = On |
• | • | • | • |
Binary Input, 7 | Head Relief Request | Indicates if the chiller is asking an outside system to provide more heat rejection from the condenser water loop. | Inactive = Off Active = On |
• | • | • | • |
Binary Input, 25 | Last Diagnostic | Indicates last diagnostic for the chiller. | Inactive = Off Active = On |
• | • | • | • |
Binary Input, 2 | Local Setpoint Control | Indicates if the chiller is being controlled by local setpoints instead of BAS setpoints. | Inactive = Remote Control Active = Local Control |
• | • | • | • |
Binary Input, 6 | Maximum Capacity | Indicates if all available chiller capacity is being used. | Inactive = Off Active = On |
• | • | • | • |
Binary Input, 5 | Noise Reduction Active | Indicates if the chiller is in a state where noise is being reduced. | Inactive = Off Active = On |
• | • | • | • |
Binary Input, 1 | Run Enabled | Indicates if the chiller is available to run or is currently running. | Inactive = Stop Active = Auto |
• | • | • | • |
Binary Input, 24 | Shutdown Alarm Present | Indicates if a shutdown alarm is active. | Inactive = No Alarm Active = None |
• | • | • | • |
Binary Input, 18 | Water Pump Request | Indicates a request from the chiller to turn on the water pump. | Inactive = Off Active = On |
• | • | • | • |
Table 9. All Object Types Sorted by Object Name
(Refer to previous tables for detailed descriptions of objects)
Object Identifier(a) | Object Name | Description |
---|---|---|
Analog Input 4 | Active Base Loading Setpoint | Value of base loading setpoint currently being used by the chiller. |
Analog Input, 1 | Active Cool/Heat Setpoint Temperature | Active chiller water or hot water setpoint. |
Analog Input, 2 | Active Current Limit Setpoint | Active capacity current limit setpoint. |
Analog Input, 3 | Active Demand Limit Setpoint | Active demand limit setpoint. |
Analog Input, 5 | Actual Running Capacity | Level of capacity that the chiller is currently running at. |
Analog Input, 42 | Airflow Percentage- Circuit 1 | Approximate airflow percentage of circuit 1. |
Analog Input, 43 | Airflow Percentage- Circuit 2 | Approximate airflow percentage of circuit 2. |
Binary Input, 23 | Alarm Present | Indicates if an alarm is active. |
Binary Input, 8 | Base Loading Active | Indicates if the base loading control method is currently being used. |
Binary Output, 3 | Base Loading Auto/On Request | Requests chiller to use base loading. |
Analog Output 5 | Base Loading Setpoint | Capacity level to which the chiller should control when base loading is active. |
Binary Input, 3 | Capacity Limited | Indicates if conditions may exist that prevent the chiller from reaching setpoint. |
Analog Output 1 | Chilled Water Setpoint | Desired leaving water temperature if chiller is in cooling mode. |
Binary Output, 1 | Chiller Auto Stop Command | Allows the chiller to run if conditions for running are met. |
Binary Output, 1 | Chiller Auto Stop Command | Allows the chiller to run if conditions for running are met. |
Analog Input, 98 | Chiller Design Capacity | Design capacity of the chiller. |
Binary Input, 4 | Chiller Running State | Indicates if the chiller is running or stopped. |
Binary Input, 9 | Compressor 1A Running | Indicates if compressor 1A is running. |
Binary Input, 10 | Compressor 1B Running | Indicates if compressor 1B is running. |
Binary Input, 13 | Compressor 1C Running | Indicates if compressor 1C is running. |
Binary Input, 11 | Compressor 2A Running | Indicates if compressor 2A is running. |
Binary Input, 14 | Compressor 2A Running | Indicates if compressor 2A is running. |
Binary Input, 12 | Compressor 2B Running | Indicates if compressor 2B is running. |
