BACnet™ Communication Interface for Chiller (BCI-C)

Integration Guide

for RTWD/RTUD, RTHD, RTAC, and CGAM

Overview

The BACnet™ Communication Interface for Chillers (BCI-C) is comprised of a Tracer™ UC400 controller with interface software. It is a non-programmable communications module that allows heating, ventilation, and air-conditioning (HVAC) equipment to communicate on a BACnet communications network.

This guide provides:

Note: Users of this guide should have basic knowledge of BACnet protocol. For more detailed information about this protocol, visit the company web site listed under "Additional Resources," p. 25.

BACnet Protocol

The Building Automation and Control Network (BACnet and ANSI/ASHRAE Standard 135-2004) protocol is a standard that allows building automation systems or components from different manufacturers to share information and control functions. BACnet provides building owners the capability to connect various types of building control systems or subsystems together for a variety of reasons. In addition, multiple vendors can use this protocol to share information for monitoring and supervisory control between systems and devices in a multi-vendor interconnected system.

The BACnet protocol identifies standard objects (data points) called BACnet objects. Each object has a defined list of properties that provide information about that object. BACnet also defines a number of standard application services that are used to access data and manipulate these objects and provides a client/server communication between devices. For more information on BACnet protocol, refer to "Additional Resources," p. 25.

BACnet Testing Laboratory (BTL) Certification

The BCI-C supports the BACnet communication protocol and has been designed to meet the requirements of the application-specific control profile. For more details, refer to the BTL web site at www.bacnetassociation.org.

Rotary Switches and LEDs

This section provides information about the BCI-C rotary switches and LED displays.

Rotary Switches

There are three rotary switches on the front of the BCI-C device that are used to define a three-digit address when the BCI-C is installed on a BACnet communications network. The three-digit address setting is the BACnet MAC address.

Note: All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet.

Figure 1. Setting rotary switches

[Diagram showing rotary switches and their settings before and after adjustment]

Important: Each device on the BACnet/MSTP link must have a unique rotary switch setting, otherwise, communication problems will occur.

[Illustration of a screwdriver being used to set rotary switches]

Note: For details on setting the baud rate, BACnet Device ID, and units of measure, refer to the section, Configuring the BCI-C in the BACnet Communication Interface (BCI-C) Field Kit Installation Guide, RF-SVN02.

LEDs Description, Behavior, and Troubleshooting

There are 15 LEDs on the front of the BCI-C unit. However, LEDs BO1 through BO9 are not used for the BCI-C controller. Figure 2 shows the locations of each LED. The following table provides a description of each LED activity, an indication or troubleshooting tips for each, and any notes.

Figure 2. LED locations

[Diagram showing the locations of LEDs on the BCI-C unit]

Table 1. LED Activities and Troubleshooting Tips
LED Name Activities Indication or Troubleshooting Tip (Denoted in Bullets) Notes
Marquee LED Shows solid green when the unit is powered and no problems exist Indicates normal operation
Marquee LED Shows solid red when the unit is powered, but represents low power or a malfunction
  • If low power; could be under voltage or the microprocessor has malfunction.
  • If malfunction; un-power and then re-power unit to bring the device back up to normal operation.
Marquee LED Shows blinking red when an alarm exists Alarm; when an alarm is triggered, for example, when a point goes into fault condition because of point failure or there is an indication of a custom alarm in TGP2
LED not lit Indicates power is OFF or there is a malfunction
  • OFF or malfunction; cycle the power.
Link and IMC TX blinks green Blinks at the data transfer rate when the unit transfers data to other devices on the link TX LED: Regardless of connectivity or not, this LED will constantly blink as it continually looks for devices to communicate to.
Link and IMC RX blinks yellow Blinks at the data transfer rate when the unit receives data from other devices on the link
Link and IMC LED not lit
  • ON solid yellow; indicates there is reverse polarity
  • Not lit; cycle the power to reestablish communication
LED not lit: Determine if, for example, a Tracer™ SC or BACnet device is trying to talk to the controller or if it is capable of talking to the controller. Also determine if the communication status shows down all of the time.
Service Shows solid green Indicates controller is operating normally, or TechView is in Binding View and commanding to the BCI-C to turn On the LED Press and hold during power up to place controller into boot code or press and hold for a count of approximately 10 seconds to clear the Device ID.
Service Blinks green Indicates controller is not accessing application software What is Boot Code? When the UC400 is placed into boot code, the system will not run any applications such as trending, scheduling, and TGP2 runtime.
Service LED not lit Restore; using TU service tool
Binary 01 to Binary 09 LED not lit Not Used

BACnet Data Points and Configuration Property Definitions

The BCI-C device allows certain models of Trane chillers with CH530 controls to communicate with BACnet systems and devices using BACnet MS/TP. This section includes information about:

BACnet Protocol Implementation Conformance Statement (PICS)

Standardized Device Profile (Annex L)
Profile Description Supported Profile
BACnet Advanced Application Controller (B-AAC) ✔️
BACnet Application Specific Controller (B-ASC) ✔️
BACnet Building Controller (B-BC) ✔️
BACnet Operator Workstation (B-OWS)
BACnet Smart Actuator (B-SA)
BACnet Smart Sensor (B-SS)
Interoperability Building Blocks (Annex K)
Data Sharing Description Supported BIBB
Data Sharing-COV-B (DS-COV-B) ✔️
Data Sharing-ReadProperty-A (DS-RP-A) ✔️
Data Sharing-ReadProperty-B (DS-RP-B) ✔️
Data Sharing-ReadPropertyMultiple-B (DS-RPM-B) ✔️
Data Sharing-WriteProperty-A (DS-WP-A) ✔️
Data Sharing-WriteProperty-B (DS-WP-B) ✔️
Data Sharing-WriteProperty Multiple-B (DS-WPM-B) ✔️
Alarm and Event Management Description Supported BIBB
Alarm and Event-ACKI-B (AE-ACK-B) ✔️
Alarm and Event-Alarm Summary-B (AE-ASUM-B) ✔️
Alarm and Event-Enrollment Summary-B (AE-ESUM-B) ✔️
Alarm and Event-Information-B (AE-INFO-B) ✔️
Alarm and Event-Notification Internal-B (AE-N-I-B) ✔️
Trending Description Supported BIBB
Trending-Automated Trend Retrieval-B (T-ATR-B) ✔️
Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B) ✔️
Device Management Description Supported BIBB
Device Management-Backup and Restore-B (DM-BR-B) ✔️
Device Management-Device Communication Control-B (DM-DCC-B) ✔️
Device Management-Dynamic Device Binding-A (DM-DDB-A) ✔️
Device Management-Dynamic Device Binding-B (DM-DDB-B) ✔️
Device Management-Dynamic Object Binding-B (DM-DOB-B) ✔️
Device Management-List Manipulation-B (DM-LM-B) ✔️
Device Management-Object Creation and Deletion-B (DM-OCD-B) ✔️
Device Management-Private Transfer-A (DM-PT-A) ✔️
Device Management-Private Transfer-B (DM-PT-B) ✔️
Device Management-Reinitialize Device-B (DM-RD-B) ✔️
Device Management-TimeSynchronization-B (DM-TS-B) ✔️

Segmentation Capability

Segmentation Description Supported Segment
Segmented Requests/ Window Size: 1 ✔️
Segmented Responses/ Window Size: 1 ✔️

