Overview
The MPS3100/05 is a mains-powered, standalone occupancy and daylight sensor. It is an Interact Ready sensor, enabling easy upgrade to a smart lighting system. It integrates with Interact Ready luminaires featuring wireless drivers. The sensor's mounting height can range from 2.1 to 8 meters. Utilizing 2.4 GHz Zigbee technology, it provides reliable and secure communication with lights, triggering automatic responses to turn lights on or dim them based on occupancy detection and daylight variations. The sensor is designed for waterproof applications and is suitable for low to mid-bay heights.
Features and Benefits
Features
- Motion sensor PIR for occupancy detection
- Adjustable sensitivity
- Minimum false trigger
- Light sensor for daylight dependent regulation (DDR)
- Infrared receiver module for IR remote control
- Zigbee and Bluetooth Low Energy (BLE) transceiver
Benefits
- Automatic light control based on occupancy detection and daylight sensing
- Adjustable sensor parameters for personalized lighting behaviors
- Status indication via three built-in LEDs
Applications
Typical application areas include warehouses, parking garages, factories, locking docks, classrooms, auditoriums, libraries, gymnasiums, hospital corridors, patient rooms, lobbies, office corridors, and conference rooms.
The sensor is designed for surface mounting on ceilings, working with Interact Ready luminaires that have wireless drivers. The mounting height can range from 2.1 to 8 meters.
Dimensional Drawings
The sensor has a main body diameter of approximately 96.2 mm (3.79 in) and a height of 56.3 mm (2.21 in). Key dimensions include a height of 70.0 mm (2.76 in) from the base, with a depth of 37.6 mm (1.48 in) and a diameter of 40.0 mm (1.57 in) for the central dome. Mounting holes are indicated with a diameter of 4.5 mm (0.18 in). A cable exit point is shown with a diameter of 4.0 mm (0.16 in). The optional recessed mounting plate has a cable hole diameter of 6.3 mm (0.25 in) and a length of 300 mm (11.81 in).
Mounting and Cable
Mounting
Surface mounting with an installation height between 2.1 to 8 meters from the floor.
Cable
Type | H05RN-F 60245IEC57(YZW) |
---|---|
Color | Black |
Strip length | 8.5 ±1 mm |
Wire type | Solid 0.75 mm² |
Wire isolation | Insulation: E14(IE4) + (EPR) Jacket: EM2(SE4) + (CPE) |
Length | 0.3 m |
Daylight Sensing
- High accuracy of ambient light measurement from approximately 1 to 1500 lux at sensor level.
- Closed loop daylight regulation.
- Daylight fast report for calibration.
Field of View (Daylight)
The daylight sensing field of view is depicted as a cone. The diagram shows a minimum detection width of 0.75 times the mounting height (h) and a maximum width of h. The angle is indicated as 27 degrees. This coverage is applicable for mounting heights ranging from 2.1 to 8 meters (6.89 to 26.25 ft) at a temperature of 21 +/- 3 °C (70 +/- 5 °F).
PIR Occupancy Sensing
Note: As PIR based sensing works on the difference between subject's temperature and ambient temperature, the occupancy detection could vary due to clothing and size of the subject. The sensor detection area will decrease when the difference in subject's temperature and ambient temperature is approximately 5 °C or less.
Field of View (Motion)
The motion detection field of view with the lens shield is illustrated as a cone. For mounting heights (h) between 2.1 to 8 meters (6.89 to 26.25 ft), the detection ranges are shown as 1xh, 1.5xh, and 2xh. This is specified for ambient temperatures of 21 +/- 3 °C (70 +/- 5 °F).
Removing the lens shield expands the sensor's detection area. The field of view without the shield is also shown as a cone, covering ranges up to 1.5xh and 2xh for mounting heights of 2.1 to 8 meters (6.89 to 26.25 ft) at 21 +/- 3 °C (70 +/- 5 °F).
Lens Shielding Options
Lens shielding options allow for adjustment of the motion detection field of view. The 'Rectangle field of view' option is achieved by removing specific parts of the shield to create a rectangular detection pattern. The 'Hemisphere field of view' option is achieved by removing parts labeled (1) to achieve a hemispherical detection pattern (2).
