AKO D144xx Series Temperature Controllers

1. Warnings

Using the equipment without following the manufacturer's instructions may affect the device's safety requirements. To ensure that the device operates correctly, only probes supplied by AKO should be used.

The unit must be installed in a location protected from vibrations, water, and corrosive gases, where the ambient temperature does not exceed that shown in the technical data.

To ensure a correct reading, the probe must be situated in a location without any external heat influences except for the temperature which is being measured or controlled.

The power supply circuit must be provided with a main switch rated at at least 2 Amperes, 230 Volts AC, located close to the equipment. The cables will enter through the back and should be type H05VV-F or H05V-K.

The gauge (wire gauge) will depend on local regulations, but should in no case be less than 1 square millimeter. Connecting wires for the relay contacts should be sized 2.5 square millimeters.

Between -40 Degrees Celsius and +20 Degrees Celsius, if the NTC probe is prolonged up to 1000 meters with a minimum cable of 0.5 square millimeters, the maximum deviation will be of 0.25 Degrees Celsius (extension cable for probe ref. AKO-15586).

NOTE: Equipment not compatible with AKO-14917 (external communication module) and AKO-14918 (programming key).

2. Installation

The unit is designed for panel mounting with anchors. The panel cutout dimensions are 71 x 29 mm. The front panel dimensions are 79 x 38 mm, with a depth of 61 mm.

3. Wiring

The probe and its cable should NEVER be installed in the same conduit as power, control, or supply cables.

Wiring Diagrams:

Textual description of wiring for different models:

Terminal Descriptions:

4. Operation

Button Functions:

Programming Menu Navigation:

The menu structure is organized into Level 1 (Menus), Level 2 (Parameters), and Level 3 (Values). Navigation is done using the [SET] and [ESC] buttons.

4.1 Access to Set Point and Programming:

To change the set point (SP), press the [SET] key for 5 seconds. To access the programming menu, press the [SET] key for 10 seconds.

5. Start-up

On power-up, the equipment starts in Wizard mode (P3 / 1 flashing). Use the [Up Arrow] or [Down Arrow] to select the most appropriate application and press [SET].

Available applications:

WARNING: The default parameters by type of application have been defined for the most common applications. Check that these parameters are suitable for your installation.

Default Settings by Application:

ApplicationSPd0F0P0
Multipurpose-2480
Frozen-184200
Fruits and vegetables04200
Fresh fish34200
Soft Drinks84200
Bottle racks84200
AC214200
Heat/Incubators374200

6. Table of Parameters and Messages

The Def. column shows factory-set default parameters. Those marked with * are variable parameters depending on the application chosen in the wizard or the P3 parameter. Unless otherwise stated, temperatures are expressed in Degrees Celsius.

Control Parameters (C0-C12, EP)

Level 2Level 3 DescriptionValues (Units)Min.Def.Max.
C0Calibrating probe 1 (Offset)With NTC (Degrees Celsius/Fahrenheit)-20.00.020.0
C1Probe 1 differential (Hysteresis)With NTC (Degrees Celsius/Fahrenheit)0.12.020.0
C2Upper blocking of the set point (cannot be set above this value)With NTC (Degrees Celsius/Fahrenheit)-50 (-58 Fahrenheit)99 (210 Fahrenheit)150 (302 Fahrenheit)
C3Lower blocking of the set point (cannot be set below this value)With NTC (Degrees Celsius/Fahrenheit)-50 (-58 Fahrenheit)-150 (302 Fahrenheit)
C4Type of delay for protection of the compressor: 0=OFF/ON (since the last disconnection); 1=OFF-ON/ON-OFF (since the last shut-down /start-up)001
C5Protection delay time (value of the option selected in parameter C4)(minutes)00120
C6Status of COOL relay with probe fault: 0=OFF; 1=ON; 2=Average based on last 24 hours prior to probe fault; 3=ON-OFF as prog. C7 and C8023
C7Time relay ON in case of faulty probe (If C7=0 and C8≠0, the relay will always be OFF de-energised)(minutes)010120
C8Time relay OFF in case of fault of probe 1 (If C8=0 and C7≠0, the relay will always be ON energised)(minutes)05120
C9Maximum duration of fast freezing mode. (0=off)(hours)02448
C10Change set point (SP) in fast freezing mode, when it reaches this point (SP + C10) returns to normal. (SP+C10 ≥ C3) (0=OFF)(Degrees Celsius/Fahrenheit)0-50 (-58 Fahrenheit)C3-SP
C11Length of inactivity at digital input to activate ECO mode (Only if P10 or P11=1 and P0=0) (0=OFF)(hours)0224
C12Change set point (SP) in ECO mode (SP+C12 ≤ C2) (0=off)(Degrees Celsius/Fahrenheit)02C2-SP
EPExit to Level 1

