MEAN WELL XDR-150E Series: 150W AC/DC Economical Ultra Slim Industrial DIN Rail Power Supply
The XDR-150E series offers a compact, high-performance, and reliable solution for industrial power needs.
Key Features
- 85~264Vac input range
- Global certificates in multi-fields (ITE 62368-1, Industrial 61558-1/-2-16, 61010)
- 30mm slim width
- High efficiency up to 91% and low no-load power dissipation (0.6W~1W)
- Built-in constant current limiting circuit
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Fanless design, cooling by free air convection
- Over voltage category III (OVC III)
- -40~+70°C wide range operation temperature (>+50°C derating)
- Operating altitude up to 5000 meters
- Built-in DC OK relay contact
- Can be installed on DIN rail TS-35/7.5 or 15
- 3 years warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
- Battery charger
Description
The XDR-150E series is a 150W AC/DC economical ultra-slim industrial DIN rail power supply. Key features include a narrow 30mm casing for optimized system installation space and an ultra-wide input range of 85~264Vac for global use. It boasts a maximum efficiency of 91% and low standby power consumption of 0.6W~1W for energy savings. The series includes built-in constant current limiting, a fanless design, a wide operating temperature range of -40 to +70℃ (derating above +50℃), OVCIII compliance, and a built-in DC OK signal. With comprehensive protection functions, complete safety certifications, and a 3-year warranty, the XDR-150E series is a compact, high-performance, and highly reliable DIN rail power supply.
Specifications
XDR-150E-12 | XDR-150E-24 | XDR-150E-36 | XDR-150E-48 | ||
---|---|---|---|---|---|
OUTPUT | |||||
DC VOLTAGE | 12V | 24V | 36V | 48V | |
RATED CURRENT | 115VAC | 10A | 5.2A | 3.46A | 2.6A |
230VAC | 11A | 6.5A | 4.33A | 3.25A | |
CURRENT RANGE | 115VAC | 0~10A | 0~5.2A | 0~3.46A | 0~2.6A |
230VAC | 0~11A | 0~6.5A | 0~4.33A | 0~3.25A | |
RATED POWER | 115VAC | 120W | 124.8W | 124.56W | 124.8W |
230VAC | 132W | 156W | 155.88W | 156W | |
RIPPLE & NOISE (max.) | 100mVp-p | 120mVp-p | 150mVp-p | 200mVp-p | |
VOLTAGE ADJ. RANGE | 12~15V | 24~29V | 36~42V | 48~55V | |
VOLTAGE TOLERANCE | ±2.0% | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME | 1200ms, 60ms/230Vac | 2500ms, 60ms/115Vac at full load | |||
HOLD UP TIME (Typ.) | 16ms/230Vac | 8ms/115Vac at full load | |||
INPUT | |||||
AC VOLTAGE RANGE | 85~264Vac | ||||
DC VOLTAGE RANGE | 120~370Vdc | ||||
NO LOAD POWER CONSUMPTION (Typ.) | 0.6W @115Vac / 0.9W @ 230Vac (XDR-150E-12); 0.8W @115Vac / 1W @ 230Vac (XDR-150E-24) | ||||
FREQUENCY RANGE | 47~63Hz | ||||
EFFICIENCY (Typ.) | 89% | 91% | 91% | 91% | |
AC CURRENT (Typ.) | 2.6A/115Vac | 1.6A/230Vac | |||
INRUSH CURRENT (Typ.) | COLD START 40A/230Vac | 20A/115Vac | |||
LEAKAGE CURRENT | <1mA/240Vac | ||||
PROTECTION | |||||
OVERLOAD | 105~150% rated output power, constant current limiting without shutdown, recovers automatically after fault condition is removed (105~130% rated output power, constant current limiting without shutdown, recovers automatically after fault condition is removed/115Vac) | ||||
OVER VOLTAGE | 15~18V | 30~34V | 43~50V | 56~65V | |
OVER TEMPERATURE | Protection type: Shut down o/p voltage, recovers automatically after fault condition is removed | ||||
FUNCTION | |||||
DC OK RELAY CONTACT | Relay Contact Ratings (max.): 30Vdc/1A, 30Vac/0.5A resistive load | ||||
ENVIRONMENT | |||||
WORKING TEMP. | -40~+70°C (Refer to "Derating Curve") | ||||
WORKING HUMIDITY | 20~95% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -40~+85°C, 10~95% RH non-condensing | ||||