Movement type | Sensor mounting height | Maximum sensor detection diameter (ratio of mounting height (H) and diameter (D)) H:D |
---|---|---|
Major movement | 2.1 to 8 m | 1:2 |
Minor movement | 2.1 to 5 m | 1:1.5 |
For example, at a 5-meter mounting height, the maximum detection diameter for major motion is 10 meters, and for minor motion is 7.5 meters.
Specifications
Physical Data
Dimensions | Ø 96.2 x 56.3 mm |
---|---|
Installation height | 2.1 to 8 m |
Net weight | 0.19 kg |
Color | White |
Environmental Data
Operating temperature | -40 to +65 °C (-40 to +149 °F) |
---|---|
Storage temperature | -40 to +85 °C (-40 to +185 °F) |
Operating relative humidity | 20 to 85/85%, non-condensing |
Storage relative humidity | 10 to 95%, non-condensing |
Protection rating | IP66, IK08 (without lens) |
Electrical Data
Input voltage | 220 to 240 V (50 to 60 Hz) |
---|---|
Input current | 5 mA |
Input power | < 0.5 W |
Surge protection | 2 kV (line to neutral), 4 kV (line/neutral to earth) |
Communication Range
Maximum distance BLE for commissioning | 15 m line of sight |
---|---|
Maximum distance Zigbee MPS3100 to MPS3100 | 50 m line of sight, package error rate (PER) < 1% |
Compliance
Approbation: CE, CB, UKCA, ENEC, WEEE, RCM
LED Indicator
This device features a built-in RGB LED indicator underneath the PIR lens, providing clear visibility of the sensor's functions.
LED Patterns
LED pattern | Indication |
---|---|
Sensor is powered ON and stabilizing | Yellow LED is ON for 30 seconds. |
Sensor detects occupancy | Red LED is ON |
Sensor detects vacancy | Yellow LED is ON |
If the mobile app or gateway sends BLINK command to sensor for identification | Green LED toggles at a rate of 10Hz frequency for 4 seconds. |
In the mobile app: Click Delete button to remove a sensor | Green LED toggles at a rate of 10Hz frequency for 10 seconds. Then Green LED stops blinking and Yellow LED starts blinking. |
In the mobile app: Click the Reset button to factory reset a sensor | Green LED toggles at a rate of 10Hz frequency for 10 seconds. Then Green LED stops blinking and Yellow LED starts blinking. |
In the remote control: Click Add button to localize a fixture | Green LED toggles at a rate of 10Hz frequency for 10 seconds. Then Green LED stops blinking and Yellow LED starts blinking. |
In the remote control: Click 0 (zero) button to reset a fixture | Green LED toggles at a rate of 10Hz frequency for 10 seconds. Then Green LED stops blinking and Yellow LED starts blinking. |
IR Receiver
The working range of the IR receiver is within a taper area with an angle of 20°. The Philips IRT9015 or IRT9090 IR remote control is used to select luminaires during commissioning.
Connectivity
Zigbee
This device is compatible with the Zigbee standard IEEE 802.15.4. Firmware updates can be sent over the air, providing reliable and secure wireless communication.
Bluetooth
This device is compatible with the Bluetooth Low Energy protocol 4.2 (5.1 compliant) standard.
Accessory and Ordering Information
Accessory
Recessed mounting plate
Order name | Color | MOQ | Order number | Region of sale |
---|---|---|---|---|
SA3000/05 Rec Mnt MPS3xxx | White | 1 | 9137 010 75003 | Global |
Ordering Data
Order name | MOQ | Ordering number | Region of sale |
---|---|---|---|
MPS3100/05 OCC-DL IA WH 8M | 1 | 9137 010 71203 | Global (excluding North America) |
Note: The MPS3100/05 sensor is not suitable for use in North America as it is not compatible with 110 V mains power supply.
Safety Warnings
Warning ⚠️
- Avoid touching live parts!
- Do not use drivers with damaged housing and/or connectors!
- Do not use drivers with damaged wiring!
- Class 1 luminaires must be connected to protective earth!
- Switchable function to make the open load on the driver output abnormal is not an intended application and should not be allowed.
Safety Warnings and Installation Instructions
To be taken into account during design-in and manufacturing:
- Do not use damaged or defective contacts or housings.
- Do not use damaged products.
- Do not service the driver when the mains voltage is connected; this includes connecting or disconnecting the LED load.