Trane Installation Instructions

Condenser Fan Control Retrofit

RTAA Air-Cooled Chillers and RTAC Air-Condensers Kits CNT07652 and CNT07653

Model Numbers: RTAA, RTCA

This document applies to service offering application only.

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING

Proper Field Wiring and Grounding Required!

Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

WARNING

Personal Protective Equipment (PPE) Required!

Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

  • Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
  • When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
  • If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

WARNING

Follow EHS Policies!

Failure to follow instructions below could result in death or serious injury.

  • All Trane personnel must follow the company's Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
  • Non-Trane personnel should always follow local regulations.

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

Document updated to reflect Service Offering number.

General Information

Read this manual thoroughly before operating or servicing this unit.

The purpose of this bulletin is to advise customers of the parts and procedures required to replace the variable speed drive originally used to control condenser fans in RTAA and RTCA units. These parts were present on 70 to 125 ton, RTAA chillers and RTCA condensers when ordered with the low ambient operation option. The original drive will be phased out, and the parts mentioned below will be the most up-to-date and cost effective substitutes.

Notes:

Kit Selection and Contents

Obtain the required parts from the local Trane Parts Center. If the specific part number cannot be determined, contact the local Trane Parts Center with the unit model number or serial number. Two kits are available. Select the correct drive replacement kit based on the existing unit voltage per Table 1 below. In addition to the correct drive replacement kit, some additional field-provided material will be required. See "Field-Provided Material," p. 6 for a suggested list of materials.

Table 1. Kit selection

Unit Voltage Kit Part Number Kit Description
200/60/3 CNT07653 RTAA Fan Drive Retrofit 230V
380/60/3
400/50/3
460/60/3
575/60/3
CNT07652 RTAA Fan Drive Retrofit 460V

Each kit consists of an assembly and several loose parts. The assembly includes a variable speed drive and associated components mounted to a back plate. See Figure 1, p. 5 for physical dimensions and configuration. See Table 2, p. 6 for a list of service parts. See Table 3, p. 6 for a list of parts shipped loose.

Figure 1. Drive assembly

[Image of drive assembly with dimensions]

Table 2. Service parts

Device Designator Part Description CNT07653 Service Part Number CNT07652 Service Part Number
1U28 Variable Speed Drive DRV03113 DRV03114
1F1 Drive Fusing FUS01010 (30-A Fuse) FUS01010 (30-A Fuse)
1F2
1F3

Table 3. Loose shipped parts

Reference Part Number Description Qty UOM
1 570922770100 (PNL20506) Plate; Inverter Cover, (16 ga) 1 EA
2 X13500224070 Rail; DIN Terminal Block, 35 mm, 4.00 lg 1 EA
3 X13490948010 Terminal Block; 2P 20A 600V 4 EA
4 X13490948140 Pole Marking 1-10 Vert 1 EA
5 X13490948070 End Stop 2 EA
6 X13490948040 2P End Plate 1 EA
7 X45091639010 Cap; DIN Rail End 2 EA
8 SO-SVN049*-EN Installation Instructions (16 pages, 8.5 x 11-in.) 1 EA
9 507118990001 (CNT07684) AVNET Integrated Circuit 6400039050 - EPROM, UV 32KX8, CMOS 250 NS Vpp =12.5V -40 to 85C 28 DIP 27C256 Software - 6200005021 1 EA
10 X22010076080 Lock - 1/4, External Toothed 4 EA
11 X25020623250 Screw; M6x01 x 16, PH Thd Roll 4 EA
12 X22050228060 Washer; 0.265-in. ID x 0.500-in. OD, PL 4 EA
13 507119000001 Schematics; RTAA Fan Control Retrofit 1 EA

Tools Required

Common hand tools and hand-held power tools are required to perform the retrofit. A trained service technician with a well-stocked tool chest should have all of the necessary tools to perform the job. The following list is a sampling of the tools that one could expect to find inside the technician's tool chest:

The following special tools are also required to perform the retrofit:

Field-Provided Material

Some field provided material will be required to perform the RTAA/RTCA fan controls retrofit. A partial list of material is provided here to help the technician plan ahead and to avoid material shortages at the job site.

Trane has determined that inverter duty motors provide a much more robust system when combined with variable speed drives. As with the previous drive, the fan motor should also be replaced with an inverter duty rated motor if it is not already an inverter duty rated motor. The service part numbers for RTAA/RTCA inverter duty motors are found in the table below. For additional help, contact the local Trane Parts Center with the unit model number or serial number.