Object Types

Table 2. Descriptions and configurations
Object Type Required Properties Read Properties Written(a) Optional Properties Read Ability to Create Ability to Delete
Analog Input
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Present Value
  • Status_Flags
  • Event State
  • Out_Of_Service
  • Units
  • Object_Name
  • Description
  • Out_Of_Service
  • Present Value
  • Reliability
  • Min_Pres_Value
  • Max_Pres_Value
  • COV Increment
  • Time_Delay
  • Notification Class
  • High_Limit
  • Low Limit
  • Deadband
  • Limit_Enable
  • Event Enable
  • Notify_Type
  • Description
  • Reliability
  • Min_Pres_Value
  • Max_Pres_Value
  • COV Increment
  • Time_Delay
  • Notification_Class
  • High_Limit
  • Low Limit
  • Deadband
  • Limit Enable
  • Event Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
Yes Yes, only user created objects
Analog Output
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Status_Flags
  • Event State
  • Out_Of_Service
  • Units
  • Priority_Array
  • Relinquish_Default
  • Object_Name
  • Description
  • Out_Of_Service
  • Present Value
  • Reliability
  • Min_Pres_Value
  • Max_Pres_Value
  • COV Increment
  • Time_Delay
  • Notification_Class
  • High_Limit
  • Low Limit
  • Deadband
  • Limit Enable
  • Event Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
  • Description
  • Reliability
  • Out_Of_Service
  • Min_Pres-Value
  • Max_Pres_Value
  • COV Increment
  • Time_Delay
  • Notification_Class
  • High_Limit
  • Low Limit
  • Deadband
  • Limit Enable
  • Event Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
Yes Yes, only user created objects
Analog Value
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Present_Value
  • Status_Flags
  • Event State
  • Out_Of_Service
  • Units
  • Object_Name
  • Description
  • Out_Of_Service
  • Present Value
  • Reliability
  • Min_Pres_Value
  • Max_Pres_Value
  • COV Increment
  • Time_Delay
  • Notification_Class
  • High_Limit
  • Low Limit
  • Deadband
  • Limit Enable
  • Event Enable
  • Notify_Type
  • Description
  • Reliability
  • Priority_Array
  • Relinquish_Default
  • COV Increment
  • Time_Delay
  • Notification_Class
  • High_Limit
  • Low Limit
  • Deadband
  • Limit Enable
  • Event Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
Yes Yes, only user created objects
Binary Input
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Present Value
  • Status_Flags
  • Event State
  • Out_Of_Service
  • Polarity
  • Object_Name
  • Description
  • Out_Of_Service
  • Inactive Text
  • Active_Text
  • Present_Value
  • Reliability
  • Change_Of_State_Count
  • Elapsed_Active_Time
  • Time_Delay
  • Notification_Class
  • Alarm Value
  • Event_Enable
  • Acked Transitions
  • Notify_Type
  • Description
  • Inactive_Text
  • Active_Text
  • Change_Of_State_Time
  • Change_Of_State_Count
  • Time Of State Count Reset
  • Elapsed_Active_Time
  • Time Of Active Time Reset
  • Time_Delay
  • Notification_Class
  • Alarm Value
  • Event_Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
  • Reliability
Yes Yes, only user created objects
Binary Output
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Present Value
  • Status_Flags
  • Event State
  • Out_Of_Service
  • Polarity
  • Priority_Array
  • Relinquish_Default
  • Object_Name
  • Description
  • Out_Of_Service
  • Inactive Text
  • Active_Text
  • Present_Value
  • Reliability
  • Change_Of_State_Count
  • Elapsed_Active_Time
  • Minimum_On_Time
  • Minimum_Off_Time
  • Relinquish_Default
  • Time_Delay
  • Notification Class
  • Event_Enable
  • Acked Transitions
  • Notify_Type
  • Description
  • Inactive Text
  • Active_Text
  • Change_Of_State_Time
  • Change_Of_State_Count
  • Time_Of_State_Count_Reset
  • Elapsed_Active_Time
  • Time Of Active Time Reset
  • Minimum On Time
  • Minimum_Off_Time
  • Time_Delay
  • Notification Class
  • Feedback Value
  • Event Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
  • Reliability
Yes Yes, only user created objects
Binary Value
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Present_Value
  • Status_Flags
  • Event State
  • Out_Of_Service
  • Polarity
  • Object_Name
  • Description
  • Out_Of_Service
  • Inactive_Text
  • Active_Text
  • Present_Value
  • Reliability
  • Change_Of_State_Count
  • Elapsed_Active_Time
  • Minimum_On_Time
  • Minimum_Off_Time
  • Relinquish_Default
  • Time_Delay
  • Notification Class
  • Alarm Value
  • Event_Enable
  • Acked Transitions
  • Notify_Type
  • Description
  • Inactive_Text
  • Active_Text
  • Change_Of_State_Time
  • Change_Of_State_Count
  • Time_Of_State_Count_Reset
  • Elapsed_Active_Time
  • Time_Of_Active_Time_Reset
  • Priority_Array
  • Relinquish_Default
  • Minimum_On_Time
  • Minimum_Off_Time
  • Time_Delay
  • Notification Class
  • Alarm Value
  • Event_Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
  • Reliability
Yes Yes, only user created objects
Device
  • Object_Identifier
  • Object_Name
  • Object_Type
  • System_Status
  • Vendor Name
  • Vendor_Identifier
  • Model Name
  • Firmware_Revision
  • Application_Software_Version
  • Protocol Version
  • Protocol_Revision
  • Protocol_Services_Supported
  • Protocol_Object_Types_Supported
  • Object_List
  • Max_APDU_Length_Accepted
  • Segmentation_Supported
  • APDU Timeout
  • Number Of APDU Retries
  • Device_Address_Binding
  • Database Revision
  • Object_Name
  • Description
  • Location
  • Max_Segments_Accepted
  • APDU_Segment_Timeout
  • APDU Timeout
  • Number Of APDU Retries
  • Backup_Failure_Timeout
  • Location
  • Description
  • Max_Segments_Accepted
  • APDU_Segment_Timeout
  • APDU Timeout
  • Number Of APDU Retries
  • Backup_Failure_Timeout
  • Active_COV_Subscriptions
None None
Event Enrollment
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Event_Type
  • Notify_Type
  • Event_Parameters
  • Object_Property_Reference
  • Event State
  • Event Enable
  • Acked_Transitions
  • Notification_Class
  • Event_Time_Stamps
  • Object_Name
  • Notify_Type
  • Event Parameters
  • Object_Property_Reference
  • Event Enable
  • Notification_Class
  • Notify_Type
  • Event Parameters
  • Object_Property_Reference
  • Event Enable
  • Notification_Class
Yes Yes, only user created objects
Multistate Input
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Present Value
  • Status_Flags
  • Event State
  • Out_Of_Service
  • Number Of States
  • Object_Name
  • Description
  • State Text
  • Out Of Service
  • Present_Value
  • Reliability
  • Time_Delay
  • Notification Class
  • Alarm Values
  • Fault Values
  • Event_Enable
  • Notify_Type
  • State_Text
  • Reliability
  • Time_Delay
  • Notification_Class
  • Alarm Values
  • Fault_Values
  • Event Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
Yes Yes, only user created objects
Multistate Output
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Present Value
  • Status_Flags
  • Multistate Value
  • Event State
  • Out Of Service
  • Number Of States
  • Priority_Array
  • Relinquish Default
  • Object_Name
  • Description
  • State Text
  • Out_Of_Service
  • Present_Value
  • Reliability
  • Time_Delay
  • Notification Class
  • Event_Enable
  • Notify_Type
  • State_Text
  • Reliability
  • Relinquish_Default
  • Time_Delay
  • Notification_Class
  • Feedback Values
  • Event Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
Yes Yes, only user created objects
Multistate Value
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Present Value
  • Status_Flags
  • Event State
  • Out_Of_Service
  • Number_Of_States
  • Object_Name
  • Description
  • State Text
  • Out Of Service
  • Present Value
  • Reliability
  • Priority_Array
  • Relinquish_Default
  • Time_Delay
  • Notification_Class
  • Alarm Values
  • Fault_Values
  • Event Enable
  • Notify_Type
  • State Text
  • Reliability
  • Relinquish_Default
  • Time_Delay
  • Notification_Class
  • Alarm_Values
  • Fault Values
  • Event Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
Yes Yes, only user created objects
Notification Class
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Priority
  • Ack_Required
  • Notification_Class
  • Recipient_List
  • Object_Name
  • Priority
  • Ack_Required
  • Recipient_List
None Yes Yes, only user created objects
Trend
  • Object_Identifier
  • Object_Name
  • Object_Type
  • Start_Time
  • Log_Enable
  • Stop_Time
  • Start_Time
  • Log_DeviceObjectProperty
  • Log_Enable
  • Stop_Time
  • Log_Interval
  • Stop_When_Full
  • Buffer Size
  • Log_Buffer
  • Record Count
  • Total Record Count
  • Event State
  • Log_Buffer
  • Record Count
  • Notification Threshold
  • Notification Class
  • Event Enable
  • Notify_Type
  • Acked Transitions
  • Event_Time_Stamps
  • Object_Name
  • Description
  • State_Text
  • Out_Of_Service
  • Present_Value
  • Reliability
  • Time_Delay
  • Notification_Class
  • Alarm Values
  • Fault_Values
  • Event Enable
  • Notify_Type
  • State_Text
  • Reliability
  • Relinquish_Default
  • Time_Delay
  • Notification_Class
  • Feedback Values
  • Event Enable
  • Acked Transitions
  • Notify_Type
  • Event_Time_Stamps
Yes Yes, only user created objects