TEMP. COEFFICIENT | ±0.03% /°C (0~50°C) | ||||
VIBRATION | Component: 10~500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
Safety & EMC
XDR-150E-12 | XDR-150E-24 | XDR-150E-36 | XDR-150E-48 | |
---|---|---|---|---|
SAFETY STANDARDS | UL61010; TUV BS EN/EN62368-1, BS EN/EN61558-1/-2-16, BS EN/EN61010; CB IEC62368-1, IEC61558-1, IEC61010; RCM AS/NZS 62368-1, AS/NZS 61558-1/-2-16; BSMI CNS15598-1; CCC GB4943.1; EAC TPTC004 approved; KC KC62368-1 and BIS IS13252 (Part 1):2010 certified, no stock, contact sale for inquires | |||
OVER VOLTAGE CATEGORY | IEC/EN 61558-1/-2-16 (OVC III, altitude up to 2000m) | IEC/EN 61010 (OVC II, altitude up to 5000m) | IEC/EN 62368-1 (OVC II, altitude up to 5000m) | IEC/EN 61558-2-16 (SELV) |
SAFETY EXTRA-LOW VOLTAGE(SELV) | IEC/EN 61010-2-201 (SELV) | IEC/EN 62368-1 (SELV / ES1) | ||
WITHSTAND VOLTAGE | I/P-O/P: 4KVac I/P-FG: 2KVac O/P-FG: 1.5KVac O/P-DC OK: 0.5KVac | |||
ISOLATION RESISTANCE | 100M Ohms/500Vdc/25°C/70%RH | |||
EMC EMISSION | ||||
Parameter | Standard | Test Level / Note | ||
Conducted | BS EN/EN55032 (CISPR32) / BS EN/EN61204-3/CNS15936 | Class B | ||
Radiated | BS EN/EN55032 (CISPR32) / BS EN/EN61204-3/CNS15936 | Class B | ||
Harmonic Current | BS EN/EN61000-3-2 | Class A(80% LOAD) | ||
Voltage Flicker | BS EN/EN61000-3-3 | --- | ||
EMC IMMUNITY | ||||
Parameter | Standard | Test Level / Note | ||
ESD | BS EN/EN61000-4-2 | Level 3, 8KV air; Level 2, 4KV contact; criteria A | ||
Radiated | BS EN/EN61000-4-3 | Level 3, 10V/m; criteria A | ||
EFT/Burst | BS EN/EN61000-4-4 | Level 3, 2KV; criteria A | ||
Surge | BS EN/EN61000-4-5 | Level 4, 2KV/Line-Line ; Level 4, 4KV/Line-Line-Chassis ; criteria A | ||
Conducted | BS EN/EN61000-4-6 | Level 3, 10V; criteria A | ||
Magnetic Field | BS EN/EN61000-4-8 | Level 4, 30A/m; criteria A | ||
OTHERS | ||||
MTBF | 2201.7K hrs min. Telcordia SR-332 (Bellcore); | 440.4K hrs min. MIL-HDBK-217F (25°C) | ||
DIMENSION | 30*125.2*116mm (W*H*D) | |||
PACKING | 430g; 24pcs/11.3Kg/1.16CUFT |
Block Diagram
The block diagram illustrates the internal components and signal flow of the XDR-150E series power supply, including EMI filter, rectifiers, power switching, PWM control, and DC OK relay contact.
Diagram Description: The diagram shows an input stage with an EMI filter and rectifiers, followed by a power switching stage controlled by PWM. Protection circuits like OLP (Over Load Protection) and OTP (Over Temperature Protection) are integrated. The output stage includes rectifiers and filters, with a DC OK signal and relay control.
Derating Curve
Diagram Description: The derating curve graph shows the relationship between ambient temperature (°C) on the x-axis and load percentage (%) on the y-axis. It indicates that the power supply can operate at 100% load up to approximately 50°C, after which the load capacity decreases as the temperature increases, reaching 75% load at 60°C and a reduced capacity at 70°C.
Static Characteristics
Diagram Description: The static characteristics graph illustrates the load percentage (%) versus input voltage (V) for different output voltage models. For the 12V model, the output is stable at 100% load from approximately 100V to 264V input. For the 24V to 48V models, the output is stable at 100% load from approximately 135V to 264V input, with a slight reduction in load capacity at lower input voltages.
Function Manual: DC OK Relay Contact
The DC OK relay contact indicates the status of the power supply unit (PSU). When the PSU is ON and the DC OK signal is active, the contact is closed. When the PSU turns OFF or experiences a DC Fail, the contact is open.