The fan drive retrofit kits have been sized to fit in the main RTAA control enclosure. Some existing components may need to be relocated. The standard RTCA control enclosure is not large enough for the drive retrofit kits. A separate enclosure is required for RTCA. PNL34974 is recommended. PNL34974 may optionally be used with RTAA if additional cabinet space is desired.

When using a separate enclosure, such as PNL34974, additional mounting hardware may be required depending on the selected mounting location. Additional conduit, fittings, and wire will also be required.

Previous applications of TR170 drives, including earlier versions of this kit, included a blanket heater and temperature control to protect the drives from low temperatures. This heater and control is no longer required and has been removed from this kit. These service parts, HTR16716 and CNT06627, may be purchased separately if desired.

Table 4. RTAA/RTCA fan motor part numbers

RTAA Design Sequence RTCA Design Sequence Motor Voltage Motor Frequency Standard Duty Motor Inverter Duty Motor
AO - LO A0-E0 200-460/400 60/50 MOT06367 MOT14610
M0 - RO F0-G0 200-230 60 MOT09903 MOT14016
460/380-415 60/50 MOT09903 MOT14017
TO and Later H0 and Later 200-230 60 MOT12634 MOT14014
460/380-415 60/50 MOT12636 MOT14015

Pre-Installation

WARNING

PPE for Arc/Flash Required!

Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.

This retrofit consists of replacing and installing components and wiring in the control panel and in an electrical enclosure under the condenser coil. See Figure 2 and Figure 3, p. 8 for examples of original drive mounting.

Figure 2. Original drive enclosure

[Image of original drive enclosure]

Figure 3. Original drive installation

[Image of original drive installation]

Figure 4. Typical RTAA control panel

[Image of typical RTAA control panel with labels for modules]

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer's literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

  1. Turn off power to the machine, water pumps, and any field provided control power. For RTCA units, also remove the power from the associate chiller (RTUA).
  2. Secure all disconnect switches following lockout/tagout safety procedures.
  3. Open the control panel doors and verify all power has been removed.
  4. Remove any louvers or wire panels that may prevent access to the existing variable speed drives.
  5. Verify the condenser fan motor is inverter duty rated. If it is not, replace the motor. See "Field-Provided Material," p. 6 for motor identification.
  6. Record the following information from the condenser fan motor nameplate. This information will be needed during drive configuration.
    • Motor Power
    • Motor Voltage
    • Motor Frequency
    • Motor Current
    • Motor Nominal Speed
  7. If using a new additional enclosure, such as PNL34974, for drive mounting, select a convenient location and mount. Avoid mounting the enclosure under the condenser coil or in any location that would prevent access to other serviceable components.

Control Panel Modifications

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer's literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

Removal of Existing Controls

  1. Locate original drive enclosure underneath the condenser coil. See Figure 2, p. 8.
  2. Remove the drive enclosure cover.
  3. Remove the variable speed drive being replaced.
  4. Speed and fault signal wiring may be pulled back into the control panel.
  5. Locate the cover plate (PNL20506) in the loose parts of the kit.
  6. Install the cover plate over the opening left by the drive.
  7. Locate the DIN rail, DIN rail caps, terminal blocks, end plate, terminal labels, and end stops in the loose parts of the kit.
  8. Mount the DIN rail and caps in a convenient location in the existing drive enclosure.
  9. Mount the terminal blocks, end plate, terminal labels, and end stops onto the DIN rail. This terminal block may be labelled 2TB1.
  10. The new drive in the control panel will require a direct ground connection from the motor to the drive. Run a new ground wire from the drive enclosure back to the control panel.
  11. Connect the motor wires to the wires running back to the control panel. These wire are color coded. See Table 5 for connections.

Table 5. Drive enclosure connections

Connection Color Description
2TB1-1 Red L1
2TB1-2 Blue L2
2TB1-3 Black L3
2TB1-4 Green GND

See Figure 5 for an example of the drive enclosure with one drive removed.

Figure 5. Enclosure with original drive removed

[Image of enclosure with original drive removed]

New Drive Installation

  1. Locate a convenient location in the control panel for installation. This may be a new enclosure such as PNL34974. The front of the drive will need to be accessible for entering drive parameters. The top and bottom of the drive require 4 inches of clear space for ventilation. The drive assembly must be mounted directly to the back of the enclosure to allow the door to close.
    Some existing components may need to be relocated. For example, 575-V units have an autotransformer that may be moved to under the panel mullion.
    This kit is for a single drive replacement, however the other drive may need to be replaced in the future. Leave enough space for another drive to be installed in the future.
  2. Place the drive assembly in the desired location and mark locations for the drive assembly mounting holes on the back of the enclosure. Remove the assembly.
  3. The following hardware is provided for mounting the drive assembly. Drill a 3/16-inch pilot hole at each marked location. Lift the assembly back into place and mount using the included hardware.
Part Number Description Qty UOM
X22010076080 Lock - 1/4, External Toothed 4 EA
X25020623250 Screw; M6x01 x 16, PH Thd Roll 4 EA
X22050228060 Washer; 0.265 ID x 0.500 OD, PL 4 EA

Note: Field-provided hardware can be substituted, however, thread-rolling fasteners or sealing washers are required to prevent moisture from entering the control panel.