Binary Input, 15 | Compressor 2B Running | Indicates if compressor 2B is running. |
Binary Input, 16 | Compressor 2C Running | Indicates if compressor 2C is running. |
Analog Input, 58 | Condenser Control Output | Percentage of condenser water flow being requested by the chiller. |
Analog Input, 46 | Condenser Entering Water Temp | Temperature of the water entering the condenser. |
Analog Input, 47 | Condenser Leaving Water Temp | Temperature of the water leaving the condenser. |
Analog Input, 16 | Condenser Refrigerant Pressure- Ckt 1 | Circuit 1 condenser refrigerant pressure. |
Analog Input, 18 | Condenser Refrigerant Pressure- Ckt 2 | Circuit 2 condenser refrigerant pressure. |
Analog Input, 20 | Condenser Saturated Refrigerant Temperature- Ckt 1 | Circuit 1 condenser refrigerant temperature. |
Analog Input, 22 | Condenser Saturated Refrigerant Temperature- Ckt 2 | Circuit 2 condenser refrigerant temperature. |
Binary Input, 5 | Condenser Water Flow Status | Condenser water flow status. |
Binary Input, 19 | Condenser Water Pump Request | Indicates a request from the chiller to turn on the condenser water pump. |
Analog Input, 2 | Current Limit Setpoint | Sets the maximum capacity that the chiller can use. |
Binary Input, 21 | Defrost Mode (or in Defrost) | Indicates if one or more circuits are in a defrost mode. |
Analog Input, 3 | Demand Limit Setpoint | Sets the maximum capacity that the chiller can use. |
Analog Input, 17 | Discharge Pressure- Ckt 1 | Circuit 1 discharge pressure. |
Analog Input, 19 | Discharge Pressure- Ckt 2 | Circuit 2 discharge pressure. |
Analog Input, 21 | Discharge Saturated Refrigerant Temperature- Ckt 1 | Circuit 1 discharge refrigerant temperature. |
Analog Input, 23 | Discharge Saturated Refrigerant Temperature- Ckt 2 | Circuit 2 discharge refrigerant temperature. |
Analog Input, 44 | Evaporator Entering Water Temp | Temperature of the water entering the evaporator. |
Analog Input, 45 | Evaporator Leaving Water Temp | Temperature of the water leaving the evaporator. |
Binary Input, 22 | Evaporator Water Flow Status | Indicates if water is flowing through the evaporator. |
Binary Input, 17 | Evaporator Water Pump Request | Indicates a request from the chiller to turn on the evaporator water pump. |
Analog Input, 9 | Evaporator Refrigerant Pressure- Ckt 2 | Circuit 2 evaporator refrigerant pressure. |
Binary Input, 7 | Head Relief Request | Indicates if the chiller is asking an outside system to provide more heat rejection from the condenser water loop. |
Analog Input, 48 | High Side Oil Pressure- Compressor 1A | Pressure of the oil at the high side of compressor 1A. |
Analog Input, 49 | High Side Oil Pressure- Compressor 1B | Pressure of the oil at the high side of compressor 1B. |
Analog Input, 50 | High Side Oil Pressure- Compressor 2A | Pressure of the oil at the high side of compressor 2A. |
Analog Input, 51 | High Side Oil Pressure- Compressor 2B | Pressure of the oil at the high side of compressor 2B. |
Analog Output 4 | Hot Water Setpoint | Desired leaving water temperature if chiller is in heating mode. |
Binary Input, 25 | Last Diagnostic | Indicates the last diagnostic for the chiller. |
Analog Input, 83 | Line 1 Current (%RLA)- Compressor 1A | Line 1 Current (%RLA)- Compressor 1A. |
Analog Input, 86 | Line 1 Current (%RLA)- Compressor 1B | Line 1 Current (%RLA)- Compressor 1B. |
Analog Input, 89 | Line 1 Current (%RLA)- Compressor 2A | Line 1 Current (%RLA)- Compressor 2A. |
Analog Input, 92 | Line 1 Current (%RLA)- Compressor 2B | Line 1 Current (%RLA)- Compressor 2B. |
