Philips Dynalite DCM-DyNet Communications Module Installation Guide

This document provides detailed instructions for the installation of the Philips Dynalite DCM-DyNet Communications Module.

Important Safety Information

⚠ Devices must be installed by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.

Les appareils doivent être installés par un électricien diplômé conformément à tous les codes et réglementations électriques et de construction nationaux et locaux.

Die Geräte sind von einem qualifizierten Elektriker in Übereinstimmung mit allen geltenden Vorschriften zu installieren.

Los dispositivos deben ser instalados por un electricista calificado y cumpliendo todas las normas y regulaciones, tanto nacionales como locales, sobre instalaciones eléctricas y obras.

I dispositivi devono essere installati da un elettricista qualificato in conformità con le norme locali e nazionali vigenti in materia di costruzioni edilizie e installazione di impianti elettrici.

De apparaten moeten worden aangebracht door een gekwalificeerde elektricien en in overeenstemming met alle nationale en plaatselijke elektriciteits- en bouwvoorschriften.

装置を取り付ける際は、資格のある電気技師に依頼し、国および地域の電気および建設に関するすべての法令に従ってください。

根据国家/地区及当地的电气与建筑规范和法规,该设备必须由有资质的电工进行安装。

يجب تركيب الأجهزة من قبل فني كهربائي مؤهل وفقًا لكافة قوانين ولوائح التركيب الكهربائي المحلي والوطني.

Product Overview and Dimensions

The DCM-DyNet Communications Module is a component for the Philips Dynalite lighting control system.

Diagram Description (Page 1): This diagram shows the DCM-DyNet module with its physical dimensions: 60 mm (2.36 in) width, 94 mm (3.70 in) height, and 305 mm (12.01 in) depth. It illustrates the various connection terminals available on the module, including BUS, RJ12 ports, DMX Rx, UL924 Dry Contact Inputs, and RS-485 DyNet connections. The diagram also shows essential tools required for installation: pliers, wire strippers, and screwdrivers.

Installation and Wiring

Diagram Description (Page 2, Figure 2): This illustration shows the DCM-DyNet module mounted within a typical enclosure, connected to a 12V or 24V power supply and integrated into the DyNet network.

Diagram Description (Page 2, Figure 3): This diagram outlines a DMX 512 system configuration, demonstrating how the DCM-DyNet module interfaces with a DMX controller and other DMX 512 devices.

Diagram Description (Page 2, Figure 4): This shows the procedure for mounting the DCM-DyNet module onto a standard DIN rail. It specifies a torque of 1 Nm (8.8 Lb-in) for securing connections.

Diagram Description (Page 3, Figure 5): This figure provides detailed wiring instructions for the UL924 Dry Contact Inputs and the RS-485 DyNet/DMX Rx connections. It labels specific terminals for power (+24V, GND), inputs (IN1, IN2, IN3, IN4), and data communication (D+, D-, SHLD).

Diagram Description (Page 3, Figure 6): This section details RS-485 DyNet wiring, presenting options for using RJ12 connectors and screw terminals. It specifies suitable cable gauges (e.g., ≤2.5 mm², 12+ AWG) and torque recommendations (0.5 Nm / 4.4 Lb-in).

Diagram Description (Page 3, Figure 7A & 7B): These diagrams illustrate specific wiring examples for the DMC2 and DMC4 modules, showing connections for DMX and RS-485 DyNet interfaces.

Diagram Description (Page 4, Figures 8 & 9): These figures show the physical arrangement and connection of DMC2 and DMC4 modules within an enclosure.

Diagram Description (Page 4, Figure 10): This diagram provides a system overview, illustrating how multiple DCM-DyNet modules are interconnected via the RS-485 DyNet network.

Diagram Description (Page 4, Figure 11): This shows the process of inserting a memory card into the DCM-DyNet module.

Diagram Description (Page 4, Figure 12): This displays the DCM-DyNet Communication Module with its identification barcode and product name.

Environmental and Operating Conditions

Diagram Description (Page 2, Figure 2): Indicates IEC Pollution Degree II.

Operating Temperature: 0° C (32° F) to 40° C (104° F).

Humidity: ≤90% (non-condensing).

Compliance Information

The product complies with IEC Overvoltage Category III.

Federal Communications Commission (FCC) Compliance Notice: This equipment complies with Part 15 of the FCC Rules for Class B digital devices. It is designed to provide reasonable protection against harmful interference in residential installations. Users are advised to correct interference by reorienting antennas, increasing separation, or consulting a technician. Modifications not approved by the manufacturer may void the user's authority to operate the device.

Installation of home and building automation systems must comply with HD 60364-4-41. Temperature limits and current-carrying capacities for communication wires specified in HD 384.5.523 must not be exceeded.

This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B).

Models: DCM-DyNet, Dynalite Multipurpose Controllers, DCM-DyNet Dynalite Multipurpose Controllers, Multipurpose Controllers, Dynalite DMC4 UL

File Info : application/pdf, 4 Pages, 1.10MB

PDF preview unavailable. Download the PDF instead.

DCM4-UL-Installation-Instuction

References

PDFium PDFium

Related Documents

Preview Philips Dynalite Multipurpose Controllers: Comprehensive Product Overview
Explore the Philips Dynalite Multipurpose Controllers, a versatile range of lighting control solutions designed for diverse load types and project requirements. Learn about their benefits, features, and various models.
Preview Philips Dynalite DMC4 Modular Controller Installation Instructions
This document provides comprehensive installation instructions for the Philips Dynalite DMC4 Modular Controller. It covers essential safety precautions, mounting procedures, wiring diagrams, and system integration details for qualified electricians.
Preview Philips Dynalite Multipurpose Controllers | Product Family Leaflet
Explore the Philips Dynalite range of multipurpose controllers, offering customizable lighting control solutions for various load types. This leaflet details benefits, features, applications, and product versions with their specifications.
Preview Philips Dynalite Multipurpose Controllers: Versatile Lighting Control Solutions
Discover the Philips Dynalite Multipurpose Controllers, offering versatile and customizable lighting control for various applications. Learn about their features, benefits, and different models for efficient project management.
Preview Philips Dynalite Multipurpose Controllers: Versatile Lighting Control
Explore the Philips Dynalite Multipurpose Controllers, offering flexible and efficient lighting control solutions for various applications. Learn about their features, benefits, and available models for seamless integration into any lighting project.
Preview Philips Dynalite Multi-Function Controller: Simple, Energy-Efficient Lighting Control
Explore the Philips Dynalite Multi-Function Controller, a sophisticated yet simple lighting control solution designed for energy efficiency. This document details various Dynalite modules and their applications in retail, hospitality, offices, public spaces, and residential areas.
Preview Philips Dynalite DDFCUC010 Fan Coil Unit Controller Installation Instructions
Detailed installation guide for the Philips Dynalite DDFCUC010 Fan Coil Unit Controller, covering wiring, connections, safety precautions, and output specifications for HVAC systems.
Preview Philips Dynalite DDNP1501 Network Power Supply Installation Instructions
Detailed installation guide for the Philips Dynalite DDNP1501 Network Power Supply, covering electrical connections, physical specifications, environmental requirements, and safety guidelines.