Defrost Control (d0-d15, EP)

Level 2Level 3 DescriptionValues (Units)Min.Def.Max.
d0Defrost frequency (Time between two starts)(hours)0096
d1Maximum defrost duration (0=defrost deactivated)(minutes)00255
d2Type of message during defrost: 0=Current temperature; 1=Temperature at start of defrost; 2=Display dEF message022
d3Maximum duration of message (time added at the end of the defrost)(minutes)05255
d4Defrost end temperature (probe 2) (If P4 ≠ 1)(Degrees Celsius/Fahrenheit)-50 (-58 Fahrenheit)8 (46 Fahrenheit)99.9 (211 Fahrenheit)
d5Defrost on equipment start-up: 0=NO, First defrost as per d0; 1=YES, First defrost as per d6001
d6Defrost start delay on equipment start-up(minutes)00255
d7Defrost type: 0=Resistors, 1=Inverted cycle (In two-relay equipment, P6 must be programmed to zero)001
d8Calculated time between defrost periods: 0=Total actual time; 1=Sum of times the compressor is on001
d9Drip time at end of defrost (compressor and fans off) (if P4 ≠ 1)(minutes)01255
d101st defrost start time (RTC required)(hours)00 Off023
d112nd defrost start time (RTC required)(hours)00 Off023
d123rd defrost start time (RTC required)(hours)00 Off023
d134th defrost start time (RTC required)(hours)00 Off023
d145th defrost start time (RTC required)(hours)00 Off023
d156th defrost start time (RTC required)(hours)00 Off023
EPExit to Level 1

FAN Control (F0-F5, EP)

Level 2Level 3 DescriptionValues (Units)Min.Def.Max.
F0Fan shut-down temperature as per probe 2 (if P4 ≠ 1)(Degrees Celsius/Fahrenheit)-50 (-58 Fahrenheit)99.9 (211 Fahrenheit)
F1Probe 2 differential (If P4 ≠ 1)(Degrees Celsius/Fahrenheit)0.12.020.0
F2Stop fans when stopping compressor: 0=No, 1=Yes011
F3Fan status during defrost: 0=Off; 1=On001
F4Starting delay after defrost (if F3=0)(minutes)0399
F5Stop fans on opening the door: 0=No, 1=Yes (Requires a digital input configured as port P10 or P11=1)001
EPExit to Level 1

ALARMS Control (A0-A12, EP)

Level 2Level 3 DescriptionValues (Units)Min.Def.Max.
A0Configuration of temperature alarms: 0=Relative to SP; 1=Absolute001
A1Maximum alarm probe 1 (must be greater than SP)With NTC (Degrees Celsius/Fahrenheit)-99.9 (211 Fahrenheit)99.9 (211 Fahrenheit)
A2Minimum alarm probe 1 (must be less than SP)With NTC (Degrees Celsius/Fahrenheit)-50 (-58 Fahrenheit)--
A3Temperature alarm delay during start-up(minutes)00120
A4Temperature alarm delay after completion of a defrost(minutes)0099
A5Temperature alarm delay after reaching the value of A1 or A2(minutes)03099
A6External alarm / Severe external alarm delay when receiving digital input signal (P10 or P11=2 or 3)(minutes)00120
A7Deactivation delay of the external alarm / Severe external alarm when the signal of the digital input disappears (P10 or P11=2 or 3)(minutes)00120
A8Show warning if defrost is terminated by time-out: 0=No, 1=Yes001
A9Alarm relay polarity: 0=Relay ON in alarm (OFF no alarm); 1=Relay OFF on alarm (ON with no alarm)001
A10Temperature Alarm Differential (A1 and A2)(Degrees Celsius/Fahrenheit)0.11.020.0
A12Door open alarm delay (if P10 or P11=1)(minutes)02120
EPExit to Level 1