Analog Input, 71 | Line 1 Current (in Amps)- Compressor 1A | Line 1 Current (in Amps)- Compressor 1A. |
Analog Input, 74 | Line 1 Current (in Amps)- Compressor 1B | Line 1 Current (in Amps)- Compressor 1B. |
Analog Input, 77 | Line 1 Current (in Amps)- Compressor 2A | Line 1 Current (in Amps)- Compressor 2A. |
Analog Input, 80 | Line 1 Current (in Amps)- Compressor 2B | Line 1 Current (in Amps)- Compressor 2B. |
Analog Input, 84 | Line 2 Current (%RLA)- Compressor 1A | Line 2 Current (%RLA)- Compressor 1A. |
Analog Input, 87 | Line 2 Current (%RLA)- Compressor 1B | Line 2 Current (%RLA)- Compressor 1B. |
Analog Input, 90 | Line 2 Current (%RLA)- Compressor 2A | Line 2 Current (%RLA)- Compressor 2A. |
Analog Input, 93 | Line 2 Current (%RLA)- Compressor 2B | Line 2 Current (%RLA)- Compressor 2B. |
Analog Input, 72 | Line 2 Current (in Amps)- Compressor 1A | Line 2 Current (in Amps)- Compressor 1A. |
Analog Input, 75 | Line 2 Current (in Amps)- Compressor 1B | Line 2 Current (in Amps)- Compressor 1B. |
Analog Input, 78 | Line 2 Current (in Amps)- Compressor 2A | Line 2 Current (in Amps)- Compressor 2A. |
Analog Input, 81 | Line 2 Current (in Amps)- Compressor 2B | Line 2 Current (in Amps)- Compressor 2B. |
Analog Input, 85 | Line 3 Current (%RLA)- Compressor 1A | Line 3 Current (%RLA)- Compressor 1A. |
Analog Input, 88 | Line 3 Current (%RLA)- Compressor 1B | Line 3 Current (%RLA)- Compressor 1B. |
Analog Input, 91 | Line 3 Current (%RLA)- Compressor 2A | Line 3 Current (%RLA)- Compressor 2A. |
Analog Input, 94 | Line 3 Current (%RLA)- Compressor 2B | Line 3 Current (%RLA)- Compressor 2B. |
Analog Input, 73 | Line 3 Current (in Amps)- Compressor 1A | Line 3 Current (in Amps)- Compressor 1A. |
Analog Input, 76 | Line 3 Current (in Amps)- Compressor 1B | Line 3 Current (in Amps)- Compressor 1B. |
Analog Input, 79 | Line 3 Current (in Amps)- Compressor 2A | Line 3 Current (in Amps)- Compressor 2A. |
Analog Input, 82 | Line 3 Current (in Amps)- Compressor 2B | Line 3 Current (in Amps)- Compressor 2B. |
Binary Input, 25 | Last Diagnostic | Indicates the last diagnostic for the chiller. |
Analog Input, 25 | Local Atmospheric Pressure | Local atmospheric pressure. |
Binary Input, 2 | Local Setpoint Control | Indicates if the chiller is being controlled by local setpoints instead of BAS setpoints. |
Multi-State Input, 7 | Manufacturing Location | Location where chiller was manufactured. |
Binary Input, 6 | Maximum Capacity | Indicates if all available chiller capacity is being used. |
Multi-State Input, 5 | Model Information | Indicates the model type of the chiller. |
Multi-State Input, 3 | MP Communication Status | Communication status. |
Binary Input, 5 | Noise Reduction Active | Indicates if the chiller is in a state where noise is being reduced. |
Binary Output, 4 | Noise Reduction Request | Requests chiller to enter mode to reduce noise. |
Analog Input, 52 | Oil Temp- Compressor 1A | Temperature of the oil in compressor 1A. |
Analog Input, 52 | Oil Temp- Compressor 1B | Temperature of the oil in compressor 1B. |
Analog Input, 54 | Oil Temp- Compressor 2A | Temperature of the oil in compressor 2A. |
Analog Input, 55 | Oil Temp- Compressor 2B | Temperature of the oil in compressor 2B. |
Multi-State Input, 2 | Operating Mode | Indicates the primary operating mode of the chiller. |
Analog Input, 57 | Outdoor Air Temperature | Outdoor air temperature. |
Analog Input, 59 | Phase AB Voltage- Compressor 1A | Phase AB voltage, compressor 1A. |
Analog Input, 62 | Phase AB Voltage- Compressor 1B | Phase AB voltage, compressor 1B. |
Analog Input, 65 | Phase AB Voltage- Compressor 2A | Phase AB voltage, compressor 2A. |