BACnet Protocol

Data Link Layer Options
Data Link Layer Description Supported
ANSI/ATA 878.1, 2.5 Mb ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), Baud Rate(s)
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7) (10Base2, 10Base5, 10BaseT, Fiber)
LonTalk, (Clause 11), Medium
MS/TP Master (Clause 9), Baud Rate(s): 9600, 19200, 38400, 76800, and 115200 @1.5% Nominal Baud Rate ✔️
MS/TP Slave (Clause 9), Baud Rate(s)
Other
Point-to-Point, EIA 232 (Clause 10), Baud Rate(s): 9600, 19200, 38400
Point-to-Point, Modem (Clause 10), Baud Rate(s): 9600, 19200, 38400
Device Address Binding
Device Address Binding Supported?
Static Device Binding Supported ✔️
Networking Options
Networking Descriptions Supported Option
Annex H, BACnet Tunneling
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD Support Registrations by Foreign Devices?
Router
Character Sets

Indicates support for multiple characters sets, but does not imply that all character sets are supported simultaneously. Maximum supported string length is 64 bytes (any character set).

Character Set Descriptions Supported
ANSI X3.4
IBM/Microsoft DBCS
ISO 10646 (UCS-4) ✔️
ISO 10646 (UCS2) ✔️
ISO 8859-1 ✔️
JIS C 6226

Object and Diagnostic Data Points and Corresponding Chiller Models

For quick reference, the following tables are listed and sorted two different ways. Tables 3 through 9 are listed by input/output type and sorted by object identifier. These tables provide the user with the units type for each object type. Table 9, p. 22 is sorted by object name and provides a complete list of object names, types, values/ranges, and descriptions. Not all points are available to the user. The available data points are defined during self-configuration and are dependent on the type of equipment. Listed at the bottom of tables 3 through 8 are specific footnotes that correspond to either specific chiller models or object states that are identified by a larger dot or boldface text.

Note: The last four columns in each table identifies which chiller model corresponds with each object name.

Table 3. Analog Output

Object Identifier Object Name Description Dimensionality Valid Range Relinq Default RTWD/RTUD RTHD RTAC CGAM
Analog Output 1 Chilled Water Setpoint Desired leaving water temperature if chiller is in cooling mode. Temperature 0°F to 75°F (-17.8°C to 23.8°C) 44°F (6.7°C)
Analog Output 2 Current Limit Setpoint Sets the maximum capacity that the chiller can use. Percent 0% to 120% 100%
Analog Output 3 Demand Limit Setpoint Sets the maximum capacity that the chiller can use. Percent 0% to 120% 100%
Analog Output 4 Hot Water Setpoint Desired leaving water temperature if chiller is in heating mode. Temperature 80°F to 140°F (26.7°C to 60°C) 120°F (48.9°C) (a) (a) (a) (b)
Analog Output 5 Base Loading Setpoint Capacity level to which the chiller should control when base loading is active. Percent 0% to 100% 50%

(a) Leaving condenser water temperature control.

(b) Hot water control with heat pumps in heating mode.