General Status Parameters (P0-P19, EP)

Level 2Level 3 DescriptionValues (Units)Min.Def.Max.
P0Type of operation: 0=Direct,Cold; 1=Inverted,Heat001
P1Delay of all functions on receiving electrical power(minutes)00255
P2Access code (password) functions: 0=Inactive; 1=Block access to parameters; 2=Keyboard lock002
P4Selection of type of inputs: 1=1 probe + 2 digital inputs; 2=2 probes +1 digital input; 3=3 probes (1)113
P5MODBUS address11255
P6Configuration of AUX relay: 1=Defrost / 2nd Defrost (1); 2=Alarm; 3=Light; 4=Pump down (1); 5=Master Defrost(1)015
P7Temperature display mode: 0=Whole in Degrees Celsius; 1=One decimal in Degrees Celsius; 2=Whole in Degrees Fahrenheit; 3=One decimal in Degrees Fahrenheit013
P8Probe to be displayed (as per parameter P4): 0=visualization of all the probes in sequence; 1=Probe 1; 2=Probe 2; 3=Probe 3 (1)112
P9Selection of probe type: 0=NTC; 1=PTC001
P10Configuring digital input 1: 0= Off; 1=Door contact; 2=External alarm; 3=Severe external alarm; 4=Slave defrost; 5=Act. ECO mode by pushbutton; 6=Act.Fast Freezing; 7= Low pressure switch (1); 8=Remote defrost; 9=Act. ECO mode by switch009
P11Configuring digital input 2: 0= Off; 1=Door contact; 2=External alarm; 3=Severe external alarm; 4=Slave defrost; 5=Act. ECO mode by pushbutton; 6=Act.Fast Freezing; 7=Not used; 8=Remote defrost; 9=Act. ECO mode by switch009
P12Digital input polarity 1: 0=Energised on closed contact, 1=Energised on open contact001
P13Digital input polarity 2: 0=Energised on closed contact, 1=Energised on open contact001
P14Maximum start-up time after pump down ((Values between 1 and 9 seconds are not accepted)(Sec.)10120
P15Maximum pump down time(minutes)0015
P19Lights in ECO Mode (P6=3): 0=ON; 1=OFF001
EPExit to Level 1

REAL TIME CLOCK Parameters (RTC required)

Level 2Level 3 DescriptionValues (Units)Min.Def.Max.
r1Clock configuration:HOUR(hours)0023
r2Clock configuration:MINUTES(minutes)0059
EPExit to Level 1

Access and Information Control

Level 2Level 3 DescriptionValues (Units)Min.Def.Max.
L5Access code (Password)0-99
PUProgram version (Information)---
PrProgram revision (Information)---
EPExit to Level 1

MESSAGES

7. Technical Specifications

Power Supply

ModelPower Supply
AKO-D1441212 Volts AC ±20% 2 VA
AKO-D14412-RC12 Volts AC ±20% 3 VA
AKO-D14420120 Volts AC +8% -12% 50/60 Hz 4 VA
AKO-D14123-2-RC/D14423-RC/D14323-C90-240 Volts AC 50/60 Hz 7 VA
AKO-D14423230 Volts AC 50/60 Hz 3.75 VA

