RenewAire Energy Recovery Ventilation

CSI Specifications

RD-4XRT Product Specification Guide

Model: RENEWAIRE ERV – AIR-AIR ENERGY RECOVERY VENTILATOR

Application: FOR EXTERIOR OR INTERIOR INSTALLATION

Category: CSI MASTERFORMAT CATEGORY 23 72 00

Notice to User

This document is protected by copyright and is the exclusive property of RenewAire, LLC. RenewAire authorizes the user to use this document or portions thereof for limited, non-exclusive purposes to prepare written product specifications for the CSI MasterFormat category above. All information contained herein provided by RenewAire, LLC is for informational purposes only and is furnished without representation or warranty of any kind, express or implied, regarding the user or any other party, including, without limitation, ANY IMPLIED WARRANTY OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, OR NON-INFRINGEMENT. To the extent permitted by applicable law, RenewAire disclaims all liability, and the user assumes all responsibility and risk associated with the use of, or reliance on, this document or the information contained herein, whether modified by the user or not. Users should consult www.renewaire.com to verify that this document corresponds to the most recent version.

For RenewAire product data, including equipment description, catalog, and instruction manuals, visit www.renewaire.com/our-ervs/.

This product is available in several different configurations. The unit is typically installed as part of a building's HVAC system.

For questions regarding this product, please contact your local authorized RenewAire representative. To find your local representative, visit www.renewaire.com/how-to-buy/find-a-dealer/ and select your region.

SECTION 23 72 00 - AIR-AIR ENERGY RECOVERY VENTILATOR

PART 1 – GENERAL

1.1 SUMMARY

This section includes air-air energy recovery ventilators intended for rooftop installation. In this document, these units may be abbreviated as "energy recovery ventilator" (ERV) for brevity.

1.2 REFERENCES

Drawings and general contract provisions, including "General Requirements," "Division 01," "Division 23," and "Specifications," along with common HVAC requirements, apply to work specified herein. Section 23 09 00: Controls and Instrumentation.

1.3 DOCUMENTS TO BE FURNISHED

1.4 QUALITY ASSURANCE

1.5 COORDINATION

PART 2 – PRODUCTS

2.1 MANUFACTURERS

2.2 FABRICATED UNITS

Air-air energy recovery ventilators shall be fully factory assembled and consist of a fixed-plate, cross-flow heat exchanger with no moving parts, a 20-gauge insulated casing [single][double] [G90 galvanized][painted], an outdoor air hood with bird screen, a motorized outdoor air intake damper, filter assemblies for supply and exhaust air, an enthalpy core, a supply air fan assembly, a motorized exhaust air damper, an exhaust air hood, an exhaust fan assembly, and an electrical control box with all specified components and factory-installed internal accessories, tested and prepared for single-point high-voltage connection. The entire unit, except for site-installed components, shall be factory assembled and tested.

2.3 CABINET

2.4 FAN SECTION

2.5 MOTORS

Fan motors shall be high efficiency, EISA compliant, TEFC motors with factory-installed starters.

2.6 UNIT CONTROLS

CONTROLLER DDC:

BMS INTERFACE:

GENERAL OPERATION

POWER UP:

When the unit main circuit breaker is closed, a 10-second (adjustable) delay shall elapse before the controller comes online.

ERV UNIT START COMMAND:

An input signal is required to activate unit operation. The unit is started by:

All activated input types must be true before the unit will start.

ERV UNIT SHUTDOWN COMMAND (OR POWER OFF):

SUPPLY FAN OPERATION:

SUPPLY FAN STATUS:

Once the supply fan current switch is closed, [heating] [cooling] operation is permitted. After a 90-second (adjustable) delay from the supply fan start signal, if the supply fan current switch is still open, the supply fan alarm shall be activated and [heating], [cooling] operation shall be prohibited. Supply fan status shall only be active when the supply fan output is active and the supply fan current switch is closed. Supply fan status shall be inactive under all other circumstances.

