Installation Instructions
Philips OCC0100A/02 BP Sensor WH
Philips OCC0101A/02 DL BP Sensor WH
Product Overview
This document provides installation instructions for the Philips BP Sensor WH (model OCC0100A/02) and the Philips DL BP Sensor WH (model OCC0101A/02). These are motion and occupancy sensors designed for lighting control applications.
The sensors are white, cylindrical devices.
Important Safety Information
Note: Battery replacement must be performed by a skilled or instructed person.
Caution: Risk of explosion if the battery is replaced by an incorrect type. Dispose of used batteries according to the instructions.
Battery: Requires 1x R6 Li-Ion 3.6V battery with a lifetime exceeding 8 years.
Operating Temperature: Minimum -5°C, Maximum +45°C.
Weight: 0.090 kg.
Installation Steps
Step 1: Mounting Plate Installation
Begin by installing the circular mounting plate. This plate features screw holes for secure attachment and a central opening for wiring. The diameter of the mounting plate is 86.5 mm (3.41 in).
Step 2: Sensor Mounting
Mount the sensor onto the ceiling. The recommended mounting height is between 2.5 meters and 4 meters (8.2 to 13.1 ft). The detection range is specified as greater than 3 meters (9.8 ft).
Step 3: Coverage Area
The detection coverage area varies depending on the mounting height:
- At a 2.5m (8.2 ft) mounting height, the coverage area is approximately 5.4m x 7.2m (17.7 ft x 23.6 ft).
- At a 3.6m (11.8 ft) mounting height, the coverage area is approximately 5.4m x 5.4m (17.7 ft x 17.7 ft).
Step 4: Detection Parameters
The detection diameter is calculated based on the mounting height (h) using the formula Ø 1.4 x h. A minimum mounting height of 0.7 x h is advised. The sensor is equipped with a lux sensor to measure ambient light levels.
Step 5: Wiring and Battery Installation
Connect the necessary electrical wires to the sensor's terminals. Subsequently, insert the R6 Li-Ion 3.6V battery into its designated compartment. The sensor includes a FOV (Field of View) indicator.
Step 6: OCC0101A/02 DL Model Specifics
This step is exclusive to the OCC0101A/02 DL BP Sensor WH model. It may involve a "Green 10 s" indicator, which likely signifies its daylight sensing function or operational status.
Technical Specifications
Battery: 1x R6 Li-Ion 3.6V, lifetime >8 years
Operating Temperature: -5°C to +45°C
Weight: 0.090 kg
Recommended Mounting Height: 2.5 m to 4 m (8.2 to 13.1 ft)
Detection Range: > 3 m (9.8 ft)
Detection Diameter: Ø 1.4 x h (where h is mounting height)
Radio Frequency: 2.4 GHz (for wireless communication)
Regulatory Compliance
FCC Statement: This device complies with Part 15 of the FCC Rules. Operation is subject to two conditions: (1) it must not cause harmful interference, and (2) it must accept any interference received, including interference that may cause undesired operation. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. If this equipment causes harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: reorient or relocate the receiving antenna; increase the separation between the equipment and receiver; connect the equipment into an outlet on a circuit different from that to which the receiver is connected; or consult the dealer or an experienced radio/TV technician for help. Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with a minimum distance of 200 mm between the radiator and a human body.
RF Exposure Information (EU): This device meets the EU requirements (2014/53/EU) on the limitation of exposure of the general public to electromagnetic fields by way of health protection. The device complies with RF specifications when the device is used at 200 mm from the body.
ISED Statement (Canada): This device contains licence-exempt transmitter(s) that comply with Innovation, Science and Economic Development Canada's licence-exempt RSS(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. This equipment complies with ISED radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with a minimum distance of 200 mm between the radiator and a human body.
EU Declaration of Conformity: Signify declares that the radio equipment type OCC0100A-02 and OCC0101A/02 are in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following Internet address: http://www.philips.com/red
Chinese Regulatory Notes: This product is classified as a Class F device under Chinese regulations for low-power short-range radio transmitting equipment. It uses an omnidirectional antenna, transmits at less than 10 milliwatts, and operates at 2.4 GHz. Users must comply with national radio management regulations. Unauthorized modifications, increased power, or antenna changes are prohibited. The device must not cause harmful interference to other legal radio stations and must not claim protection from such interference. If interference occurs, cease use and take corrective measures. Consult the manufacturer if interference from ISM equipment or other legal radio stations occurs. Use in specific electromagnetic protection areas (e.g., airports, radio astronomy observatories) must comply with relevant regulations.
General Information:
- Copyright © 2023-2024 Signify Holding. All rights reserved.
- Specifications are subject to change without notice.
- No representation or warranty as to the accuracy or completeness of the information included herein is given, and any liability for any action in reliance thereon is disclaimed.
- Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V.
- All other trademarks are owned by Signify Holding or their respective owners.
Document Number: 4422 963 41133
Date: 11 January 2024
UK Importer: Signify Commercial UK Limited, 3, Guildford Business Park, GU2 8XG
Website: www.philips.com/lighting