Philips Dynalite DDRC1220FR-GL Relay Controller

Installation Instructions

General Safety Information

Devices must be installed in an approved enclosure by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.

French: Les appareils doivent être installés dans un lieu jugé apte, par un électricien qualifié et conformément aux règles et normes locales et nationales en matière d'électricité et de construction.

German: Die Geräte müssen von einem geprüften Elektriker entsprechend allen nationalen und lokalen Elektro und Bauvorschriften in einem zugelassenen Gehäuse installiert werden.

Spanish: Los dispositivos se deben instalar en un recinto aprobado por un electricista cualificado de acuerdo a todos los reglamentos eléctricos y de construcción locales y nacionales pertinentes.

Italian: I dispositivi devono essere installati da un elettricista qualificato in un luogo approvato, in conformità a tutti gli standard e le norme nazionali e locali vigenti in materia di impianti elettrici e costruzioni edilizie.

Dutch: Apparaten moeten door een erkende elektricien worden geïnstalleerd in een goedgekeurde behuizing in overeenstemming met alle nationale en lokale elektriciteits - en bouwvoorschriften en wetgeving.

Japanese: デバイスを取り付ける際は、資格のある電気技師に依頼し、電気と建設に関する国および地域のすべての法令に 従って、認可されている筐体内に取り付けてください。

Chinese: 根据国家/地区及当地的电气与建筑规范和法规,该设备必须由有资质的电工安装在经批准的外罩内。

Arabic: يلزم تركيب الأجهزة داخل حاوية معتمدة، من قبل كهربائي مؤهل وفقًا لجميع قوانين ولوائح الكهرباء والإنشاءات الوطنية والمحلية.

Product Overview and Dimensions

The Philips Dynalite DDRC1220FR-GL is a Relay Controller.

Dimensions:

Operating Conditions:

Certifications: CE, UKCA, C-Tick, RCM, FCC, UL Listed

Pollution Degree: IEC Pollution Degree II

Wiring and Installation Examples

The document provides several wiring examples for different voltage configurations:

Example 2 A: 100-240 V~

This section shows the connection for a 100-240V~ supply, with terminals for 12 channels (CH1-CH12), each with IN and OUT connections. It specifies wire gauge (≤ 5 mm² / 10+ AWG), torque (0.62 Nm / 5.5 Lb-in), and maximum current per channel (20A).

Diagram Description: A terminal block with 12 channels, each having an input and output. The supply is connected to 'NL' and 'L1, L2, L3' (for 3-phase) or 'N L' (for single phase). The diagram illustrates connections for each channel, indicating 'IN' and 'OUT' terminals. It also shows the 'SUPPLY' connection.

Example 2 B: 277/480 V~

This section details the installation for a 277/480V~ supply, also featuring 12 channels with IN/OUT terminals. It highlights the use of 'N L1 L2 L3' for the supply and shows specific wiring configurations with 'xx' indicating connections to be made.

Diagram Description: Similar to 2A, but specifically for 277/480V~ supply, showing connections to L1, L2, L3 and Neutral. The 'xx' marks indicate specific wiring points.

Example 2 C: 277/480 V~ (3-Phase)

This example illustrates the installation for a 3-phase 277/480V~ system, again with 12 channels and specific wiring instructions.

Diagram Description: Depicts a 3-phase power connection (L1, L2, L3) to the controller, along with the neutral. The channel connections are shown, with 'xx' marking the required wiring points.

Output Ratings and Specifications

Output Ratings/Channel (CH)

Load Type Rating
General Use 16 A, 277 V~ (UL) / 20 A, 240 V~ (CE)
Incandescent 20 A, 240 V~ (CE)
Standard Ballast 16 A, 277 V~
Electronic Ballast 16 FLA (1 HP), 120 V~
Motor 14.5 FLA (2 1/2 HP), 240 V~ / 14.1 FLA (3 HP), 277 V~
Inrush Current 500 A

Output Ratings/Group

CH-CH ≤ 300 V~ (UL) / 400 V~ (CE)

DDRC1220FR-GL ≤ 180 A

Power Supply: 100-240 V~, 0.25 A

IEC Overvoltage Category: III

Communication and Control Interfaces

The device features several connection ports:

Diagram Description: A detailed schematic shows the internal connections and external interfaces of the DDRC1220FR-GL, including the microprocessor, channel connections, power supply, communication ports (RS-485 DyNet/DMX), and auxiliary connections.