Table 4. Analog Input

Object Identifier Object Name Description Dimensionality RTWD/RTUD RTHD RTAC CGAM
Analog Input, 1 Active Cool/Heat Setpoint Active chiller water or hot water setpoint. Temperature
Analog Input, 2 Active Current Limit Setpoint Active capacity current limit setpoint. Percent
Analog Input, 3 Active Demand Limit Setpoint Active demand limit setpoint. Percent
Analog Input 4 Active Base Loading Setpoint Value of base loading setpoint currently being used by the chiller. Percent
Analog Input, 5 Actual Running Capacity Level of capacity that the chiller is currently running at. Percent
Analog Input, 6 Evaporator Refrigerant Pressure- Ckt1 Circuit 1 evaporator refrigerant pressure. Pressure
Analog Input, 7 Suction Pressure- Ckt 1 Circuit 1 suction pressure. Pressure
Analog Input, 8 Suction Pressure- Ckt 1 Circuit 1 suction pressure. Pressure
Analog Input, 9 Evaporator Refrigerant Pressure- Ckt 2 Circuit 2 evaporator refrigerant pressure. Pressure
Analog Input, 10 Suction Pressure- Ckt 2 Circuit 2 suction pressure. Pressure
Analog Input, 11 Suction Pressure- Ckt 2 Circuit 2 suction pressure. Pressure
Analog Input, 12 Evaporator Saturated Refrigerant Temperature- Ckt 1 Circuit 1 evaporator refrigerant temperature. Temperature
Analog Input, 13 Suction Saturated Refrigerant Temperature- Ckt 1 Circuit 1 suction refrigerant temperature. Temperature
Analog Input, 14 Evaporator Saturated Refrigerant Temperature- Ckt 2 Circuit 2 evaporator refrigerant temperature. Temperature
Analog Input, 15 Suction Saturated Refrigerant Temperature- Ckt 2 Circuit 2 suction refrigerant temperature. Temperature
Analog Input, 16 Condenser Refrigerant Pressure- Ckt 1 Circuit 1 condenser refrigerant pressure. Pressure
Analog Input, 17 Discharge Pressure- Ckt 1 Circuit 1 discharge pressure. Pressure
Analog Input, 18 Condenser Refrigerant Pressure- Ckt 2 Circuit 2 condenser refrigerant pressure. Pressure
Analog Input, 19 Discharge Pressure- Ckt 2 Circuit 2 discharge pressure. Pressure
Analog Input, 20 Condenser Saturated Refrigerant Temperature- Ckt 1 Circuit 1 condenser refrigerant temperature. Temperature
Analog Input, 21 Discharge Saturated Refrigerant Temperature- Ckt 1 Circuit 1 discharge refrigerant temperature. Temperature
Analog Input, 22 Condenser Saturated Refrigerant Temperature- Ckt 2 Circuit 2 condenser refrigerant temperature. Temperature
Analog Input, 23 Discharge Saturated Refrigerant Temperature- Ckt 2 Circuit 2 discharge refrigerant temperature. Temperature
Analog Input, 24 Unit Power Consumption The power being consumed by the chiller. Power (a) (a) (a) (a)
Analog Input, 25 Local Atmospheric Pressure Local atmospheric pressure. Pressure
Analog Input, 26 Starts- Compressor 1A Number of starts for compressor 1A.
Analog Input, 27 Starts- Compressor 1B Number of starts for compressor 1B.
Analog Input, 28 Starts- Compressor 2A Number of starts for compressor 2A.
Analog Input, 29 Starts- Compressor 2B Number of starts for compressor 2B.
Analog Input, 30 Starts- Compressor 1C Number of starts for compressor 1C.
Analog Input, 31 Starts- Compressor 2A Number of starts for compressor 2A.
Analog Input, 32 Starts- Compressor 2B Number of starts for compressor 2B.
Analog Input, 33 Starts- Compressor 2C Number of starts for compressor 2C.
Analog Input, 34 Run Time- Compressor 1A Total run time of compressor 1A. Time
Analog Input, 35 Run Time- Compressor 1B Total run time of compressor 1B. Time
Analog Input, 36 Run Time- Compressor 2A Total run time of compressor 2A. Time
Analog Input, 37 Run Time- Compressor 2B Total run time of compressor 2B. Time
Analog Input, 38 Run Time- Compressor 1C Total run time of compressor 1C. Time
Analog Input, 39 Run Time- Compressor 2A Total run time of compressor 2A. Time
Analog Input, 40 Run Time- Compressor 2B Total run time of compressor 2B. Time
Analog Input, 41 Run Time- Compressor 2C Total run time of compressor 2C. Time
Analog Input, 42 Airflow Percentage- Circuit 1 Approximate airflow percentage of circuit 1. Percent
Analog Input, 43 Airflow Percentage- Circuit 2 Approximate airflow percentage of circuit 2. Percent
Analog Input, 44 Evaporator Entering Water Temp Temperature of the water entering the evaporator. Temperature
Analog Input, 45 Evaporator Leaving Water Temp Temperature of the water leaving the evaporator. Temperature
Analog Input, 46 Condenser Entering Water Temp Temperature of the water entering the condenser. Temperature
Analog Input, 47 Condenser Leaving Water Temp Temperature of the water leaving the condenser. Temperature
Analog Input, 48 High Side Oil Pressure- Compressor 1A Pressure of the oil at the high side of compressor 1A. Pressure
Analog Input, 49 High Side Oil Pressure- Compressor 1B Pressure of the oil at the high side of compressor 1B. Pressure
Analog Input, 50 High Side Oil Pressure- Compressor 2A Pressure of the oil at the high side of compressor 2A. Pressure
Analog Input, 51 High Side Oil Pressure- Compressor 2B Pressure of the oil at the high side of compressor 2B. Pressure
Analog Input, 52 Oil Temp- Compressor 1A Temperature of the oil in compressor 1A. Temperature
Analog Input, 52 Oil Temp- Compressor 1B Temperature of the oil in compressor 1B. Temperature
Analog Input, 54 Oil Temp- Compressor 2A Temperature of the oil in compressor 2A. Temperature
Analog Input, 55 Oil Temp- Compressor 2B Temperature of the oil in compressor 2B. Temperature
Analog Input, 56 Refrigerant Disch Temp- Ckt 1 Temperature of the refrigerant being discharged from Ckt 1. Temperature
Analog Input, 57 Outdoor Air Temperature Outdoor air temperature. Temperature
Analog Input, 58 Condenser Control Output Percentage of condenser water flow being requested by the chiller. Percent
Analog Input, 59 Phase AB Voltage- Compressor 1A Phase AB voltage, compressor 1A. Voltage
Analog Input, 60 Phase BC Voltage- Compressor 1A Phase BC voltage, compressor 1A. Voltage
Analog Input, 61 Phase CA Voltage- Compressor 1A Phase CA voltage, compressor 1A. Voltage
Analog Input, 62 Phase AB Voltage- Compressor 1B Phase AB voltage, compressor 1B. Voltage
Analog Input, 63 Phase BC Voltage- Compressor 1B Phase BC voltage, compressor 1B. Voltage
Analog Input, 64 Phase CA Voltage- Compressor 1B Phase CA voltage, compressor 1B. Voltage
Analog Input, 65 Phase AB Voltage- Compressor 2A Phase AB voltage, compressor 2A. Voltage
Analog Input, 66 Phase BC Voltage- Compressor 2A Phase BC voltage, compressor 2A. Voltage
Analog Input, 67 Phase CA Voltage- Compressor 2A Phase CA voltage, compressor 2A. Voltage
Analog Input, 68 Phase AB Voltage- Compressor 2B Phase AB voltage, compressor 2B. Voltage
Analog Input, 69 Phase BC Voltage- Compressor 2B Phase BC voltage, compressor 2B. Voltage
Analog Input, 70 Phase CA Voltage- Compressor 2B Phase CA voltage, compressor 2B. Voltage
Analog Input, 71 Line 1 Current (in Amps)- Compressor 1A Line 1 Current (in Amps)- Compressor 1A. Current
Analog Input, 72 Line 2 Current (in Amps)- Compressor 1A Line 2 Current (in Amps)- Compressor 1A. Current
Analog Input, 73 Line 3 Current (in Amps)- Compressor 1A Line 3 Current (in Amps)- Compressor 1A. Current
Analog Input, 74 Line 1 Current (in Amps)- Compressor 1B Line 1 Current (in Amps)- Compressor 1B. Current
Analog Input, 75 Line 2 Current (in Amps)- Compressor 1B Line 2 Current (in Amps)- Compressor 1B. Current
Analog Input, 76 Line 3 Current (in Amps)- Compressor 1B Line 3 Current (in Amps)- Compressor 1B. Current
Analog Input, 77 Line 1 Current (in Amps)- Compressor 2A Line 1 Current (in Amps)- Compressor 2A. Current
Analog Input, 78 Line 2 Current (in Amps)- Compressor 2A Line 2 Current (in Amps)- Compressor 2A. Current
Analog Input, 79 Line 3 Current (in Amps)- Compressor 2A Line 3 Current (in Amps)- Compressor 2A. Current
Analog Input, 80 Line 1 Current (in Amps)- Compressor 2B Line 1 Current (in Amps)- Compressor 2B. Current
Analog Input, 81 Line 2 Current (in Amps)- Compressor 2B Line 2 Current (in Amps)- Compressor 2B. Current
Analog Input, 82 Line 3 Current (in Amps)- Compressor 2B Line 3 Current (in Amps)- Compressor 2B. Current
Analog Input, 83 Line 1 Current (%RLA)- Compressor 1A Line 1 Current (%RLA)- Compressor 1A. Percent
Analog Input, 84 Line 2 Current (%RLA)- Compressor 1A Line 2 Current (%RLA)- Compressor 1A. Percent
Analog Input, 85 Line 3 Current (%RLA)- Compressor 1A Line 3 Current (%RLA)- Compressor 1A. Percent
Analog Input, 86 Line 1 Current (%RLA)- Compressor 1B Line 1 Current (%RLA)- Compressor 1B. Percent
Analog Input, 87 Line 2 Current (%RLA)- Compressor 1B Line 2 Current (%RLA)- Compressor 1B. Percent
Analog Input, 88 Line 3 Current (%RLA)- Compressor 1B Line 3 Current (%RLA)- Compressor 1B. Percent
Analog Input, 89 Line 1 Current (%RLA)- Compressor 2A Line 1 Current (%RLA)- Compressor 2A. Percent
Analog Input, 90 Line 2 Current (%RLA)- Compressor 2A Line 2 Current (%RLA)- Compressor 2A. Percent
Analog Input, 91 Line 3 Current (%RLA)- Compressor 2A Line 3 Current (%RLA)- Compressor 2A. Percent
Analog Input, 92 Line 1 Current (%RLA)- Compressor 2B Line 1 Current (%RLA)- Compressor 2B. Percent
Analog Input, 93 Line 2 Current (%RLA)- Compressor 2B Line 2 Current (%RLA)- Compressor 2B. Percent
Analog Input, 94 Line 3 Current (%RLA)- Compressor 2B Line 3 Current (%RLA)- Compressor 2B. Percent
Analog Input, 95 Number of Circuits Number of Circuits. None
Analog Input, 96 Number of Compressors, Ckt 1 Number of Compressors, Ckt 1. None
Analog Input, 97 Number of Compressors, Ckt 2 Number of Compressors, Ckt 2. None
Analog Input, 98 Chiller Design Capacity Design Capacity of the Chiller. None