See Figure 6 for an example of a mounted drive assembly inside an RTAA control panel.

Figure 6. Mounted drive assembly

[Image of mounted drive assembly]

  1. Place the module on a conductive bench, i.e. metal surface. While working, you and the module must be in contact with the bench to avoid you or the module from developing a damaging static discharge.
  2. Remove the fish paper insulator.
  3. Remove the screws securing the PCB assembly to the sheet metal cover. The screws are located under the fish paper. Touch the screw driver to the metal bench before use to avoid a damaging static discharge to the module.
  4. There are eight #6-32 screws located under the compressor module. Remove all eight.
  5. The EPROM is the chip that is installed in the socket. It is designated as U2 on the compressor module. This is shown below in Figure 7.
  6. Note the orientation of EPROM before removing. The notch in the EPROM should line up with the notch in the socket and the notch drawn in the outline on the PCB.

Figure 7. EPROM location

[Image showing EPROM location on PCB]

EPROM Installation

NOTICE

Static Sensitive Components!

Static charge on the human body can regularly reach voltages of more than 12,000 volts. You MUST follow instructions below to reduce the risk of damage to the electronics. Before handling the module, discharge yourself by touching the panel sheet metal or use an anti-static wrist strap.

For RTAA units, the following controls work should be completed in the unit control panel. For RTCA units, the EPROM work needs to be completed in the RTUA control panel.

  1. Record the software part number and extension found on the EPROM provided in the upgrade kit, before installing into the module. These numbers will be used later to verify the correct EPROM was installed.
  2. Disconnect power from the compressor module.
  3. Before handling the compressor module, discharge yourself by touching the panel sheet metal or use an anti-static wrist strap.

Important: See Figure 4, p. 9 for module locations. Compressor modules 1U4 and 1U5 are located BEHIND other modules.

  1. Remove 1U4 (compressor A) and 1U5 (compressor B) modules from the panel. The modules have key holes so the mounting screws need only be loosened but not removed. Note where the various wires are plugged into the module connectors. The plugs may be labeled to avoid confusion when reconnecting. If the module is beneath another, the connectors on just one side of the upper module may be removed and the module hinged out to access the lower module.
  2. Install the new EPROM. Align the notch in the EPROM to the notch in the socket and on the PCB as the original EPROM was. Make sure that the PCB assembly is lying flat on the bench surface when pressing down on the EPROM. Press the EPROM firmly into place.
  3. Inspect the EPROM and the socket to make sure that all pins are lined up and inserted correctly. Verify that there are no bent pins.
  4. Install the sheet metal cover and fish paper. Torque screws 8 in-lbs minimum and 11 in-lbs maximum.
  5. Install the module.
  6. Verify that all of the connections are correct and that the mounting screws are tight.
  7. The EPROM includes a sticky label that indicates the replacement of the EPROM. Apply the label to the outside of the compressor module. This will alert a technician that a replacement EPROM will need to be ordered in the event of module replacement.

Wiring

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer's literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

Power wiring, motor wiring, and drive signal wiring all must be relocated from the fan contactor and drive fuses to the new drive assembly. Table 6 indicates the wiring connections that must be made. Remove any existing wiring from terminals being reused.

Note:

Table 6. Wiring connections

Wire Identification Replacing Circuit 1 Drive From Existing Unit Connection Wire Identification Replacing Circuit 2 Drive From Existing Unit Connection To Drive Assembly Connection
20A, 44B, or 47A(a) 1F1 or 1T10-X1(a) 23A, 50B, or 53A(a) 1F4 or 1T11-X1(a) 1F1
21A, 45B, or 48A(a) 1F2 or 1T10-X2(a) 24A, 51B, or 54A(a) 1F5 or 1T11-X2(a) 1F2
22A, 46B, or 49A(a) 1F3 or 1T10-X3(a) 25A, 52B, or 55A(a) 1F6 or 1T11-X3(a) 1F3
Red 2TB1-1 (3B2[RED]) Red 2TB1-1 (4B2[RED]) 1U28-96 (U)
Blue 2TB1-2 (3B2[BLU]) Blue 2TB1-2 (4B2[BLU]) 1U28-97 (V)
Black 2TB1-3 (3B2[BLK]) Black 2TB1-3 (4B2[BLK]) 1U28-98 (W)
Field Provided (Motor Ground) 2TB1-4 (Motor Ground) Field Provided (Motor Ground) 2TB1-4 (Motor Ground) 1U28-99 (PE)
29A or 29C 1U4-J9-6 or 1TB9-1 36A or 36C 1U5-J9-6 or 1TB9-5 1U28-53 (Speed)
56A or 59C 1U4-J9-5 or 1TB9-2 57A or 57C 1U5-J9-5 or 1TB9-6 1U28-55 (Common)
30A or 30C 1U4-J9-4 or 1TB9-3 37A or 37C 1U5-J9-4 or 1TB9-7 1U28-03 (Alarm)
31A or 31C 1U4-J9-3 or 1TB9-4 38A or 38C 1U5-J9-3 or 1TB9-8 1U28-01 (Alarm)
Field Provided 1K9-L1 Field Provided 1K13-L1 1U28-12 (+24VDC)
Field Provided 1K9-T1 Field Provided 1K13-T1 1U28-18 (Enable)

(a) 575V units only.

General Start-Up Review

  1. When all components have been mounted and wired, close all electrical enclosures.
  2. Restore machine power.
  3. Place the unit in STOP to prevent unintended operation.

WARNING

PPE for Arc/Flash Required!

Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.

  1. Open the cover or door over the drive and verify the drive has powered up.

Note: The drive cooling fan may be operating, even if the unit is in standby mode.

  1. Proceed to entering drive parameters.

Entering Drive Parameters

Drives are shipped with generic settings. These setting must be updated to reflect the drive application. Table 7 lists the drive parameters that must be changed for correct operation.

Notes:

Table 7. Drive parameters

Level 1 Level 2 Level 3 Description Settings
0-03 0-0 0 - ** Regional settings North America
0-06 0-4 0-40(a) Grid Type Unit Voltage
1-20 1-22 [Hand on] Key on LCP (0) Disable
1-23 1-24 Motor Power ---HP(b)
1-25 1-** Motor Voltage ---V(b)
1-71 1-72 Motor Frequency --Hz(b)
1-73 1-8 Motor Current --A(b)
1-82 1-9 Motor Nominal speed --rpm(b)
1-90 2-** Start Delay 3 s(b)
2-1 2-10 Start function (0) DC Hold
3-02 3-0 Flying start (1) Enable
3-03 3-** Min speed 0.1 Hz
3-41 3-4 Motor Thermal Protection (4) ETR Trip 1
3-42 4-10 Brake Function (0) Brake Function Off
4-12 4-** Minimum Reference 0
4-1 4-14 Maximum Reference 50/60(c)
4-18 5-1 5-12(d) Ramp 1 Ramp Up time 5 s
5-** 5-4 5-40 Ramp 1 ramp Down Time 20 s
6-10 6-** Motor Speed Direction (0) Clockwise
6-1 6-14 6-15 Motor Speed Low Limit 3 Hz
14-0 14-01 14-1 Current Limit 50/60 Hz(c)
14-12 14-** 14-20 Terminal 27 Digital Input 140%
14-2 14-21 14-5 Function Relay (0) No Operation
14-50 Terminal 53 Low Voltage (0) Alarm (9)
Terminal 53 Low Ref/Feeb Value 0 V
Terminal 53 High Ref/Feeb. Value 0
Switching Frequency 5 KHz
Function at mains Imbalance (3) De-Rate
Reset Mode (10) Auto Reset x 10
Automatic Restart Time 30 s
RFI Filter (0)

(a) Parameter 0-40 may be enabled for drive/rotation troubleshooting.
(b) Parameters are from motor nameplate.
(c) Use when the frequency is either 50 or 60 Hz.
(d) The default setting for parameter 5-12 will cause a drive error. Parameter 5-12 must be set to (0) No Operation.

General Start-Up Review

Optional Drive Parameter Copy Procedure

If chiller has multiple drives, the following procedure can be used to copy parameter settings from one drive to another.

Note: Step 2 can also be used to backup drive parameter settings.