General Specifications

SpecificationDetails
Maximum Voltage SELV circuits20 V
CommunicationModbus RTU RS485
Inputs (According to P4)3 NTC/PTC inputs (Sólo AKO-D14412-RC y AKO-D14423-RC); 2 NTC/PTC inputs + 1 digitised input; 1 NTC/PTC input + 2 digitised input
Relay 2 CV(EN60730-1: 16(10) A 250 V~)
Relay 16 A(EN60730-1: 12(9) A 250 V~)
Relay 6 A(EN60730-1: 5(4) A 250 V~)
Relay 8 A(EN60730-1: 8(4) A 250 V~)
Number of relay operationsEN60730-1: 100,000 operations
Types of probeNTC AKO-149xx / PTC AKO-1558xx
Measurement range NTC-50.0 °C to +99.9 °C (-58.0 °F to 211 °F)
Measurement range PTC-50.0 °C to +150 °C (-58.0 °F to 302 °F)
Resolution (-50 to 100 °C)0.1 °C
Resolution (> 100 °C)1 °C
Working environment-10 to 50 °C, humidity <90 %
Ambient storage humidity-30 to 70 °C, humidity <90 %
Class of protection - front panelIP65
FixationPanel-mounted with anchors
Panel cutout dimensions71 x 29 mm
Front panel dimensions79 x 38 mm
Depth61 mm
ConnectionsConnections via screw terminals for cables up to 2.5 mm²
Rating of control deviceBuilt-in, automatic operation feature Type 1.B, for use in clean environments, Class A software and continuous operation. Pollution classification 2 s / UNE-EN 60730-1. Double insulation between supply, secondary circuit and relay output.
Rated pulse voltage2500 V
Temperature during ball-pressure test (Accessible parts)75 °C
Temperature during ball-pressure test (Parts which position active elements)125 °C
Voltage and current as per EMC test
    AKO-D14123-2-RC/D14423/D14423-RC/D14323-C207 V, 17 mA
    AKO-D14420105 V, 36 mA
    AKO-D14412/D14412-RC9.6 V, 181 mA
Current of radio jamming suppression tests270 mA
Models: D14412 Temperature Controller, D14412, Temperature Controller, Controller

PDF preview unavailable. Download the PDF instead.

513158ako-d14423-rc-bvm328ako-d14xxxengpdf-bvm328akod14xxxeng Corel PDF Engine Version 15.2.0.695

Related Documents

Preview AKO Thermometers and Temperature Controllers User Manual
User manual for AKO's range of thermometers and temperature controllers, detailing features, operation, wiring, and technical specifications.
Preview Manual de Usuario: Termómetros y Controladores de Temperatura AKO Darwin
Manual de usuario detallado para los termómetros y controladores de temperatura AKO de la gama Darwin. Cubre la presentación, descripción, configuración inicial, funcionamiento, conexionado, conectividad, configuración de parámetros, y especificaciones técnicas.
Preview Ako D14XXX Series Temperature Controllers: Part Numbers and Details
A comprehensive guide to Ako D14XXX series temperature controlling thermometers, detailing part numbers, specifications, applications, and programming parameters for various models.
Preview AKO D14112, D14123-2, D14212, D14223, D14312, D14323 Temperature Controller User Manual
User manual for AKO D14112, D14123-2, D14212, D14223, D14312, D14323 temperature controllers, covering installation, operation, parameter settings, and technical specifications.
Preview AKO D142H232 Digital Thermostat Installation and Operation Manual
Installation and operation instructions for the AKO D142H232 digital thermostat, covering wiring, setup, parameters, and technical specifications.
Preview AKO D141xx/D101xx & D140xx Series Temperature Controllers: Programming and Parameter Guide
Comprehensive guide to programming and understanding parameters for AKO D141xx/D101xx and D140xx series temperature controllers, detailing menu navigation, settings, and error messages.
Preview AKO D141H232 Digital Thermostat Installation and Operation Guide
This document provides installation, wiring, and operational instructions for the AKO D141H232 digital thermostat, covering its features, parameters, and technical specifications.
Preview AKO D142H232 Temperature Controller Installation Instructions
Installation instructions for the AKO D142H232 series temperature controllers, covering wiring, operation, start-up, and technical specifications. Includes a detailed parameter table.