Table 5. Multistate Output

Object Identifier Object Name Description Relinq Default Object States RTWD/RTUD RTHD RTAC CGAM
Multi-State Output, 1 Chiller Mode Command Mode of operation of the chiller. 1 = Cool 1 = HVAC Cool
2 = HVAC_Heat
3 = HVAC_Ice (a)
4 = Not Used

(a) Chiller should be selected for ice making.

Table 6. Multistate Input

BCI-C Object Identifier Object Name Description Object States RTWD/RTUD RTHD RTAC CGAM
Multi-State Input, 1 Running Mode Indicates the primary running mode of the chiller. 1 = Chiller Off
2 = Chiller in Start Mode
3 = Chiller in Run Mode
4 = Chiller in Pre-shutdown Mode
5 = Chiller in Service Mode
Multi-State Input, 2 Operating Mode Indicates the primary operating mode of the chiller. 1 = HVAC_Cool
2 = HVAC_Heat
3 = HVAC_Ice (a)
4 = Not Used
Multi-State Input, 3 MP Communication Status Communication status. 1 = R-22
2 = Communication
3 = Communication Lost
4 = Failed to Established
5 = Waiting to Establish
Multi-State Input, 4 Refrigerant Type Refrigerant type. 1 = R-11
2 = R-12
3 = R-22
4 = R-123
5 R-134A
6 = R407C
7 = R-410A
Multi-State Input, 5 Model Information Indicates the model type of the chiller. 1 = RTA
2 = CVH
3 = CVG
4 = CVR
5 = CDH
6 = RTH
7 = CGW
8 = CGA
9 = CCA
10 = RTW
11 = RTX
12 = RTU
13 = CCU
14 = CXA
15 = CGC
16 = RAU
Multi-State Input, 6 Cooling Type Cooling type of the condenser. 1 = Water Cooled
2 = Air Cooled
Multi-State Input, 7 Manufacturing Location Location where chiller was manufactured. 1 = Field Applied
2 = La Crosse
3 = Pueblo
4 = Charmes
5 = Rushville
6 = Macon
7 = Waco
8 = Lexington
9 = Forsyth
10 = Clarksville
11 = Penang
12 = Colchester
13 = Curitiba
14 = Taicang
15 = Taiwan
16 = Epinal
17 = Golbey

(a) Chiller should be selected for ice making.

Table 7. Binary Output

Object Identifier Object Name Description Relinq Default Object States RTWD/RTUD RTHD RTAC CGAM
Binary Output, 1 Chiller Auto Stop Command Allows the chiller to run if conditions for running are met. False Inactive = Stop
Active = Auto
Binary Output, 2 Remote Diagnostic Reset Command Resets remotely diagnostics that can be reset. False Inactive = No Reset Request
Active = Reset Request
Binary Output, 3 Base Loading Auto/On Request Requests chiller to use base loading. False Inactive = Auto
Active = On
Binary Output, 4 Noise Reduction Request Requests chiller to enter mode to reduce noise. False Inactive = Normal
Active = Reduced Noise

Table 8. Binary Input

Object Identifier Object Name Description Object States RTWD/RTUD RTHD RTAC CGAM
Binary Input, 23 Alarm Present Indicates if an alarm is active. Inactive = No Alarm
Active = Alarm
Binary Input, 8 Base Loading Active Indicates if the base loading control method is currently being used. Inactive = Inactive
Active = Active
Binary Input, 3 Capacity Limited Indicates if conditions may exist that prevent the chiller from reaching setpoint. Inactive = Not Limited
Active = Limited
Binary Input, 4 Chiller Running State Indicates if the chiller is running or stopped. Inactive = Off
Active = On
Binary Input, 9 Compressor 1A Running Indicates if compressor 1A is running. Inactive = Off
Active = Running
Binary Input, 10 Compressor 1B Running Indicates if compressor 1B is running. Inactive = Off
Active = Running
Binary Input, 13 Compressor 1C Running Indicates if compressor 1C is running. Inactive = Off
Active = Running
Binary Input, 11 Compressor 2A Running Indicates if compressor 2A is running. Inactive = Off
Active = Running
Binary Input, 14 Compressor 2A Running Indicates if compressor 2A is running. Inactive = Off
Active = Running
Binary Input, 12 Compressor 2B Running Indicates if compressor 2B is running. Inactive = Off
Active = Running
Binary Input, 15 Compressor 2B Running Indicates if compressor 2B is running. Inactive = Off
Active = Running
Binary Input, 16 Compressor 2C Running Indicates if compressor 2C is running. Inactive = Off
Active = Running
Binary Input, 5 Condenser Water Flow Status Condenser water flow status. Inactive = No Flow
Active = Flow
Binary Input, 19 Condenser Water Pump Request Indicates a request from the chiller to turn on the condenser water pump. Inactive = Off
Active = On
Binary Input, 21 Defrost Mode (or in Defrost) Indicates if one or more circuits are in a defrost mode. Inactive = Not in Defrost
Active = Defrost
(a)
Binary Input, 22 Evaporator Water Flow Status Indicates if water is flowing through the evaporator. Inactive = No Flow
Active = Flow
Binary Input, 17 Evaporator Water Pump Request Indicates a request from the chiller to turn on the evaporator water pump. Inactive = Off
Active = On
Binary Input, 7 Head Relief Request Indicates if the chiller is asking an outside system to provide more heat rejection from the condenser water loop. Inactive = Off
Active = On
Binary Input, 25 Last Diagnostic Indicates last diagnostic for the chiller. Inactive = Off
Active = On
Binary Input, 2 Local Setpoint Control Indicates if the chiller is being controlled by local setpoints instead of BAS setpoints. Inactive = Remote Control
Active = Local Control
Binary Input, 6 Maximum Capacity Indicates if all available chiller capacity is being used. Inactive = Off
Active = On
Binary Input, 5 Noise Reduction Active Indicates if the chiller is in a state where noise is being reduced. Inactive = Off
Active = On
Binary Input, 1 Run Enabled Indicates if the chiller is available to run or is currently running. Inactive = Stop
Active = Auto
Binary Input, 24 Shutdown Alarm Present Indicates if a shutdown alarm is active. Inactive = No Alarm
Active = None
Binary Input, 18 Water Pump Request Indicates a request from the chiller to turn on the water pump. Inactive = Off
Active = On