  1. Program first drive (#1) per Table 7, p. 13.
  2. On the programmed drive, upload data to the local control panel (LCP #1) as follows:
    1. Go to 0-50 LCP copy.
    2. Press [OK].
    3. Select All to LCP.
    4. Press [OK]. A progress bar shows the uploading process.
    5. Press [Hand on] to return to normal operation.
  3. Remove LCP #1 from programmed drive (#1).
  4. Replace LCP on drive to be programmed (#2), with LCP #1, removed from drive #1.
  5. Download data onto drive #2 as follows:
    1. Go to 0-50 LCP copy.
    2. Press [OK].
    3. Select All from LCP.
    4. Press [OK]. A progress bar shows the downloading process.
    5. Press [Hand on] to return to normal operation.
  6. Remove LCP #1 and reinstall LCP #2 on drive #2.
  7. Repeat Step 4 through Step 6 for any additional drives to be programmed.
  8. Reinstall LCP #1 on drive #1.

Verify Fan Function

WARNING

Rotating Components!

Failure to disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious injury. During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks.

  1. Place the drive in HAND mode.
    Note: Parameter 40 will need to be enabled.
  2. Turn the fan to low speed.
  3. Observe the fan rotational direction.

a. If the fan rotates in the wrong direction, turn off power to the machine, water pumps, and any field provided control power.

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer's literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

  1. b. Secure all disconnect switches following lockout/tagout safety procedures.
  2. c. Open the control panel doors and verify all power has been removed.
  3. d. Switch the blue and black wire at the drive terminals.
  4. e. Restore unit power.
  5. f. Return to Step 1.
  1. Increase speed and verify the fan operates over the full speed range.
  2. Return drive to AUTO mode.
    Note: Change parameter 40 to Disable.
  3. Close the control panel.
  4. Return the machine to standard operating condition.
Models: RTAA, RTCA, RTAA Condenser Fan Control Retrofit, Condenser Fan Control Retrofit, Fan Control Retrofit, Control Retrofit, Retrofit

File Info : application/pdf, 16 Pages, 2.18MB

PDF preview unavailable. Download the PDF instead.

SO-SVN049A-EN 10132023

References

Acrobat Distiller 23.0 (Windows)

Related Documents

Preview Trane Condenser Fan Control Retrofit Installation Instructions for RTAC Chillers
Detailed installation instructions for retrofitting condenser fan controls on Trane RTAC Air-Cooled Chillers using kits CNT07650 and CNT07651. Covers general information, pre-installation steps, control panel modifications, wiring, and start-up procedures.
Preview Trane TR170 VFD Installation Guide for RTAC Condenser Fans
Comprehensive installation guide for replacing Trane TR1 Variable Frequency Drives (VFDs) with TR170 VFDs on RTAC™ air-cooled chillers. Covers removal, installation, wiring, and parameter programming.
Preview Manual de Instalação, Operação e Manutenção de Resfriadores de Líquido Rotativo TRANE RTAA Série R® com Condensação a Ar
Guia completo para a instalação, operação e manutenção dos resfriadores de líquido rotativo com condensação a ar TRANE Série RTAA, modelos RTAA-70 a RTAA-125. Inclui procedimentos detalhados, informações técnicas e diretrizes de segurança.
Preview Trane RTAC Rotary Chiller Tracer AdaptiView Display Upgrade Kit Installation Instructions
This document provides detailed installation instructions for the Trane Tracer AdaptiView Display Upgrade Kit for RTAC Rotary Chillers, replacing older DynaView systems. It covers safety, required tools, step-by-step procedures, and integration options.
Preview Trane Serie R RTAC: Enfriadora de Líquido de Alto Rendimiento
Descubra la enfriadora de líquido Trane RTAC Serie R, diseñada para alta fiabilidad, eficiencia energética y rendimiento superior en aplicaciones industriales y comerciales. Conozca sus características y especificaciones.
Preview Trane Integrated Variable or Multi Speed Control Drive Replacement Installer's Guide
Comprehensive installer's guide for replacing Trane Integrated Variable or Multi Speed Control Drives. Covers safety warnings, required tools and parts, terminology, step-by-step removal and installation procedures, thermal grease application, final inspection, and drive board return instructions.
Preview Trane BACnet Communication Interface (BCI2-C) Installation Instructions
Installation guide for the Trane BACnet Communication Interface (BCI2-C) for chillers, covering specifications, installation procedures, configuration with Tracer TU and BCI2 Service Tool, and integration with CH530.
Preview Trane BCI2-C Installation Instructions for BACnet Communication Interface for Chillers
Comprehensive installation guide for the Trane BACnet Communication Interface for Chillers (BCI2-C), detailing setup, configuration, and integration with HVAC systems for models RTWD, RTAC, and CGAM.