Contact Ratings (max.): 30Vdc/1A, 30Vac/0.5A resistive load.
Diagram Description: An internal circuit diagram shows the DC OK status via a relay contact. Another diagram shows the physical unit with indicators for +Vo, -Vo, Status, Vo Adj., and DC OK.
Mechanical Specification
Dimensions: 30mm (Width) x 125.2mm (Height) x 116mm (Depth).
Diagram Description: Mechanical drawings show the dimensions and terminal pin assignments for AC input, DC output, and the DC OK relay contact.
Recommended Wiring
AC Input T.B | DC Output T.B | Signal connector | |
---|---|---|---|
Solid Wire | 6mm² max. | 6mm² max. | 1.5mm² max. |
A.W.G | 20~10 AWG | 16~10 AWG | 24~16 AWG |
Wire Stripping Length | 7~8mm | 7~8mm | 8~9mm |
Screw Terminal Torque | 5 Lb-In | 5 Lb-In | / |
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the instruction manual available at: http://www.meanwell.com/manual.html
File Info : application/pdf, 7 Pages, 345.30KB
DocumentDocumentReferences
Installation Manual-MEAN WELL Switching Power Supply Manufacturer
Product Liability Disclaimer-MEAN WELL Switching Power Supply Manufacturer
Global Trade Item Number (GTIN)-MEAN WELL Switching Power Supply Manufacturer
Related Documents
![]() |
MEAN WELL XDR-150E Series: 150W Economical Ultra Slim Industrial DIN Rail Power Supply Datasheet Comprehensive datasheet for the MEAN WELL XDR-150E series, a 150W AC/DC ultra-slim industrial DIN rail power supply. Features include wide input range, high efficiency, fanless design, wide operating temperature, and various safety certifications. |
![]() |
MEAN WELL XDR-75E Series: 75W Economical Ultra Slim Industrial DIN Rail Power Supply The MEAN WELL XDR-75E series offers a 75W AC/DC economical and ultra-slim industrial DIN rail power supply. Key features include a narrow 30mm width, ultra-wide 85-264Vac input range, high efficiency up to 91%, low standby power consumption (<1W), built-in constant current limiting, and fanless design. It operates in a wide temperature range (-40 to +70°C) and supports up to 5000 meters altitude. Comprehensive protections, global safety certifications, and a 3-year warranty make it a reliable choice for industrial control, factory automation, and battery charging applications. |
![]() |
MEAN WELL XDR-75E Series: 75W Economical Ultra Slim Industrial DIN Rail Power Supply Detailed specifications and features of the MEAN WELL XDR-75E series, a 75W AC/DC economical ultra-slim industrial DIN rail power supply. Includes technical data, applications, safety certifications, and installation guidelines. |
![]() |
MEAN WELL XDR-240E Series: 240W Economical Ultra Slim Industrial DIN Rail Power Supply Datasheet Detailed specifications, features, applications, and technical data for the MEAN WELL XDR-240E series 240W AC/DC economical ultra-slim industrial DIN rail power supply. Includes dimensions, electrical characteristics, safety compliance, and installation information. |
![]() |
MEAN WELL XDR-960E Series: 960W AC/DC Economical Ultra Slim Industrial DIN Rail Power Supply Detailed datasheet for the MEAN WELL XDR-960E series 960W AC/DC industrial DIN rail power supply. Features include ultra-slim design, high efficiency, wide operating temperature, parallel function, and comprehensive protections. |
![]() |
Confirmation Letter of Declaration for SuZhou MEAN WELL Technology Co., Ltd. XDR-75E Series Power Supplies This document is a Confirmation Letter of Declaration for the XDR-75E series power supplies manufactured by SuZhou MEAN WELL Technology Co., Ltd. It details the product's compliance with safety standards, including a list of critical components and their specifications. |
![]() |
明纬 (MEAN WELL): 标准开关电源制造商 - 全面产品目录 探索明纬 (MEAN WELL) 广泛的标准开关电源产品系列,包括 AC-DC、DC-DC、DC-AC 转换器、LED 驱动器等。自 1982 年以来,为全球行业提供可靠的电源解决方案。 |
![]() |
MEAN WELL XTR-240 Series 240W AC/DC 3Ø Input Ultra Slim Industrial DIN Rail Power Supply Detailed technical specifications and features for the MEAN WELL XTR-240 series, a 240W AC/DC 3-phase ultra-slim industrial DIN rail power supply. Includes information on efficiency, operating temperature, safety certifications, applications, and installation. |