Table 9. All Object Types Sorted by Object Name

(Refer to previous tables for detailed descriptions of objects)

Object Identifier(a) Object Name Description
Analog Input 4 Active Base Loading Setpoint Value of base loading setpoint currently being used by the chiller.
Analog Input, 1 Active Cool/Heat Setpoint Temperature Active chiller water or hot water setpoint.
Analog Input, 2 Active Current Limit Setpoint Active capacity current limit setpoint.
Analog Input, 3 Active Demand Limit Setpoint Active demand limit setpoint.
Analog Input, 5 Actual Running Capacity Level of capacity that the chiller is currently running at.
Analog Input, 42 Airflow Percentage- Circuit 1 Approximate airflow percentage of circuit 1.
Analog Input, 43 Airflow Percentage- Circuit 2 Approximate airflow percentage of circuit 2.
Binary Input, 23 Alarm Present Indicates if an alarm is active.
Binary Input, 8 Base Loading Active Indicates if the base loading control method is currently being used.
Binary Output, 3 Base Loading Auto/On Request Requests chiller to use base loading.
Analog Output 5 Base Loading Setpoint Capacity level to which the chiller should control when base loading is active.
Binary Input, 3 Capacity Limited Indicates if conditions may exist that prevent the chiller from reaching setpoint.
Analog Output 1 Chilled Water Setpoint Desired leaving water temperature if chiller is in cooling mode.
Binary Output, 1 Chiller Auto Stop Command Allows the chiller to run if conditions for running are met.
Binary Output, 1 Chiller Auto Stop Command Allows the chiller to run if conditions for running are met.
Analog Input, 98 Chiller Design Capacity Design capacity of the chiller.
Binary Input, 4 Chiller Running State Indicates if the chiller is running or stopped.
Binary Input, 9 Compressor 1A Running Indicates if compressor 1A is running.
Binary Input, 10 Compressor 1B Running Indicates if compressor 1B is running.
Binary Input, 13 Compressor 1C Running Indicates if compressor 1C is running.
Binary Input, 11 Compressor 2A Running Indicates if compressor 2A is running.
Binary Input, 14 Compressor 2A Running Indicates if compressor 2A is running.
Binary Input, 12 Compressor 2B Running Indicates if compressor 2B is running.
Binary Input, 15 Compressor 2B Running Indicates if compressor 2B is running.
Binary Input, 16 Compressor 2C Running Indicates if compressor 2C is running.
Analog Input, 58 Condenser Control Output Percentage of condenser water flow being requested by the chiller.
Analog Input, 46 Condenser Entering Water Temp Temperature of the water entering the condenser.
Analog Input, 47 Condenser Leaving Water Temp Temperature of the water leaving the condenser.
Analog Input, 16 Condenser Refrigerant Pressure- Ckt 1 Circuit 1 condenser refrigerant pressure.
Analog Input, 18 Condenser Refrigerant Pressure- Ckt 2 Circuit 2 condenser refrigerant pressure.
Analog Input, 20 Condenser Saturated Refrigerant Temperature- Ckt 1 Circuit 1 condenser refrigerant temperature.
Analog Input, 22 Condenser Saturated Refrigerant Temperature- Ckt 2 Circuit 2 condenser refrigerant temperature.
Binary Input, 5 Condenser Water Flow Status Condenser water flow status.
Binary Input, 19 Condenser Water Pump Request Indicates a request from the chiller to turn on the condenser water pump.
Analog Input, 2 Current Limit Setpoint Sets the maximum capacity that the chiller can use.
Binary Input, 21 Defrost Mode (or in Defrost) Indicates if one or more circuits are in a defrost mode.
Analog Input, 3 Demand Limit Setpoint Sets the maximum capacity that the chiller can use.
Analog Input, 17 Discharge Pressure- Ckt 1 Circuit 1 discharge pressure.
Analog Input, 19 Discharge Pressure- Ckt 2 Circuit 2 discharge pressure.
Analog Input, 21 Discharge Saturated Refrigerant Temperature- Ckt 1 Circuit 1 discharge refrigerant temperature.
Analog Input, 23 Discharge Saturated Refrigerant Temperature- Ckt 2 Circuit 2 discharge refrigerant temperature.
Analog Input, 44 Evaporator Entering Water Temp Temperature of the water entering the evaporator.
Analog Input, 45 Evaporator Leaving Water Temp Temperature of the water leaving the evaporator.
Binary Input, 22 Evaporator Water Flow Status Indicates if water is flowing through the evaporator.
Binary Input, 17 Evaporator Water Pump Request Indicates a request from the chiller to turn on the evaporator water pump.
Analog Input, 9 Evaporator Refrigerant Pressure- Ckt 2 Circuit 2 evaporator refrigerant pressure.
Binary Input, 7 Head Relief Request Indicates if the chiller is asking an outside system to provide more heat rejection from the condenser water loop.
Analog Input, 48 High Side Oil Pressure- Compressor 1A Pressure of the oil at the high side of compressor 1A.
Analog Input, 49 High Side Oil Pressure- Compressor 1B Pressure of the oil at the high side of compressor 1B.
Analog Input, 50 High Side Oil Pressure- Compressor 2A Pressure of the oil at the high side of compressor 2A.
Analog Input, 51 High Side Oil Pressure- Compressor 2B Pressure of the oil at the high side of compressor 2B.
Analog Output 4 Hot Water Setpoint Desired leaving water temperature if chiller is in heating mode.
Binary Input, 25 Last Diagnostic Indicates the last diagnostic for the chiller.
Analog Input, 83 Line 1 Current (%RLA)- Compressor 1A Line 1 Current (%RLA)- Compressor 1A.
Analog Input, 86 Line 1 Current (%RLA)- Compressor 1B Line 1 Current (%RLA)- Compressor 1B.
Analog Input, 89 Line 1 Current (%RLA)- Compressor 2A Line 1 Current (%RLA)- Compressor 2A.
Analog Input, 92 Line 1 Current (%RLA)- Compressor 2B Line 1 Current (%RLA)- Compressor 2B.
Analog Input, 71 Line 1 Current (in Amps)- Compressor 1A Line 1 Current (in Amps)- Compressor 1A.
Analog Input, 74 Line 1 Current (in Amps)- Compressor 1B Line 1 Current (in Amps)- Compressor 1B.
Analog Input, 77 Line 1 Current (in Amps)- Compressor 2A Line 1 Current (in Amps)- Compressor 2A.
Analog Input, 80 Line 1 Current (in Amps)- Compressor 2B Line 1 Current (in Amps)- Compressor 2B.