Analog Input, 68 | Phase AB Voltage- Compressor 2B | Phase AB voltage, compressor 2B. |
Analog Input, 60 | Phase BC Voltage- Compressor 1A | Phase BC voltage, compressor 1A. |
Analog Input, 63 | Phase BC Voltage- Compressor 1B | Phase BC voltage, compressor 1B. |
Analog Input, 66 | Phase BC Voltage- Compressor 2A | Phase BC voltage, compressor 2A. |
Analog Input, 69 | Phase BC Voltage- Compressor 2B | Phase BC voltage, compressor 2B. |
Analog Input, 61 | Phase CA Voltage- Compressor 1A | Phase CA voltage, compressor 1A. |
Analog Input, 64 | Phase CA Voltage- Compressor 1B | Phase CA voltage, compressor 1B. |
Analog Input, 67 | Phase CA Voltage- Compressor 2A | Phase CA voltage, compressor 2A. |
Analog Input, 70 | Phase CA Voltage- Compressor 2B | Phase CA voltage, compressor 2B. |
Multi-State Input, 4 | Refrigerant Type | Refrigerant type. |
Binary Output, 2 | Remote Diagnostic Reset Command | Resets remotely diagnostics that can be reset. |
Binary Input, 1 | Run Enabled | Indicates if the chiller is available to run or is currently running. |
Analog Input, 34 | Run Time- Compressor 1A | Total run time of compressor 1A. |
Analog Input, 35 | Run Time- Compressor 1B | Total run time of compressor 1B. |
Analog Input, 38 | Run Time- Compressor 1C | Total run time of compressor 1C. |
Analog Input, 36 | Run Time- Compressor 2A | Total run time of compressor 2A. |
Analog Input, 39 | Run Time- Compressor 2A | Total run time of compressor 2A. |
Analog Input, 37 | Run Time- Compressor 2B | Total run time of compressor 2B. |
Analog Input, 40 | Run Time- Compressor 2B | Total run time of compressor 2B. |
Analog Input, 41 | Run Time- Compressor 2C | Total run time of compressor 2C. |
Multi-State Input, 1 | Running Mode | Indicates the primary running mode of the chiller. |
Binary Input, 24 | Shutdown Alarm Present | Indicates if a shutdown alarm is active. |
Analog Input, 26 | Starts- Compressor 1A | Number of starts for compressor 1A. |
Analog Input, 27 | Starts- Compressor 1B | Number of starts for compressor 1B. |
Analog Input, 30 | Starts- Compressor 1C | Number of starts for compressor 1C. |
Analog Input, 28 | Starts- Compressor 2A | Number of starts for compressor 2A. |
Analog Input, 31 | Starts- Compressor 2A | Number of starts for compressor 2A. |
Analog Input, 29 | Starts- Compressor 2B | Number of starts for compressor 2B. |
Analog Input, 32 | Starts- Compressor 2B | Number of starts for compressor 2B. |
Analog Input, 33 | Starts- Compressor 2C | Number of starts for compressor 2C. |
Analog Input, 7 | Suction Pressure- Ckt 1 | Circuit 1 suction pressure. |
Analog Input, 8 | Suction Pressure- Ckt 1 | Circuit 1 suction pressure. |
Analog Input, 10 | Suction Pressure- Ckt 2 | Circuit 2 suction pressure. |
Analog Input, 11 | Suction Pressure- Ckt 2 | Circuit 2 suction pressure. |
Analog Input, 13 | Suction Saturated Refrigerant Temperature- Ckt 1 | Circuit 1 suction refrigerant temperature. |
Analog Input, 15 | Suction Saturated Refrigerant Temperature- Ckt 2 | Circuit 2 suction refrigerant temperature. |
Analog Input, 24 | Unit Power Consumption | The power being consumed by the chiller. |
Analog Input, 18 | Water Pump Request | Indicates a request from the chiller to turn on the water pump. |
BCI-C Alarming
The BCI-C unit has three binary input points that are used for communicating alarms and one binary output point that is used to reset alarms remotely. Those inputs and output points are:
- BI 23; Alarm Present– This object indicates if any alarms are active regardless of severity. A notification will be sent to any recipients of the Information Notification Class object when the point transitions from No Alarm to Alarm.
