Ako D14XXX Series Temperature Controlling Thermometers

List of Part Numbers and Details

The following table provides details for various Ako temperature controlling thermometers, including model numbers, power supply, relay configurations, communication options, and display types. Unless otherwise indicated, all devices are supplied with one 1.5-metre NTC probe. For additional probes, request parts AKO-149xx for NTC probes and AKO-1558xx for PTC probes.

MODELSPOWER SUPPLYRELAYSREMOVABLE PROBETERMINAL FORMATPROBE TYPEDIGITAL INPUTS*COMMUNICATIONRTCECO MODEFANAUXSTRIPDISPLAY
AKO-D1401212/24VNOSLIM(NTC/PTC)1NONONOSET1
AKO-D14023230VNOSLIM(NTC/PTC)1NONONOSET1
AKO-D14120110V16 ANOSLIM(NTC/PTC)3NONONOSET1
AKO-D14123230V16 ANOSLIM(NTC/PTC)3NONONOSET1
AKO-D14125230V16 AWithout probeSTANDARD(NTC/PTC)1YESNONOSET1
AKO-D14023-C90-260V 50/60Hz(NTC/PTC)1YESNONOSET1
AKO-D1411212/24V16 ANOSTANDARDUp to 2 (NTC/PTC)Up to 24NONOYESSET1
AKO-D14123-2230V2 CVNOSTANDARDUp to 2 (NTC/PTC)Up to 24NONOYESSET1
AKO-D14123-2-RC90-260V 50/60Hz2 CVYESSTANDARDUp to 2 (NTC/PTC)Up to 24YESYESYESSET1
AKO-D1421212V16 A8 ANOSTANDARDUp to 2 (NTC)Up to 24NONOYESSET1
AKO-D14220120V16 A8 ANOSTANDARDUp to 2 (NTC)Up to 24NONOYESSET1
AKO-D14223230V16 A8 ANOSTANDARDUp to 2 (NTC)Up to 24NONOYESSET13 digits with decimal point and minus sign, red display
AKO-D1431212V16 A6 A8 ANOSTANDARDUp to 2 (NTC)Up to 24NONOYESSET1
AKO-D14320120V16 A6 A8 ANOSTANDARDUp to 2 (NTC)Up to 24NONOYESSET1
AKO-D14323230V16 A6 A8 ANOSTANDARDUp to 2 (NTC)Up to 24NONOYESSET1
AKO-D14323-C90-260V 50/60Hz16 A6 A8 AYESSTANDARDUp to 2 (NTC)Up to 24YESNOYESSET1
AKO-D14412-RC12V6 A6 A6 AYESSTANDARDUp to 3 (NTC)Up to 34YESYESYESSET1
AKO-D14423-RC90-260V 50/60Hz6 A6 A6 AYESSTANDARDUp to 3 (NTC)Up to 34YESYESYESSET1
AKO-D10123230V2 CVNOEXTENDEDUp to 2 (NTC/PTC)Up to 24NONOYESSET1
AKO-D10223230V16 CV8 ANOEXTENDEDUp to 2 (NTC)Up to 24NONOYESSET1
AKO-D10323230V16 CV6 A8 ANOEXTENDEDUp to 2 (NTC)Up to 24NONOYESSET1
AKO-D1632390-260V 50/60Hz16 A6 A8 ASIEXTENDEDUp to 2 (NTC)Up to 22NONOYESSET1BIGDarwin 2 digits with decimal point and minus sign, red display

Common 230 VAC Applications

The following table outlines common applications for 230 VAC models:

CONSERVATIONFREEZINGHEAT
Static evaporator
AKO-D14123
Ventilated evaporator
AKO-D14223
Ventilated evaporator
AKO-D14323
With integrated communications
+ 2 CV relay + RTC
AKO-D14123-2-RC
With integrated communications
+ auxiliary relay
AKO-D14323-C
With integrated communications
+ auxiliary relay + RTC
AKO-D14423-RC
Static evaporator
AKO-D14223
With integrated communications
AKO-D14123-2-RC
With integrated communications
+ RTC
AKO-D14323-C

Setpoint and Programming Access

Accessing setpoint and programming functions varies by device type:

3- and 4-key devices

Setpoint Access: Display shows temperature. Press and hold SET for 5 seconds, then release to access setpoint. Press SET again to confirm.

Programming Access: Display shows temperature. Press and hold SET for 10 seconds, then release to access programming.

Key functions during programming:

1-key devices

Setpoint Access: Display shows temperature. Press and hold SET for 5 seconds, then release to access setpoint. Press SET again to confirm.

Stand-by Mode: Press and release SET for less than 5 seconds to go to Stand-by.

Programming Access: Display shows temperature. Press and hold SET for 10 seconds, then release to access programming.