FAN FIXED SPEED OPTION:

Analog voltage command to the supply fan VFD can be set from the unit controller screen [or provided by the BMS]. The adjustable range of 0% to 100% corresponds to the minimum and maximum fan speed. This supply fan operating mode can be used to balance supply airflow in the field.

SUPPLY AIRFLOW CONTROL OPTION:

The controller adjusts the supply fan VFD command to maintain the supply airflow at a setpoint. The supply airflow setpoint is entered and adjusted from the unit controller screen [or provided by the BMS]. Minimum and maximum values for the supply airflow setpoint are unit dependent. An adjustable PI (proportional and integral) loop compares the measured supply airflow to the airflow setpoint and adjusts fan speed. If the measured airflow varies by more than 10% (adjustable) from the desired airflow for more than 60 seconds (adjustable), a supply airflow alarm shall be triggered. This supply fan operating mode can be used to provide constant airflow when unit filters become loaded.

SUPPLY DUCT STATIC PRESSURE CONTROL OPTION:

The controller adjusts the supply fan frequency drive command to maintain the supply duct static pressure at a setpoint. The supply duct static pressure setpoint is entered and set from the unit controller screen [or provided by the BMS]. Minimum and maximum values for the supply duct static pressure setpoint are unit dependent. An adjustable PI (proportional and integral) loop compares the measured supply duct static pressure to the static pressure setpoint and adjusts fan speed. If the measured static pressure varies by more than 0.05 inches of water column (adjustable) for more than 60 seconds (adjustable) from the desired static pressure, a supply air static pressure alarm shall be activated. This supply fan operating mode can be used to provide constant duct static pressure for VAV systems.

ROOM STATIC PRESSURE CONTROL OPTION:

The controller adjusts the supply fan frequency drive command to maintain room static pressure at a setpoint. Room static pressure is typically measured as the differential pressure between the room and an adjacent space or the outside. The room static pressure setpoint is entered and set from the unit controller screen [or provided by the BMS]. An adjustable PI (proportional and integral) loop compares the measured room static pressure to the static pressure setpoint and adjusts supply fan speed. If the measured static pressure varies by more than 0.05 inches of water column (adjustable) for more than 60 seconds (adjustable) from the desired static pressure, a supply air static pressure alarm shall be triggered. This supply fan operating mode can be used to maintain constant room static pressure in a zone to control infiltration or exfiltration from an adjacent zone or the outside.

INDOOR AIR QUALITY (TVOC) CONTROL OPTION:

The controller adjusts the supply fan VFD command to maintain the ambient or return air TVOC level at a setpoint. The TVOC setpoint is entered and adjusted from the unit controller screen [or provided by the BMS]. An adjustable PI (proportional and integral) loop compares the measured TVOC level to the TVOC setpoint and adjusts fan speed. Minimum and maximum fan speed commands are adjustable. If the measured TVOC level exceeds 1000 ppm (CO(2) equivalent, adjustable) for more than 60 seconds (adjustable), a TVOC alarm shall be triggered. This supply fan operating mode can be used to provide demand-controlled ventilation for a space. Minimum fan speed shall provide the minimum required outdoor air when the TVOC level is at or below the TVOC setpoint.

CO2 CONTROL OPTION:

The controller adjusts the supply fan VFD command to maintain the room or return air CO2 level at a setpoint. The CO2 setpoint is entered and set from the unit controller screen [or provided by the BMS]. An adjustable PI (proportional and integral) loop compares the measured CO2 level to the CO2 setpoint and adjusts fan speed. Minimum and maximum fan speed commands are adjustable. If the measured CO(2) level exceeds 1000 ppm (adjustable) for more than 60 seconds (adjustable), a CO(2) alarm shall be triggered. This supply fan operating mode can be used to provide demand-controlled ventilation for a space. Minimum fan speed shall provide the minimum required outdoor air when the CO(2) level is at or below the CO(2) setpoint.