- BI 24; Shutdown Alarm Present– This object indicates if any alarms that result in the shutdown of the chiller are active. A notification will be sent to any recipients of the Critical Notification Class object when the point transitions from No Alarm to Alarm.
- BI 25; Last Diagnostic– The active text of this object will reflect the description of the last diagnostic to occur on the chiller.
- BO 2; Remote Diagnostic Reset Command– This object is used to remotely reset diagnostics on the chiller. Immediately after commanding this point value to 1, the BCI-C will send the reset command to the chiller and set this point value back to 0 and clear the priority array.
Note: Not all diagnostics are able to be reset remotely. Some will require local reset at the chiller front panel.
Additional Resources
Use the following documents and links as additional resources:
- BACnet™ Communication Interface for Chillers (BCI-C) Field Kit Installation Guide (RF-SVN02)
- Product support online: www.trane.com
- www.bacnet.org
- www.ashrae.org
- www.bacnetassociation.org
- Tracer TU Help online
- Tracer™ BACnet™ Terminator Installation Instructions (X39641151-01)
- Tracer™ TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)
- Tracer™ TU Service Tool for Water-cooled CenTraVac™ Chillers with Tracer AdaptiView™ Control Programming Guide (CTV-SVP02)
Note: For further assistance, contact your local Trane sales office.
Glossary
A
ASHRAE
See American Society of Heating, Refrigeration, and Air-conditioning Engineers
American Society of Heating, Refrigeration, and Air-conditioning Engineers
An international organization of 50,000 persons with chapters throughout the world. The Society is organized for the sole purpose of advancing the arts and sciences of heating, ventilation, air conditioning and refrigeration. It benefits the public with its research, standards writing, continuing education, and publications.
B
BACnet™
See Building Automation Control network
BACnet interoperability building blocks
A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality. The BIBBs are grouped together into BACnet device profiles.
BACnet object
An abstract representation of the physical point or points where data is input from or output to an I/O device. Each object may have several BACnet properties that describe the status of that object.
baud rate
The number of signaling elements that occur each second during electronic data transmission. At slow speeds, baud indicates the number of bits per second that are transmitted. For example, 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps). At higher speeds, multiple bits may be encoded with each electrical change. For example, 4,800 baud may allow 9,600 bits to be sent each second. Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud. For example, a 9,600 bps modem may operate at only 2,400 baud.
BIBB
See BACnet interoperability building blocks
Building Automation Control network (BACnet and ANSI/ASHRAE Standard 135-2004)
An interoperable protocol developed specifically for the building controls industry. The American National Standards Institute named it as a standard and Trane advocates BACnet protocol for use in system-level control devices.
device
A device is a standard BACnet object as defined by ASHRAE Standard 135-2004. The Tracer UC800 contains the BACnet object.
Device ID
The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302. There cannot be more than one device using the same Device ID. Each of the sample applications operate as a device and requires its own device id which defaults to zero.
interoperability
The ability to integrate equipment from different vendors into a comprehensive automation and control system. In addition, digital communications between products designed independently, but designed to the same communication standard.
P
protocol
A set of rules (language) that governs the exchange of data over a digital communications system.