RenewAire HE 1.5XIN Energy Recovery Ventilator
Indoor Unit
Specifications & Dimensions
Energy recovery core is AHRI Certified® ✔️
Model HE1.5XINH shown.
Certifications: ETL LISTED ⚡
General Specifications
Ventilation Type | Static plate, heat and humidity transfer |
Airflow Range | 375-1,650 CFM |
AHRI 1060 Certified Core | One L62-G5 and one L125-G5 |
Standard Features | Non-fused disconnect, 24VAC transformer/relay package, Cross-core differential pressure ports |
Filters | Total Qty. 4, MERV 8: (2) 14" x 20" x 2" and (2) 16" x 20" x 2" |
Unit Weight | 337-504 lbs., varies by option(s) |
Max. Shipping Dimensions & Weight (on pallet) | H: 70" L x 47" W x 53" H (571 lbs.), V: 70" L x 47" W x 59" H (71 lbs.) |
Motor(s) | Qty. 2, 1.0 HP ea., Direct drive standard motorized impellers |
Available Options
- Qty. 2, variable speed/ECM: Direct drive motors (1.0 HP 120V/1Ph/60Hz, 1.0 HP 208-230V/1Ph/60Hz)
- Independent blower control
- Fused disconnect
- Integrated programmable controls: enhanced, premium
- Bypass economizer damper: dry-bulb temperature controls (standard), enthalpy controls (option)
- Class 1 low leakage motorized isolation dampers: FA, EA or both airstreams
- Gravity backdraft dampers
- Factory mounted filter alarms: both airstreams
- Double wall construction
- Exterior paint: white, custom colors
Accessories
- Filters: MERV 13, 2" (shipped loose)
- Backdraft damper: OA or EA
- Automatic balancing damper: 4", 5", 6"
- Digital time clock: wall mount (TC7D-W), in exterior enclosure (TC7D-E)
- Carbon dioxide sensor/control: wall mount (CO2-W), duct mount (CO2-D)
- IAQ sensor: wall mount (IAQ-W), duct mount (IAQ-D)
- Motion occupancy sensor/control: ceiling mount (MC-C), wall mount (MC-W)
- Smoke detector: duct mount (SD-D)
- BACnet fan control: wall mount (BACNETFC-W)
- Indoor electric duct heater: EK series (1-175 kW)
- Indirect gas-fired duct furnace: GH series (50-400 MBH); installed downstream of any fans
Airflow Performance
External Static Pressure (Inches Water Column)
Blower RPM | 0.00 | 0.25 | 0.50 | 0.75 | 1.00 | 1.25 | 1.50 | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
SCFM | Watts | SCFM | Watts | SCFM | Watts | SCFM | Watts | SCFM | Watts | SCFM | Watts | SCFM | Watts | |
1475 | 1575 | 1545 | 1470 | 1525 | 1570 | 1400 | 1350 | 1435 | 1500 | 1380 | 1225 | 1475 | 1090 | 1435 |
1475 | 950 | 1380 | 940 | 1210 | 795 | 1300 |
Operation in this zone outside of core airflow limits.
Note: Watts is for the entire unit (2 motors). Airflow performance includes effect of clean, standard filter supplied with unit.
Electrical Data
Watts | Volts | Hz | Phase | FLA per motor | Min. Cir. Amps | Max. Overcurrent Protection Device |
---|---|---|---|---|---|---|
1 | 120 | 60 | Single | 6.5 | 14.6 | 20 |
1 | 208-230 | 60 | Single | 3.3-3.4 | 7.7 | 15 |
1 | 277 | 60 | Single | 2.7 | 6.1 | 15 |
1 | 208-230 | 60 | Three | 2.2-2.2 | 5.0 | 15 |
1 | 460 | 60 | Three | 1.13 | 2.5 | 15 |
Augmented Reality (AR)
Scan QR code to see life size version of HE1.5X, or view here: https://ar.marketscale.com/renewaire/he
[QR Code Placeholder: Scan for Augmented Reality view]
Unit Mounting & Application
Can be mounted in any orientation. RA/EA airstream can be switched with OA/FA airstream unless certain options are selected. Duct configuration is field convertible.
Installation Orientation: Unit may be installed in any orientation.
Notes:
- 1. UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
- 2. SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
- 3. MIN. DUCT CLEARANCE FROM DAMPER BLADE WHEN FULLY OPENED TO BE 2". SMACNA RULES APPLY.
Dimensional Views & Airflow Configuration
The following describes the unit's dimensions and airflow paths. Specific models mentioned include HE1.5XINH and HE1.5XINV.
Top View
Depicts the unit's top profile. Key features include: overall dimensions (e.g., HE1.5XINH: 48 3/4" Overall width, 32" Case width, 42 5/8" Case depth; HE1.5XINV: 46 1/4" Overall width, 49 5/8" Case width, 32 5/8" Case depth), patch pan (opening used for alternative unit configurations), door swing, and duct receiving flanges (18" x 18" Typ.).
Front View
Shows the front of the unit. Features include: overall dimensions (e.g., HE1.5XINH: 52 3/4" Case height, 48 3/4" Overall width; HE1.5XINV: 59 1/2" Overall height with Damper Frames), pressure ports (4) Typ., door-interlocked disconnect switch, damper frames (5" Typ.), and duct receiving flanges (18" x 18" Typ.). Airflow paths are indicated: OA (Outside Air), RA (Room Air), FA (Fresh Air), EA (Exhaust Air).
Left View
Illustrates the left side of the unit. Features include: case dimensions (e.g., HE1.5XINH: 53 5/8" Overall height, 52 3/4" Case height; HE1.5XINV: 45 3/4" Case height), duct receiving flanges (18" x 18" Typ.), power wiring inlet (7/8" dia.), control wiring inlet (7/8" dia.), and damper locations (FA Damper Location - Optional, EA Damper Location - Optional).
Right View
Presents the right side of the unit. Features include: overall dimensions, minimum service area (20 1/8"), case dimensions, door swing, and duct receiving flanges (18" x 18" Typ.).
Airflow Configuration
Available as shown in dimension drawings. The unit supports various airflow configurations, typically involving Outside Air (OA), Exhaust Air (EA), Room Air (RA), and Fresh Air (FA).
Bypass Economizer Options
Models with bypass economizers (e.g., HE1.5XINV) include additional features and considerations.
Bypass Airflow Schematic (Top View)
Illustrates the bypass airflow. Key components shown are: 12" Bypass Duct Connection (Direct Mount to Damper, By Others), Face Damper, Bypass Damper, and air streams: RA, EA, FA, BP (Bypass Air outlet). The schematic indicates that OA/FA airstream is not shown in this specific diagram.
Bypass Unit Notes:
- Units with bypass will require additional space for the connection of the bypass duct (by others).
- For installation details, refer to I&O Manual Supplement for Bypass.
Unit Mounting & Application (Bypass): Can be mounted in any orientation. Airstreams cannot be switched.