CO2 AIRFLOW CONTROL OPTION:

The controller adjusts the supply fan frequency drive command based on the measured room or return air CO2 level. The supply airflow setpoint is derived from the minimum and maximum CO2 levels and desired minimum and maximum airflow rates entered by the user. When the CO(2) level is at or below the minimum CO(2) level, the airflow setpoint is at minimum, and when the CO(2) level is at or above the maximum CO(2) level, the airflow setpoint is at maximum. Between the minimum and maximum CO(2) levels, the airflow setpoint is linearly proportional. If the measured CO(2) level exceeds 1000 ppm (adjustable) for more than 60 seconds (adjustable), a CO(2) alarm shall be triggered. This supply fan operating mode can be used to provide demand-controlled ventilation for a space. Minimum fan speed shall provide the minimum required outdoor air when the CO(2) level is at or below the CO(2) setpoint.

EXHAUST FAN OPERATION:

EXHAUST FAN STATUS:

After a 90-second (adjustable) delay from the exhaust fan start signal, if the exhaust fan current switch is still open, the exhaust fan alarm shall be activated. Exhaust fan status shall only be active when the exhaust fan output is active and the exhaust fan current switch is closed. Exhaust fan status shall be inactive under all other circumstances.

FAN FIXED SPEED OPTION:

Analog voltage command to the exhaust fan VFD can be set from the unit controller screen [or provided by the BMS]. The adjustable range of 0% to 100% corresponds to the minimum and maximum fan operating speed (0 VCC minimum to 10 VCC maximum, adjustable). This exhaust fan operating mode can be used to balance exhaust airflow in the field.

EXHAUST AIRFLOW CONTROL OPTION:

The controller adjusts the exhaust fan VFD command to maintain the exhaust airflow at a setpoint. The exhaust airflow setpoint is entered and adjusted from the unit controller screen [or provided by the BMS]. Minimum and maximum values for the exhaust airflow setpoint are unit dependent. An adjustable PI (proportional and integral) loop compares the measured exhaust airflow to the airflow setpoint and adjusts fan speed. If the measured exhaust airflow varies by more than 10% (adjustable) from the desired airflow for more than 60 seconds (adjustable), an exhaust airflow alarm shall be triggered. This exhaust fan operating mode can be used to maintain constant exhaust airflow when unit filters are saturated.

SUPPLY FAN TRACKING CONTROL OPTION:

The controller adjusts the exhaust fan frequency drive command to track the supply fan command. Minimum (50%) and maximum (200%) tracking rates are adjustable. This exhaust fan operating mode can be used to maintain proportional commands of supply and exhaust fans when the supply fan modulates.

SUPPLY FAN AIRFLOW TRACKING CONTROL OPTION:

The controller adjusts the exhaust fan frequency drive command to track the supply fan airflow. Offset from supply airflow is adjustable from -25% to +25%. An adjustable PI (proportional and integral) loop compares the measured exhaust airflow to the airflow setpoint and adjusts fan speed. If the measured airflow at the outlet varies by more than 10% (adjustable) from the desired airflow for more than 60 seconds (adjustable), an outlet airflow alarm shall be triggered. This exhaust fan operating mode can be used to maintain proportional supply and exhaust airflows when the supply fan modulates and unit filters are loaded.

ROOM STATIC PRESSURE CONTROL OPTION:

The controller adjusts the exhaust fan frequency drive command to maintain room static pressure at a setpoint. Room static pressure is typically measured as the pressure difference between the room and an adjacent space or the outside. The room static pressure setpoint is entered and adjusted from the unit controller screen [or provided by the building automation system (BMS)]. Minimum and maximum values for the exhaust fan speed are adjustable. An adjustable PI (proportional and integral) loop compares the measured room static pressure to the static pressure setpoint and adjusts exhaust fan speed. If the measured static pressure varies by more than 0.05 inches of water column (adjustable) for more than 60 seconds (adjustable) from the desired static pressure, an exhaust air static pressure alarm shall be triggered. This exhaust fan operating mode can be used to maintain constant room static pressure in a zone to control infiltration or exfiltration from an adjacent zone or the outside.

