Philips Dynalite DUS360CS-D Multifunction Sensor
Installation Instructions
General Installation Requirements
Important Safety Note: Devices must be installed by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.
The following text is provided in multiple languages for installation guidance:
- French: Les appareils doivent être installés par un électricien diplômé conformément à tous les codes et réglementations électriques et de construction nationaux et locaux.
- German: Die Geräte sind von einem qualifizierten Elektriker in Übereinstimmung mit allen geltenden Vorschriften zu installieren.
- Spanish: Los dispositivos deben ser instalados por un electricista calificado y cumpliendo todas las normas y regulaciones, tanto nacionales como locales, sobre instalaciones eléctricas y obras.
- Italian: I dispositivi devono essere installati da un elettricista qualificato in conformità con le norme locali e nazionali vigenti in materia di costruzioni edilizie e installazione di impianti elettrici.
- Dutch: De apparaten moeten worden aangebracht door een gekwalificeerde elektricien en in overeenstemming met alle nationale en plaatselijke elektriciteits- en bouwvoorschriften.
- Japanese: 装置を取り付ける際は、資格のある電気技師に依頼し、国および地域の電気および建設に関するすべての法令に従ってください。
- Chinese: 根据国家/地区及当地的电气与建筑规范和法规,该设备必须由有资质的电工进行安装。
- Arabic: يجب تركيب الأجهزة من قبل فني كهربائي مؤهل وفقًا لكافة قوانين ولوائح التركيب الكهربائي المحلي والوطني.
Installation Steps and Diagrams
Step 1A & 1B: PIR Sensor Coverage
Diagrams illustrate the Passive Infrared (PIR) sensor's detection pattern, showing a wide coverage angle (120°). The device is rated for IEC Pollution Degree II.
Step 2: PIR Detection Range and Height
This diagram shows the PIR sensor's detection range. The maximum range is up to 7.0 meters (23 ft) when mounted at a height between 2.4 meters and 4.0 meters (7.9 ft to 13.1 ft). Optimal performance, including maximum range, is achieved at temperatures at or below 25° C (77° F).
Step 3: Protective Earth (PE) Connection
Illustrates the correct connection for the Protective Earth (PE) terminal. The diagram shows a checkmark [✔️] for proper connection and crosses [❌] for incorrect placement. The PE connection should be made with wire less than 1 mm² (16+ AWG) and tightened to 0.4 Nm (3.5 Lb-in). The device is rated for IEC Overvoltage Category III.
Step 4: IR Sensor Coverage
Depicts the Infrared (IR) sensor's detection pattern, typically a more directional beam with a 120° angle. The diagram indicates correct placement with a checkmark [✔️] and incorrect placement with crosses [❌].
Step 5: Wiring Details
This diagram details the wiring connections. It specifies wire gauge requirements of less than 1 mm² (16+ AWG) and a torque setting of 0.4 Nm (3.5 Lb-in) for connections. The DALI/ELV interface operates at 9.5-22.5 V and 9 mA, with DALI insulation classified as Basic.
Step 6: Mounting and Cable Entry
Shows the sensor's mounting dimensions and the required hole size for cable entry, which is Ø6.5 mm (0.26 in). The mounting torque specification is 0.5 Nm (4.4 Lb-in). The diagram also indicates cable entry size compatibility for cables ranging from 3 mm to 25 mm (0.12 in to 0.98 in).
Step 7A: Cable Entry Dimensions
Provides specific dimensions for cable entry, showing a main entry size of 64 mm (2.51 in) and a clamp size of 25 mm (0.98 in).
Step 7B: Mounting Bracket and Cable Routing
Illustrates the mounting bracket and the method for routing cables through it. Dimensions for the bracket components are shown as 70 mm (2.75 in), 60 mm (2.36 in), and 50 mm (1.96 in).
Step 7C: Wiring Terminals and Connections
Details the wiring terminals, including connections for SELV/Class 2 power, DyNet RS-485, and other potential interfaces. It specifies wire gauge requirements of 2.5 mm² (12+ AWG) and a torque setting of 0.4 Nm (3.5 Lb-in) for these terminals.
Step 8: DALI System Example
This diagram shows a typical DALI lighting control system setup. It illustrates connections between DALI controllers, such as the DDBC120-DALI and DDBC320-DALI, and DALI-compatible devices like LED drivers or lamps.
Step 9: Labeling and Barcode Application
Depicts the process of applying identification labels or barcodes to the product or its packaging for tracking and management.
Technical Specifications
- Operating Voltage (DALI/ELV): 9.5 - 22.5 V
- Operating Current (DALI): 9 mA
- DALI Insulation: Basic
- PIR Detection Angle: 120°
- PIR Detection Range: Up to 7.0 m (23 ft) at 2.4 m - 4.0 m (7.9 ft - 13.1 ft) mounting height (optimal at ≤ 25° C / 77° F)
- Operating Temperature: 0° C to 45° C (32° F to 113° F)
- Operating Humidity: < 90% (non-condensing)
- Wire Gauge (PE): < 1 mm² / 16+ AWG
- Wire Gauge (Terminals): 2.5 mm² / 12+ AWG
- Torque (PE): 0.4 Nm (3.5 Lb-in)
- Torque (Terminals): 0.4 Nm (3.5 Lb-in)
- Torque (Mounting): 0.5 Nm (4.4 Lb-in)
- Cable Entry Diameter: 3 mm - 25 mm (0.12 in - 0.98 in)
- IEC Overvoltage Categories: II (Pollution Degree II), III (Overvoltage Category III)
Compliance and Regulatory Information
Safety Warnings:
- Do not connect DALI inputs to mains power. DALI wires are NOT SELV and should never be considered touch safe. ⚠️
- Refer to the Service Guide for full cleaning recommendations.
Federal Communications Commission (FCC) Compliance: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. If interference occurs, users are encouraged to correct it by reorienting the antenna, increasing separation, or connecting to a different circuit. Modifications not approved by the manufacturer may void the user's authority to operate the device.
Canadian Compliance: This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B).
Building Automation Systems: Installation of a home and building automation and control system shall comply with IEC 60364 (all parts). Temperature limits and current-carrying capacities for communication wires specified in IEC 60364-5-52 must not be exceeded.