Installation Steps and Considerations

Step 1: Connect the power supply to the 'SUPPLY' terminals (NL, L1, L2, L3 as applicable).

Step 2: Wire the loads to the 'CH' (Channel) IN/OUT terminals. Ensure correct polarity and wire gauge.

Step 3: Connect the communication cables (RS-485 DyNet) to the designated ports. Observe the maximum cable length of 20 meters.

Step 4: Connect any auxiliary devices or emergency lighting systems as required.

Step 5: Ensure all connections are secure and comply with local electrical codes.

Diagram Description: An illustration shows a hand connecting wires to the terminal blocks, with labels indicating 'ON' and 'OFF' states for the channels.

Regulatory Information

FCC Compliance Notice: This equipment complies with Part 15 of the FCC Rules for Class B digital devices. It is designed to provide reasonable protection against harmful interference in residential installations.

Canadian Compliance: This Class B digital apparatus complies with Canadian ICES-003.

General Installation Compliance: Installation of a home and building automation and control system shall comply with IEC 60364 (all parts). The temperature limits and current-carrying capacities for the communication wires specified in IEC 60364-5-52 shall not be exceeded.

Contact and Further Information

For further information and support, please refer to the Philips Dynalite website: www.dynalite.com

© 2022 Signify Holding. All rights reserved.

Models: DDRC1220FR-GL, Relay Controller, DDRC1220FR-GL Relay Controller, Controller

File Info : application/pdf, 4 Pages, 1.14MB

PDF preview unavailable. Download the PDF instead.

DYN DDRC1220FR-GL II-R21

References

Adobe PDF Library 16.0.7 Adobe InDesign 17.2 (Macintosh)

Related Documents

Preview Philips Dynalite DDFCUC010 Fan Coil Unit Controller Installation Instructions
Detailed installation guide for the Philips Dynalite DDFCUC010 Fan Coil Unit Controller, covering wiring, connections, safety precautions, and output specifications for HVAC systems.
Preview Philips Dynalite DDBC120-DALI DALI-2 Driver Controller Installation Instructions
Comprehensive installation guide for the Philips Dynalite DDBC120-DALI DALI-2 Driver Controller. Covers electrical specifications, wiring diagrams, safety warnings, and compliance information for professional installers.
Preview Philips Dynalite PAxBPE AntumbraButton User Interface Installation Guide
Comprehensive installation guide for the Philips Dynalite PAxBPE AntumbraButton User Interface. Provides detailed steps for electrical installation, wiring, mounting, and compliance information for home and building automation systems.
Preview Philips Dynalite PAxBPE AntumbraButton User Interface Installation Guide
Comprehensive installation instructions for the Philips Dynalite PAxBPE AntumbraButton User Interface, detailing safety precautions, mounting procedures, wiring specifications, and compliance information for lighting control systems.
Preview Philips Dynalite DDBC120-DALI DALI-2 Driver Controller Installation Instructions
Detailed installation instructions for the Philips Dynalite DDBC120-DALI DALI-2 Driver Controller, covering electrical specifications, wiring, safety, and compliance.
Preview Philips Dynalite DCM-DyNet Communications Module Installation Guide
Comprehensive installation instructions for the Philips Dynalite DCM-DyNet Communications Module, detailing wiring, mounting, and system integration for lighting control applications.
Preview Philips Dynalite DMC4 Modular Controller Installation Instructions
This document provides comprehensive installation instructions for the Philips Dynalite DMC4 Modular Controller. It covers essential safety precautions, mounting procedures, wiring diagrams, and system integration details for qualified electricians.
Preview Philips Dynalite DDBC320-DALI DALI-2 Driver Controller Installation Instructions
Detailed installation guide for the Philips Dynalite DDBC320-DALI DALI-2 Driver Controller, covering safety, wiring, and setup for professional lighting control systems.