ECONOMIZER (BYPASS) OPERATION:

Under normal operation, the bypass damper shall remain closed and the face damper open to allow for total energy recovery. In economizer mode, the bypass damper shall be open and the face damper closed to bypass the core. Economizer status can be controlled by temperature or enthalpy.

COOLING OPERATION:

Cooling shall be locked out if the outdoor air temperature is below 70 degrees (adjustable) or if heating is active. The temperature setpoint may be configured as constant (adjustable) or reset based on outdoor air temperature. Cooling shall be controlled using supply air temperature or return air temperature.

SUPPLY AIR CONSTANT TEMPERATURE OPTION:

The controller adjusts the 0 to 10 VCC analog output to the cooling device to maintain air temperature at a setpoint. The air temperature setpoint is entered and adjusted from the unit controller screen [or provided by the BMS]. Minimum and maximum values for the supply air temperature setpoint are unit dependent and adjustable. An adjustable PI (proportional and integral) loop compares the measured supply air temperature to the air temperature setpoint and adjusts the 0 to 10 VCC analog output. Two-stage cooling demand indicating digital outputs are also provided. Analog and digital outputs can be used to control a chilled water valve, remote DX condensing units, or a heat pump.

AIR TEMPERATURE RESET OPTION:

The controller adjusts the 0 to 10 VCC analog output to the cooling device to maintain air temperature at a setpoint. The air temperature setpoint is calculated based on outdoor air temperature. The air setpoint is adjusted between a maximum of 70 °F (adjustable) and a minimum of 55 °F (adjustable) when the measured temperature varies between a minimum of 70 °F (adjustable) and a maximum of 90 °F (adjustable). These values are entered and set from the unit controller screen [or provided by the BMS]. An adjustable PI (proportional and integral) loop compares the measured air temperature to the air temperature setpoint and adjusts the analog output. Two-stage cooling demand indicating digital outputs are also provided. Analog and digital outputs can be used to control a chilled water valve, remote DX condensing units, or a heat pump. Coil freeze protection shall be provided by others in the field.

HEATING OPERATION:

Heating shall be locked out if the outdoor air temperature is above 70 degrees (adjustable). The temperature setpoint may be configured as constant (adjustable) or reset based on outdoor air temperature. Heating shall be controlled using supply air temperature or return air temperature.

CONSTANT TEMPERATURE OPTION:

The controller energizes heating equipment or adjusts the 0 to 10 VCC analog output to the heating equipment to maintain air temperature at a setpoint. The air temperature setpoint is entered and set from the equipment controller screen [or provided by the BMS]. Minimum and maximum values for the air temperature setpoint are equipment dependent and adjustable. An adjustable PI (proportional and integral) loop compares the measured air temperature to the air temperature setpoint and adjusts the analog output. A digital output indicating heating demand is also provided. Analog and digital outputs can be used to control a hot water valve, electric heater, gas heater, or heat pump.

AIR TEMPERATURE RESET OPTION:

The controller adjusts the 0 to 10 VCC analog output to the heating device to maintain air temperature at a setpoint. The air temperature setpoint is calculated based on outdoor air temperature. The air setpoint is adjusted between a maximum of 100 °F (adjustable) and a minimum of 70 °F (adjustable) when the measured temperature varies between a minimum of 20 °F (adjustable) and a maximum of 70 °F (adjustable). These values are entered and adjusted from the unit controller screen [or provided by the BMS]. An adjustable PI (proportional and integral) loop compares the measured supply air temperature to the supply air temperature setpoint and adjusts the 0 to 10 VCC analog output. A digital output indicating heating demand is also provided. Analog and digital outputs can be used to control a hot water valve, electric heater, gas heater, or heat pump. Coil freeze protection shall be provided by others in the field.

2.7 FILTER SECTION

The ERV shall be equipped with 2-inch thick disposable pleated filters [MERV 8][MERV 13] located in the outdoor and exhaust air streams. All filters shall be accessible from the exterior of the unit.