Key functions during programming:

BIGDarwin

Setpoint Access: Display shows temperature. Press and hold the UP arrow (?) for 5 seconds to access setpoint. Press UP arrow (?) again to confirm.

Stand-by Mode: Press and release the DOWN arrow (?) for less than 5 seconds to go to Stand-by.

Programming Access: Display shows temperature. Press and hold the UP arrow (?) for 10 seconds, then release to access programming.

Key functions during programming:

Table of Parameters

The following tables detail various control and monitoring parameters, alarm settings, defrost controls, fan controls, and real-time clock parameters.

CONTROL AND MONITORING

ParameterDescriptionUnitsParameterDescriptionUnits
SPTemperature Adjustment (Set Point)(°C/°F)AOConfiguration of temperature alarms: 0=Relative to SP; 1=Absolute
COCalibrating probe 1 (Offset)(°C/°F)A1Maximum alarm probe 1 (must be greater than SP)(°C/°F)
C1Probe 1 differential (Histeresis)(°C/°F)A2Minimum alarm probe 1 (must be less than SP)(°C/°F)
C2Upper blocking of the Set Point (cannot be set above this value)(°C/°F)A3Temperature alarm delay during start-up(min.)
C3Lower blocking of the Set Point (cannot be set below this value)(°C/°F)A4Temperature alarm delay after completion of a defrost(min.)
C4Type of delay for protection of the compressor: 0=OFF/ON (since the last disconnection); 1=ON (since start-up/reset); 2=OFF-ON/ON-OFF (since the last shut-down/start-up)A5Temperature alarm delay after reaching the value of A1 or A2(min.)
C5Protection delay time (value of the option selected in parameter C4)(min.)A6External alarm delay when receiving digital input signal (P10 or P11=2 or 3)(min.)
C6Status of COOL relay with probe fault 0=OFF; 1=ON; 2=Average based on last 24 hours prior to probe fault; 3=ON-OFF as prog. C7 and C8 (in heat mode always OFF)A7External alarm delay when receiving digital input signal (P10 or P11=2 or 3)(min.)
C7Alarm relay polarity 0=Relay ON in alarm (OFF no alarm) 1=Relay OFF on alarm (ON with no alarm)A8Show warning if defrost is terminated by time-out 0=No, 1=Yes
C8Time relay ON in case of faulty probe (If C7=0 and C8≠0, the relay will always be OFF deenergised) Time relay OFF in case of fault of probe 1 (If C8=0 y C7≠0, the relay will always be ON energised)(min.)A9Alarm relay polarity 0=Relay ON in alarm (OFF no alarm) 1=Relay OFF on alarm (ON with no alarm)
C9Maximum duration of fast freezing mode. (0=Off)(min.)A10Temperature Alarm Differential (A1 and A2)(°C/°F)
C10Change set point (SP) in fast freezing mode, when it reaches this point (SP + C10) returns to normal. (SP+C10 ≥ C3) (0=OFF). The value of this parameter is always negative or 0.(°C/°F)A12Door open alarm delay (if P10 or P11=1)(min.)
C11Length of inactivity at digital input to activate ECO mode (Only if P10 or P11=1 and P0=0) (0=OFF)(h.)EPExit to Level 1
C12Change set point (SP) in ECO mode (SP+C12≤ C2) (0= Off)(°C/°F)
CnFSet the default parameters according to the type of application 1=Multipurpose 2=Frozen 3=Fruit and Vegetables 4=Fresh Fish 5=Soft Drinks 6=Bottle Racks 7=AC 8=Heat/Incubators
P1Delay of all functions on receiving electrical power(min.)POType of operation 0=Direct, Cold; 1=Inverted, Heat
P2Access code (password) functions 0=Inactive; 1=Block access to parameters; 2=Keyboard lockP3Access code (password) functions
P4Selection of type of inputs 1=1 probe + 2 digital inputs 2=2 probes +1 digital input 3=3 probesP5MODBUS address
P6Configuration of AUX relay 0=Fans 1=Defrost/2nd Defrost 2=Alarm 3=Light 4=Pump down 5=Master DefrostP7Temperature display mode 0=Whole in °C 1=One decimal in °C 2=Whole in °F 3=One decimal in °F
P8Probe to be displayed (as per parameter P4) 0=visualization of all the probes in sequence 1=Probe 1 2=Probe 2P9Selection of probe type 0=NTC; 1=PTC
P10Configuring digital input 1 0= Off 1=Door contact 2=External alarm 3=Severe external alarmP11Configuring digital input 2 0= Off 1=Door contact 2=External alarm 3=Severe external alarm
P12Digital input polarity 10=Energised on closed contact, 1=Energised on open contactP13Digital input polarity 20=Energised on closed contact, 1=Energised on open contact
P14Maximum start-up time after pump down(sec.)P15Maximum pump down time(sec. x10)
EPExit Level 1

