EV 200 ENERGY RECOVERY VENTILATOR
SPECIFICATIONS & DIMENSIONS
INDOOR UNIT
Note: There are multiple control options designed to address individual climate conditions. Please consult your local installer for the best installation controls for your climate.
ELECTRICAL DATA
HP | Volts | Hz | Phase | Watts | FLA |
---|---|---|---|---|---|
0.1 | 120 | 60 | Single | 157 @ 181 CFM | 1.5 |
SPECIFICATIONS
Ventilation Type: Static plate, heat and humidity transfer
Typical Airflow Range: 100-200 CFM
Unit is HVI Tested/Certified per CSA C439 Protocol: Using one L-100-G5 Core
Standard Features:
- White painted cabinet
- Line-cord power supply
- Low-voltage circuit for controls
- Unit may be mounted in any orientation
- Cross-core differential pressure ports
Controls:
Onboard 24VAC transformer/relay package
Filters:
Total qty. 2, MERV 8, spun-polyester media: 10 1/2" x 21 3/4" x 1"
Unit Weight: 68 lbs.
Max. Shipping Dimensions & Weight (on pallet): 34" L x 44" W x 34" H, 110 lbs.
Units Per Pallet: 4
UNIT PERFORMANCE
Airflow (CFM) | External Static Pressure (Inches Water Column) |
---|---|
95 | 0.80 |
131 | 0.70 |
157 | 0.60 |
172 | 0.50 |
182 | 0.40 |
189 | 0.30 |
195 | 0.20 |
206 | 0.10 |
CORE PERFORMANCE
Airflow (CFM) | Temp EFF% | Total EFF% Winter/Summer |
---|---|---|
95 | 83 | 79/68 |
131 | 80 | 76/64 |
157 | 79 | 74/62 |
172 | 78 | 73/61 |
182 | 77 | 72/60 |
189 | 77 | 71/59 |
195 | 76 | 71/59 |
206 | 76 | 70/58 |
Note: These are core-only ratings and are not HVI certified. Total EFF% calculated at 35/33wb OA and 70/58wb RA (winter) and 98/78wb OA and 75/63wb RA (summer). HVI ratings apply to complete units only. This unit is HVI certified. See HVI certified ratings on pg. 48 of Single/Multi-Family Catalog and at hvi.org.
UNIT DIMENSIONS
AIRFLOW ORIENTATION
〰️ Available as shown in dimension drawing.
UNIT MOUNTING & APPLICATION
⚙️ Can be mounted in any orientation. RA/EA airstream can be switched with OA/SA airstream.
Diagrams:
Top View: Top view showing overall dimensions (33 1/4"), case dimensions (28 3/4"), and two 2 1/4" typical duct connections.
Left View: Left view detailing 'OA' and 'RA' duct connections, 11 7/8" typical dimension, 6" nominal duct, and four pressure ports.
Front View: Front view showing 'EA' and 'SA' duct connections, 20" overall dimension, 23 7/8" case dimension, and a 24V AC control terminal.
Right View: Right view with 'EA' and 'SA' duct connections, 23 7/8" case dimension, 22 1/4" minimum service area, and a 24V AC control terminal.
ABBREVIATIONS
- EA:
- Exhaust Air to outside
- OA:
- Outside Air intake
- RA:
- Room Air to be exhausted
- SA:
- Supply Air to inside
INSTALLATION ORIENTATION
Unit may be installed in any orientation.
NOTES
- UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
- SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.