LOW PROFILE MULTI-FAMILY RESIDENTIAL/LIGHT COMMERCIAL
SL 75 ENERGY RECOVERY VENTILATOR EC MOTOR
INDOOR UNIT
Overview
Note: There are multiple control options designed to address individual climate conditions. Please consult your local installer for the best installation controls for your climate.
Specifications
Ventilation Type: Static plate, heat and humidity transfer
Typical Airflow Range: 30-130 CFM
HVI Tested/Certified per CSA C439 Protocol: Using one L-30-G5 Core
Standard Features:
- White painted cabinet
- Line-cord power supply or hard wired to junction box (H)
- Low-voltage circuit for controls
- Unit may be mounted in any orientation
- Cross-core differential pressure ports
- Dial-A-Flow: balance and airflow adjustment
- Variable speed
- Boost-mode
Controls:
- Onboard digital controller with independent variable speeds
Filters:
- Total qty. 2, MERV 8, spun-polyester media: 7 1/2" x 10 1/2" x 1"
Unit Weight: 35 lbs.
Max. Shipping Dimensions & Weight (in carton): 31 1/4" L x 22 3/8" W x 14 3/8" H, 41 lbs.
Units Per Pallet: 10
Motor(s)
- Qty. 2, 120V EC motorized impellers
Accessories:
- Backdraft damper: 6", 8"
- Automatic balancing damper: 4", 5", 6"
- Motorized dampers: 6", 8"
- Concentric vent: 6" (CV6-110)
- Louvered wall vent 6": white, brown
- Louvered wall vent 8": taupe vinyl, galvanized, paintable galvanneal
- Louvered wall vent with 8" round duct connection: 12" W x 8" H
- Digital time clock: wall mount (TC7D-W), in exterior enclosure (TC7D-E)
- Carbon dioxide sensor/control: wall mount (CO2-W)
- IAQ sensor: wall mount (IAQ-W)
- Motion occupancy sensor/control: ceiling mount (MC-C), wall mount (MC-W)
- Push-button boost timer (PBT)
- Percentage timer control (PTL)
- Percentage timer control with furnace interlock (FM)
- BACnet fan control: wall mount (BACNETFC-W)
- Push-button point-of-use controls (PBL), PTL req'd.
- MERV 13 filter: OA airstream (shipped loose)
- Wall bracket kit
- Electric duct heater: RH series (1-4 kW); designed for indoor ductwork installation only
EC Motor Operating Range and Core Performance
This section presents the operating characteristics of the EC motor. A graph illustrates the relationship between Airflow (CFM) on the horizontal axis and External Static Pressure (ESP in. H2O) on the vertical axis, showing performance across a range of airflow from 0 to 140 CFM and ESP from 0 to 1.8 in. H2O. Two data sets are shown: "Actual tested sample points" (dots) and "Operating curves" where airflow is held constant as static pressure varies.
Airflow (CFM) | External Static Pressure (Inches Water Column) | Unit Power Consumption (Watts) | Sensible EFF% | Total EFF% Winter/Summer | |
---|---|---|---|---|---|
Max. Speed | Min. Speed | ||||
138 | 0.10 | 135 | 11 | 62 | 54/36 |
131 | 0.20 | 134 | 9 | 64 | 55/38 |
125 | 0.30 | 133 | 65 | 57/40 | |
117 | 0.40 | 132 | 66 | 59/42 | |
110 | 0.50 | 131 | 68 | 60/44 | |
102 | 0.60 | 129 | 69 | 62/46 | |
95 | 0.70 | 126 | 71 | 64/48 | |
87 | 0.80 | 123 | 72 | 66/51 | |
78 | 0.90 | 119 | 74 | 68/53 | |
68 | 1.00 | 114 | 76 | 70/56 | |
49 | 1.20 | 102 | 79 | 75/61 | |
21 | 1.40 | 64 | 85 | 85 | 81/69 |
26 | 0.10 | 11 | 84 | 80/68 | |
11 | 0.20 | 9 | 87 | 83/72 |
Factory Settings
- 1. High speed set to top curve.
- 2. Low speed set to ~90CFM at 0.4 in. w.g. ESP.
Notes:
- Watts is for the entire unit.
- Airflow performance includes effect of clean, standard filter supplied with unit.
- Refer to CORES for specific operating point electrical data.
- These are core-only ratings and are not HVI certified. Total EFF% calculated at 35/33wb OA and 70/58wb RA (winter) and 95/78wb OA and 75/63wb RA (summer). HVI ratings apply to complete units only. This unit is HVI certified. See HVI certified ratings on pg. 46 of Single/Multi-Family Catalog and at hvi.org.
Electrical Data
Watts | Volts | Hz | Phase | FLA per motor | Minimum Circuit Amps | Max Overcurrent Protection Device |
---|---|---|---|---|---|---|
53 | 120 | 60 | 1 | 0.85 | 15 | 15 |
Specifications & Dimensions
The SL 75 unit is designed for low-profile multi-family residential and light commercial applications. It can be mounted in any orientation. The document includes dimension drawings from the Top, Left, Front, and Right views, detailing the unit's physical size, duct connection locations (Ø8" and Ø6" nominal), control terminal access, pressure ports, and mounting considerations (ceiling brackets, hanging brackets). Key dimensions like overall height, width, depth, and required service clearances are provided. The RA/EA airstream can be switched with the OA/SA airstream.
Abbreviations:
- EA: Exhaust Air to outside
- OA: Outside Air intake
- RA: Room Air to be exhausted
- SA: Supply Air to inside
Installation Orientation:
Unit may be installed in any orientation.
Notes:
- UNLESS OTHERWISE SPECIFIED, DIMENSIONS ARE ROUNDED TO THE NEAREST EIGHTH OF AN INCH.
- SPECIFICATIONS MAY BE SUBJECT TO CHANGE WITHOUT NOTICE.
Unit Mounting & Application:
Can be mounted in any orientation. RA/EA airstream can be switched with OA/SA airstream.