2.8 COILS

2.9 EVAPORATOR COILS

PART 3 – EXECUTION

3.1 EXAMINATION

3.2 INSTALLATION

3.3 CONNECTIONS

In all cases, industry best practices shall be followed. Connections shall be made in accordance with the installation requirements indicated above.

3.4 SITE QUALITY CONTROL

The contractor shall inspect the assembled components on site and the installation of the equipment, including electrical and piping connections. The contractor shall submit results in writing to the architect/engineer. Inspection shall include a complete commissioning checklist comprising (at a minimum) the following items: Completed commissioning checklists, as shown in the manufacturer’s operation manual. Insert any other requirements here.

3.5 COMMISSIONING SERVICE

The contractor shall perform commissioning service. Clean the entire unit, comb coil fins if necessary, and install clean filters. Verify that the water source complies with the manufacturer’s requirements for flow and temperature. Measure and record electrical voltage and amperage values. Refer to Division 23 “Testing, Adjusting, and Balancing” and comply with provisions therein.

3.6 DEMONSTRATION AND TRAINING

The contractor shall train the owner’s maintenance personnel on the adjustment, operation, and maintenance of the entire makeup air unit. Refer to Division 01, section “Closeout Procedures, Demonstration, and Training.”

PDF preview unavailable. Download the PDF instead.

v1 macOS Version 14.4 (Build 23E214) Quartz PDFContext

Related Documents

Preview RenewAire CA-4XIN Energy Recovery Ventilator (ERV) CSI Specifications
Detailed technical specifications for the RenewAire CA-4XIN Energy Recovery Ventilator (ERV), covering general requirements, product details, and execution for HVAC systems.
Preview RenewAire PA12XIN ERV Specifications
Comprehensive technical specifications for the RenewAire PA12XIN Air-to-Air Energy Recovery Ventilator (ERV). This document details general provisions, product requirements including cabinet and core specifications, and execution guidelines for installation, quality control, and start-up. It covers CSI MasterFormat 23 72 00 requirements for HVAC systems.
Preview Spécifications du Ventilateur à Récupération d'Énergie RenewAire CA-3XRT
Spécifications techniques détaillées pour le Ventilateur à Récupération d'Énergie Air-Air RenewAire CA-3XRT, incluant les exigences générales, l'assurance qualité, les détails du produit et les instructions d'installation.
Preview RenewAire CA-3XIN Air-to-Air Energy Recovery Ventilator Specifications
Comprehensive CSI specifications for the RenewAire CA-3XIN ERV, detailing product features, quality assurance, installation, and execution requirements for HVAC systems.
Preview RenewAire CA-2XIN ERV: Air-to-Air Energy Recovery Ventilator Specification Guide
Detailed CSI specification guide for the RenewAire CA-2XIN Air-to-Air Energy Recovery Ventilator (ERV). Covers general requirements, product specifications, quality assurance, submittals, and execution for indoor or outdoor installation, adhering to industry standards like AHRI 1060 and UL 723.
Preview RenewAire LE-6XRT Air-to-Air Energy Recovery Ventilator Specification Guide
Detailed product specification guide for the RenewAire LE-6XRT Air-to-Air Energy Recovery Ventilator (ERV), covering general information, product details, and execution requirements for HVAC systems.
Preview RenewAire HE-1XIN Air-to-Air Energy Recovery Ventilator CSI Specification
This document provides the CSI Specification for the RenewAire HE-1XIN Air-to-Air Energy Recovery Ventilator, designed for outdoor or indoor installation. It details product specifications, quality assurance, manufacturers, manufactured units, cabinet construction, blower section, motors, unit controls, sequence of operations, and execution requirements.
Preview RenewAire PA-6XIN ERV: Product Specifications
Detailed technical specifications for the RenewAire PA-6XIN Energy Recovery Ventilator (ERV), covering product features, installation, quality assurance, and performance criteria.