Analog Input, 84 Line 2 Current (%RLA)- Compressor 1A Line 2 Current (%RLA)- Compressor 1A.
Analog Input, 87 Line 2 Current (%RLA)- Compressor 1B Line 2 Current (%RLA)- Compressor 1B.
Analog Input, 90 Line 2 Current (%RLA)- Compressor 2A Line 2 Current (%RLA)- Compressor 2A.
Analog Input, 93 Line 2 Current (%RLA)- Compressor 2B Line 2 Current (%RLA)- Compressor 2B.
Analog Input, 72 Line 2 Current (in Amps)- Compressor 1A Line 2 Current (in Amps)- Compressor 1A.
Analog Input, 75 Line 2 Current (in Amps)- Compressor 1B Line 2 Current (in Amps)- Compressor 1B.
Analog Input, 78 Line 2 Current (in Amps)- Compressor 2A Line 2 Current (in Amps)- Compressor 2A.
Analog Input, 81 Line 2 Current (in Amps)- Compressor 2B Line 2 Current (in Amps)- Compressor 2B.
Analog Input, 85 Line 3 Current (%RLA)- Compressor 1A Line 3 Current (%RLA)- Compressor 1A.
Analog Input, 88 Line 3 Current (%RLA)- Compressor 1B Line 3 Current (%RLA)- Compressor 1B.
Analog Input, 91 Line 3 Current (%RLA)- Compressor 2A Line 3 Current (%RLA)- Compressor 2A.
Analog Input, 94 Line 3 Current (%RLA)- Compressor 2B Line 3 Current (%RLA)- Compressor 2B.
Analog Input, 73 Line 3 Current (in Amps)- Compressor 1A Line 3 Current (in Amps)- Compressor 1A.
Analog Input, 76 Line 3 Current (in Amps)- Compressor 1B Line 3 Current (in Amps)- Compressor 1B.
Analog Input, 79 Line 3 Current (in Amps)- Compressor 2A Line 3 Current (in Amps)- Compressor 2A.
Analog Input, 82 Line 3 Current (in Amps)- Compressor 2B Line 3 Current (in Amps)- Compressor 2B.
Binary Input, 25 Last Diagnostic Indicates the last diagnostic for the chiller.
Analog Input, 25 Local Atmospheric Pressure Local atmospheric pressure.
Binary Input, 2 Local Setpoint Control Indicates if the chiller is being controlled by local setpoints instead of BAS setpoints.
Multi-State Input, 7 Manufacturing Location Location where chiller was manufactured.
Binary Input, 6 Maximum Capacity Indicates if all available chiller capacity is being used.
Multi-State Input, 5 Model Information Indicates the model type of the chiller.
Multi-State Input, 3 MP Communication Status Communication status.
Binary Input, 5 Noise Reduction Active Indicates if the chiller is in a state where noise is being reduced.
Binary Output, 4 Noise Reduction Request Requests chiller to enter mode to reduce noise.
Analog Input, 52 Oil Temp- Compressor 1A Temperature of the oil in compressor 1A.
Analog Input, 52 Oil Temp- Compressor 1B Temperature of the oil in compressor 1B.
Analog Input, 54 Oil Temp- Compressor 2A Temperature of the oil in compressor 2A.
Analog Input, 55 Oil Temp- Compressor 2B Temperature of the oil in compressor 2B.
Multi-State Input, 2 Operating Mode Indicates the primary operating mode of the chiller.
Analog Input, 57 Outdoor Air Temperature Outdoor air temperature.
Analog Input, 59 Phase AB Voltage- Compressor 1A Phase AB voltage, compressor 1A.
Analog Input, 62 Phase AB Voltage- Compressor 1B Phase AB voltage, compressor 1B.
Analog Input, 65 Phase AB Voltage- Compressor 2A Phase AB voltage, compressor 2A.
Analog Input, 68 Phase AB Voltage- Compressor 2B Phase AB voltage, compressor 2B.
Analog Input, 60 Phase BC Voltage- Compressor 1A Phase BC voltage, compressor 1A.
Analog Input, 63 Phase BC Voltage- Compressor 1B Phase BC voltage, compressor 1B.
Analog Input, 66 Phase BC Voltage- Compressor 2A Phase BC voltage, compressor 2A.
Analog Input, 69 Phase BC Voltage- Compressor 2B Phase BC voltage, compressor 2B.
Analog Input, 61 Phase CA Voltage- Compressor 1A Phase CA voltage, compressor 1A.
Analog Input, 64 Phase CA Voltage- Compressor 1B Phase CA voltage, compressor 1B.
Analog Input, 67 Phase CA Voltage- Compressor 2A Phase CA voltage, compressor 2A.
Analog Input, 70 Phase CA Voltage- Compressor 2B Phase CA voltage, compressor 2B.
Multi-State Input, 4 Refrigerant Type Refrigerant type.
Binary Output, 2 Remote Diagnostic Reset Command Resets remotely diagnostics that can be reset.
Binary Input, 1 Run Enabled Indicates if the chiller is available to run or is currently running.
Analog Input, 34 Run Time- Compressor 1A Total run time of compressor 1A.
Analog Input, 35 Run Time- Compressor 1B Total run time of compressor 1B.
Analog Input, 38 Run Time- Compressor 1C Total run time of compressor 1C.
Analog Input, 36 Run Time- Compressor 2A Total run time of compressor 2A.
Analog Input, 39 Run Time- Compressor 2A Total run time of compressor 2A.
Analog Input, 37 Run Time- Compressor 2B Total run time of compressor 2B.
Analog Input, 40 Run Time- Compressor 2B Total run time of compressor 2B.
Analog Input, 41 Run Time- Compressor 2C Total run time of compressor 2C.
Multi-State Input, 1 Running Mode Indicates the primary running mode of the chiller.
Binary Input, 24 Shutdown Alarm Present Indicates if a shutdown alarm is active.
Analog Input, 26 Starts- Compressor 1A Number of starts for compressor 1A.
Analog Input, 27 Starts- Compressor 1B Number of starts for compressor 1B.
Analog Input, 30 Starts- Compressor 1C Number of starts for compressor 1C.
Analog Input, 28 Starts- Compressor 2A Number of starts for compressor 2A.
Analog Input, 31 Starts- Compressor 2A Number of starts for compressor 2A.
Analog Input, 29 Starts- Compressor 2B Number of starts for compressor 2B.
Analog Input, 32 Starts- Compressor 2B Number of starts for compressor 2B.
Analog Input, 33 Starts- Compressor 2C Number of starts for compressor 2C.
Analog Input, 7 Suction Pressure- Ckt 1 Circuit 1 suction pressure.
Analog Input, 8 Suction Pressure- Ckt 1 Circuit 1 suction pressure.
Analog Input, 10 Suction Pressure- Ckt 2 Circuit 2 suction pressure.
Analog Input, 11 Suction Pressure- Ckt 2 Circuit 2 suction pressure.
Analog Input, 13 Suction Saturated Refrigerant Temperature- Ckt 1 Circuit 1 suction refrigerant temperature.
Analog Input, 15 Suction Saturated Refrigerant Temperature- Ckt 2 Circuit 2 suction refrigerant temperature.
Analog Input, 24 Unit Power Consumption The power being consumed by the chiller.
Analog Input, 18 Water Pump Request Indicates a request from the chiller to turn on the water pump.

