RenewAire HE07IN EC Motor Energy Recovery Ventilator

Product Type: Energy Recovery Ventilator (ERV)

Model: HE07IN

Specifications

Ventilation Type: Static plate, heat and humidity transfer

Airflow Range: 166-694 CFM

AHRI 1060 Certified Core: One L85-G5

Standard Features:

Filters:

Unit Weight: 148-278 lbs., varies by option(s)

Max. Shipping Dimensions & Weight (on pallet): 60" L x 30" W x 55 1/4" H, 310 lbs.

Motor(s):

Options:

Accessories:

EC Motor Operating Range and Fan Performance

The document includes performance curves for the HE07IN EC Motor, showing airflow (CFM) versus external static pressure (in. w.g.) for different motor options (Standard EC, Intermediate EC, Advanced EC) at 120V and 208-230V.

HE07IN Motor 1P/120V Options

Airflow (CFM) External Static Pressure (Inches Water Column) Unit Power Consumption (Watts)
133 3.00 458
245 3.00 631
322 2.69 706
385 2.40 760
448 2.06 804
511 1.65 833
573 1.17 847
636 0.60 840
694 0.00 815

Note: Airflow performance includes effect of clean, standard filter supplied with unit.

HE07IN Motor 1P/208-230V Options

Airflow (CFM) Standard EC Intermediate EC Advanced EC
External Static Pressure (Inches Water Column) Unit Power Consumption (Watts) External Static Pressure (Inches Water Column) Unit Power Consumption (Watts) External Static Pressure (Inches Water Column) Unit Power Consumption (Watts)
133 2.32 278 2.87 439 3.00 406
196 2.14 323 2.68 499 3.00 462
285 1.76 383 2.40 580 3.00 493
322 1.55 402 2.27 610 2.85 631
385 1.08 418 1.99 656 2.55 663
448 0.48 408 1.64 690 2.18 711
488 0.00 384 1.36 706 1.90 748
573 0.59 716 1.22 766
625 0.00 705 0.74 790
694 0.00 795

Note: Airflow performance includes effect of clean, standard filter supplied with unit.

Electrical Data

Option Watts Volts Hz Phase FLA per motor Min. Cir. Amps Max. Overcurrent Protection Device
[EE] Standard 170 208-230 60 Single 1.16 2.6 15
[BB] Intermediate 357 208-230 60 Single 2.76 6.2 15
[AA] Advanced 330 208-230 60 Single 1.55 3.5 15
[AA] Advanced 357 120 60 Single 5.4 12.2 15

Dimensions and Diagrams

The document provides detailed diagrams illustrating the unit's dimensions and airflow orientation. Key views include Top, Left, Front, and Right views, with labels for various components and connections.

Airflow Orientation:

Available as shown: EA (Exhaust Air to Outside), OA (Outside Air Intake), RA (Room Air to be Exhausted), SA (Supply Air to Inside).

Unit Mounting & Application:

The unit can be mounted in any orientation. RA/EA airstream can be switched with OA/SA airstream unless certain options are selected.

Abbreviations:

Notes:

Bypass Economizer Information (HE07INV):

For models with a bypass economizer, specific installation notes are provided:

Bypass Airflow Schematic: Diagrams illustrate the airflow path with the bypass economizer, including connections for the bypass duct and face damper.

Augmented Reality (AR)

Scan the QR code to see a life-size version of the HE07IN, or view online at: https://ar.marketscale.com/renewaire/he07in

PDF preview unavailable. Download the PDF instead.

Submittal-HE07IN-EC-Motor-June2024 Adobe PDF Library 17.0

Related Documents

Preview RenewAire EV 90 Energy Recovery Ventilator Specifications and Dimensions
Detailed specifications, performance data, and dimensional drawings for the RenewAire EV 90 Energy Recovery Ventilator, an indoor unit designed for residential and light commercial applications.
Preview RenewAire CA-2XIN ERV: Air-to-Air Energy Recovery Ventilator Specification Guide
Detailed CSI specification guide for the RenewAire CA-2XIN Air-to-Air Energy Recovery Ventilator (ERV). Covers general requirements, product specifications, quality assurance, submittals, and execution for indoor or outdoor installation, adhering to industry standards like AHRI 1060 and UL 723.
Preview Ventilateurs à Récupération d'Énergie Série HE RenewAire
Découvrez les ventilateurs à récupération d'énergie (ERV) de la série HE de RenewAire, conçus pour améliorer la qualité de l'air intérieur (QAI), réduire les coûts énergétiques et favoriser des environnements sains et productifs dans les bâtiments commerciaux. Ces unités offrent une récupération totale d'énergie, des moteurs à haut rendement, et une conception flexible pour diverses applications.
Preview RenewAire CA-3XIN Air-to-Air Energy Recovery Ventilator Specifications
Comprehensive CSI specifications for the RenewAire CA-3XIN ERV, detailing product features, quality assurance, installation, and execution requirements for HVAC systems.
Preview RenewAire HE 10RT Energy Recovery Ventilator EC Motor Specifications and Dimensions
Detailed specifications, dimensions, and performance data for the RenewAire HE 10RT Energy Recovery Ventilator with EC Motor. Includes airflow ranges, static pressure, power consumption, and electrical data.
Preview RenewAire Yaskawa Variable Frequency Drives (VFDs) Supplemental Manual for Commercial Units
This supplemental manual provides essential information on the installation, operation, and parameter settings for Yaskawa Variable Frequency Drives (VFDs) factory-installed in RenewAire commercial Energy Recovery Ventilators (ERVs). It covers wiring, control principles, motor protection, and specific parameter configurations for AC induction and EC-Titanium motors.
Preview RenewAire HE 1.5XIN Energy Recovery Ventilator Specifications and Dimensions
Detailed specifications, dimensions, airflow performance, and electrical data for the RenewAire HE 1.5XIN series of Energy Recovery Ventilators (ERVs) for indoor unit applications, including standard and bypass economizer models.
Preview RenewAire LE-6XRT Air-to-Air Energy Recovery Ventilator Specification Guide
Detailed product specification guide for the RenewAire LE-6XRT Air-to-Air Energy Recovery Ventilator (ERV), covering general information, product details, and execution requirements for HVAC systems.