DEFROST CONTROL

ParameterDescriptionUnitsParameterDescriptionUnits
d0Defrost frequency (Time between two starts)(h.)d1Maximum defrost duration (0=defrost deactivated)(min.)
d2Type of message during defrost: 0=Current temperature; 1=Temperature at start of defrost; 2=Display dEF messaged3Maximum duration of message (time added at the end of the defrost)(min.)
d4Defrost end temperature (probe 2) (If P4≠1)(°C/°F)d5Defrost on equipment start-up 0=NO, First defrost as per d0; 1=YES, First defrost as per d6
d6Defrost start delay on equipment start-up(min.)d7Defrost type: 0=Resistors 1=Inverted cycle
d8Calculated time between defrost periods: 0=Total actual time; 1 =Sum of times the compressor is ond9Drip time at end of defrost (compressor and fans off) (if P4≠1)(min.)
d101st defrost start time (RTC required)(h: min.)d112nd defrost start time (RTC required)(h: min.)
d123rd defrost start time (RTC required)(h: min.)d134th defrost start time (RTC required)(h: min.)
d145th defrost start time (RTC required)(h: min.)d156th defrost start time (RTC required)(h: min.)
EPExit Level 1

FAN CONTROL

ParameterDescriptionUnitsParameterDescriptionUnits
F0Fan shut-down temperature as per probe 2 (if P4≠ 1)(°C/°F)F1Probe 2 differential (If P4≠ 1)(°C/°F)
F2Stop fans when stopping compressor 0=No, 1=YesF3Fan status during defrost: 0=0ff; 1=On
F4Starting delay after defrost (if F3=0) Will only operate if it is higher than d9(min.)F5Stop fans on opening the door 0=No, 1=Yes (Requires a digital input configured as port P10 or P11=1)
EPExit Level 1

RTC REAL TIME CLOCK PARAMETERS

ParameterDescriptionUnitsParameterDescriptionUnits
r1Clock configuration: HOUR(h.)r2Clock configuration: MINUTES(min.)
EPExit Level 1

ACCES AND INFORMATION CONTROL

ParameterDescriptionUnitsParameterDescriptionUnits
L5Access code (Password) request.PUProgram version (Information)
PrProgram revision (Information)
EPExit Level 1

Messages

The following table lists the messages displayed by the controllers:

Display Indicators

The following indicators can be displayed:

Note: Flashing indicator lights signal that the function should be activated by temperature but is not due to a timing or protection override.

The list of parameters, messages and configurations is general. Some models may not have certain parameters or messages. Specific parameters and messages appear in the installation manual for each model.

PDF preview unavailable. Download the PDF instead.

ako-d14XXX Corel PDF Engine Version 15.0.0.486 CorelDRAW X5

Related Documents

PreviewManual de Usuario: Termómetros y Controladores de Temperatura AKO Darwin
Manual de usuario detallado para los termómetros y controladores de temperatura AKO de la gama Darwin. Cubre la presentación, descripción, configuración inicial, funcionamiento, conexionado, conectividad, configuración de parámetros, y especificaciones técnicas.
PreviewAKO Thermometers and Temperature Controllers User Manual
User manual for AKO's range of thermometers and temperature controllers, detailing features, operation, wiring, and technical specifications.
PreviewAKO D141H232 Digital Thermostat Installation and Operation Guide
This document provides installation, wiring, and operational instructions for the AKO D141H232 digital thermostat, covering its features, parameters, and technical specifications.
PreviewAKO D142H231 Installation and Operation Manual
Installation and operation instructions for AKO D142H231 temperature controllers, covering warnings, installation, connections, operation, and technical specifications.
PreviewAKO D142H232 Temperature Controller Installation Instructions
Installation instructions for the AKO D142H232 series temperature controllers, covering wiring, operation, start-up, and technical specifications. Includes a detailed parameter table.
PreviewAKO D142H232 Digital Thermostat Installation and Operation Manual
Installation and operation instructions for the AKO D142H232 digital thermostat, covering wiring, setup, parameters, and technical specifications.
PreviewAKO D144xx Series Temperature Controllers: Installation and Operation Manual
Comprehensive guide for installing, wiring, operating, and configuring AKO D144xx series temperature controllers, including detailed parameter tables and technical specifications.
PreviewAKO D141xx/D101xx & D140xx Series Temperature Controllers: Programming and Parameter Guide
Comprehensive guide to programming and understanding parameters for AKO D141xx/D101xx and D140xx series temperature controllers, detailing menu navigation, settings, and error messages.