BCI-C Alarming

The BCI-C unit has three binary input points that are used for communicating alarms and one binary output point that is used to reset alarms remotely. Those inputs and output points are:

  • BI 23; Alarm Present– This object indicates if any alarms are active regardless of severity. A notification will be sent to any recipients of the Information Notification Class object when the point transitions from No Alarm to Alarm.
  • BI 24; Shutdown Alarm Present– This object indicates if any alarms that result in the shutdown of the chiller are active. A notification will be sent to any recipients of the Critical Notification Class object when the point transitions from No Alarm to Alarm.
  • BI 25; Last Diagnostic– The active text of this object will reflect the description of the last diagnostic to occur on the chiller.
  • BO 2; Remote Diagnostic Reset Command– This object is used to remotely reset diagnostics on the chiller. Immediately after commanding this point value to 1, the BCI-C will send the reset command to the chiller and set this point value back to 0 and clear the priority array.

Note: Not all diagnostics are able to be reset remotely. Some will require local reset at the chiller front panel.

Additional Resources

Use the following documents and links as additional resources:

  • BACnet™ Communication Interface for Chillers (BCI-C) Field Kit Installation Guide (RF-SVN02)
  • Product support online: www.trane.com
  • www.bacnet.org
  • www.ashrae.org
  • www.bacnetassociation.org
  • Tracer TU Help online
  • Tracer™ BACnet™ Terminator Installation Instructions (X39641151-01)
  • Tracer™ TU Service Tool Getting Started Guide (TTU-SVN02) (X39641083)
  • Tracer™ TU Service Tool for Water-cooled CenTraVac™ Chillers with Tracer AdaptiView™ Control Programming Guide (CTV-SVP02)

Note: For further assistance, contact your local Trane sales office.

Glossary

A

ASHRAE

See American Society of Heating, Refrigeration, and Air-conditioning Engineers

American Society of Heating, Refrigeration, and Air-conditioning Engineers

An international organization of 50,000 persons with chapters throughout the world. The Society is organized for the sole purpose of advancing the arts and sciences of heating, ventilation, air conditioning and refrigeration. It benefits the public with its research, standards writing, continuing education, and publications.

B

BACnet™

See Building Automation Control network

BACnet interoperability building blocks

A block of BACnet application services that tells vendors what BACnet services must be implemented to provide specific device functionality. The BIBBs are grouped together into BACnet device profiles.

BACnet object

An abstract representation of the physical point or points where data is input from or output to an I/O device. Each object may have several BACnet properties that describe the status of that object.

baud rate

The number of signaling elements that occur each second during electronic data transmission. At slow speeds, baud indicates the number of bits per second that are transmitted. For example, 500 baud means that 500 bits are transmitted each second (abbreviated 500 bps). At higher speeds, multiple bits may be encoded with each electrical change. For example, 4,800 baud may allow 9,600 bits to be sent each second. Data transmission rates at high speeds are generally expressed in bits per second (bps) rather than baud. For example, a 9,600 bps modem may operate at only 2,400 baud.

BIBB

See BACnet interoperability building blocks

Building Automation Control network (BACnet and ANSI/ASHRAE Standard 135-2004)

An interoperable protocol developed specifically for the building controls industry. The American National Standards Institute named it as a standard and Trane advocates BACnet protocol for use in system-level control devices.

device

A device is a standard BACnet object as defined by ASHRAE Standard 135-2004. The Tracer UC800 contains the BACnet object.

Device ID

The Device ID is used to uniquely identify each BACnet Device and it can be in the range of 0 to 4194302. There cannot be more than one device using the same Device ID. Each of the sample applications operate as a device and requires its own device id which defaults to zero.

interoperability

The ability to integrate equipment from different vendors into a comprehensive automation and control system. In addition, digital communications between products designed independently, but designed to the same communication standard.

P

protocol

A set of rules (language) that governs the exchange of data over a digital communications system.

PDF preview unavailable. Download the PDF instead.

BAS-SVP-05D, BCI Integration Guide for RTWD, RTUD, RTHD, RTAC, CGAM, (04-10) Acrobat Distiller 8.2.0 (Windows)

Related Documents

Preview Trane BCI2-C Installation Instructions for BACnet Communication Interface for Chillers
Comprehensive installation guide for the Trane BACnet Communication Interface for Chillers (BCI2-C), detailing setup, configuration, and integration with HVAC systems for models RTWD, RTAC, and CGAM.
Preview Trane BACnet Communication Interface for Chillers (BCI2-C) Installation Instructions
Installation instructions for the Trane BACnet Communication Interface for Chillers (BCI2-C). This guide covers overview, specifications, installation, configuration, and troubleshooting.
Preview Trane Optimus RTHD Water-Cooled Chillers: Installation, Operation, and Maintenance Manual
Comprehensive guide for the Trane Optimus RTHD Water-Cooled Chillers (Model RTHD, Doc ID RTHD-SVX01G-EN), covering installation, operation, maintenance, safety warnings, and technical specifications for qualified personnel.
Preview Trane Symbio 700 BACnet Integration Guide for Odyssey Units
This integration guide from Trane provides detailed instructions for connecting Trane Symbio 700 controllers to Odyssey units using BACnet protocols. It covers setup, configuration, and BACnet points for building automation systems.
Preview Trane RTAC Rotary Chiller Tracer AdaptiView Display Upgrade Kit Installation Instructions
This document provides detailed installation instructions for the Trane Tracer AdaptiView Display Upgrade Kit for RTAC Rotary Chillers, replacing older DynaView systems. It covers safety, required tools, step-by-step procedures, and integration options.
Preview Trane Serie R RTAC: Enfriadora de Líquido de Alto Rendimiento
Descubra la enfriadora de líquido Trane RTAC Serie R, diseñada para alta fiabilidad, eficiencia energética y rendimiento superior en aplicaciones industriales y comerciales. Conozca sus características y especificaciones.
Preview Trane Symbio 800 Integration Guide: BACnet and Modbus
This guide provides detailed instructions for integrating Trane Symbio 800 controllers with BACnet and Modbus protocols. It covers communication setup, configuration parameters for both protocols, points lists, arbitration logic, and controller layout, aimed at system integrators and controls contractors.
Preview Trane Symbio 700 Controller Application Guide for Precedent Rooftop Air-Conditioners
This application guide provides detailed information on the Trane Symbio 700 controller for Precedent packaged rooftop air-conditioners, covering configuration, control capabilities, and troubleshooting.