RenewAire HE07IN EC Motor Energy Recovery Ventilator
Product Type: Energy Recovery Ventilator (ERV)
Model: HE07IN
Specifications
Ventilation Type: Static plate, heat and humidity transfer
Airflow Range: 166-694 CFM
AHRI 1060 Certified Core: One L85-G5
Standard Features:
- Non-fused disconnect
- 24VAC transformer/relay package
- Cross-core differential pressure ports
- Independent blower control
Filters:
- Total Qty. 2, MERV 8: 14" x 20" x 2"
Unit Weight: 148-278 lbs., varies by option(s)
Max. Shipping Dimensions & Weight (on pallet): 60" L x 30" W x 55 1/4" H, 310 lbs.
Motor(s):
- Qty. 2, 170W ea., Direct drive EC motorized impeller packages (208-230V/1Ph/60Hz)
Options:
- Qty. 2, Direct drive EC motorized impeller packages: 357W 208-230V/1Ph/60Hz (Intermediate), 330W 208-230V/1Ph/60Hz (Advanced), 357W 120V/1Ph/60Hz (Advanced)
- Fused disconnect
- Integrated programmable controls: enhanced, premium
- Bypass economizer damper (see DIM drawing): dry-bulb temperature controls (standard), enthalpy controls (option)
- Class 1 low leakage motorized isolation dampers: FA, EA or both airstreams
- Factory mounted filter alarms: both airstreams
- Double wall construction
- Exterior paint: white, custom colors
Accessories:
- Filters: MERV 13, 2" (shipped loose)
- Backdraft damper: 10", 12"
- Automatic balancing damper: 4", 5", 6"
- Hooded wall vent 10", 12": galvanized, paintable galvanneal
- Louver with 10" round duct connection: 12" x 12"
- Potentiometer speed control: remote installed
- Digital time clock: wall mount (TC7D-W), in exterior enclosure (TC7D-E)
- Carbon dioxide sensor/control: wall mount (CO2-W), duct mount (CO2-D)
- IAQ sensor: wall mount (IAQ-W), duct mount (IAQ-D)
- Motion occupancy sensor/control: ceiling mount (MC-C), wall mount (MC-W)
- Smoke detector: duct mount (SD-D)
- BACnet fan control: wall mount (BACNETFC-W)
- Indoor electric duct heater: RH series (1-11.5 kW), EK series (1-175 kW)
- Indirect gas-fired duct furnace: GH series (50-400 MBH); Installed downstream of any fans
- Hanging bracket kit
- Hanging spring vibration isolation kit
- Duct flange kit: square 12" x 12", 2 flanges
EC Motor Operating Range and Fan Performance
The document includes performance curves for the HE07IN EC Motor, showing airflow (CFM) versus external static pressure (in. w.g.) for different motor options (Standard EC, Intermediate EC, Advanced EC) at 120V and 208-230V.
HE07IN Motor 1P/120V Options
Airflow (CFM) | External Static Pressure (Inches Water Column) | Unit Power Consumption (Watts) |
---|---|---|
133 | 3.00 | 458 |
245 | 3.00 | 631 |
322 | 2.69 | 706 |
385 | 2.40 | 760 |
448 | 2.06 | 804 |
511 | 1.65 | 833 |
573 | 1.17 | 847 |
636 | 0.60 | 840 |
694 | 0.00 | 815 |
Note: Airflow performance includes effect of clean, standard filter supplied with unit.
HE07IN Motor 1P/208-230V Options
Airflow (CFM) | Standard EC | Intermediate EC | Advanced EC | |||
---|---|---|---|---|---|---|
External Static Pressure (Inches Water Column) | Unit Power Consumption (Watts) | External Static Pressure (Inches Water Column) | Unit Power Consumption (Watts) | External Static Pressure (Inches Water Column) | Unit Power Consumption (Watts) | |
133 | 2.32 | 278 | 2.87 | 439 | 3.00 | 406 |
196 | 2.14 | 323 | 2.68 | 499 | 3.00 | 462 |
285 | 1.76 | 383 | 2.40 | 580 | 3.00 | 493 |
322 | 1.55 | 402 | 2.27 | 610 | 2.85 | 631 |
385 | 1.08 | 418 | 1.99 | 656 | 2.55 | 663 |
448 | 0.48 | 408 | 1.64 | 690 | 2.18 | 711 |
488 | 0.00 | 384 | 1.36 | 706 | 1.90 | 748 |
573 | 0.59 | 716 | 1.22 | 766 | ||
625 | 0.00 | 705 | 0.74 | 790 | ||
694 | 0.00 | 795 |
Note: Airflow performance includes effect of clean, standard filter supplied with unit.
Electrical Data
Option | Watts | Volts | Hz | Phase | FLA per motor | Min. Cir. Amps | Max. Overcurrent Protection Device |
---|---|---|---|---|---|---|---|
[EE] Standard | 170 | 208-230 | 60 | Single | 1.16 | 2.6 | 15 |
[BB] Intermediate | 357 | 208-230 | 60 | Single | 2.76 | 6.2 | 15 |
[AA] Advanced | 330 | 208-230 | 60 | Single | 1.55 | 3.5 | 15 |
[AA] Advanced | 357 | 120 | 60 | Single | 5.4 | 12.2 | 15 |
Dimensions and Diagrams
The document provides detailed diagrams illustrating the unit's dimensions and airflow orientation. Key views include Top, Left, Front, and Right views, with labels for various components and connections.
Airflow Orientation:
Available as shown: EA (Exhaust Air to Outside), OA (Outside Air Intake), RA (Room Air to be Exhausted), SA (Supply Air to Inside).
Unit Mounting & Application:
The unit can be mounted in any orientation. RA/EA airstream can be switched with OA/SA airstream unless certain options are selected.
Abbreviations:
- EA: Exhaust Air to Outside
- OA: Outside Air Intake
- RA: Room Air to be Exhausted
- SA: Supply Air to Inside
Notes:
- Unless otherwise specified, dimensions are rounded to the nearest eighth of an inch.
- Specifications may be subject to change without notice.
Bypass Economizer Information (HE07INV):
For models with a bypass economizer, specific installation notes are provided:
- Units with bypass will require additional space for the connection of the bypass duct (by others).
- For installation details, refer to I&O Manual Supplement for Bypass.
- Bypass damper shipped loose, field installation required.
Bypass Airflow Schematic: Diagrams illustrate the airflow path with the bypass economizer, including connections for the bypass duct and face damper.
Augmented Reality (AR)
Scan the QR code to see a life-size version of the HE07IN, or view online at: https://ar.marketscale.com/renewaire/he07in
Related Documents
![]() |
RenewAire EV 90 Energy Recovery Ventilator Specifications and Dimensions Detailed specifications, performance data, and dimensional drawings for the RenewAire EV 90 Energy Recovery Ventilator, an indoor unit designed for residential and light commercial applications. |
![]() |
RenewAire CA-2XIN ERV: Air-to-Air Energy Recovery Ventilator Specification Guide Detailed CSI specification guide for the RenewAire CA-2XIN Air-to-Air Energy Recovery Ventilator (ERV). Covers general requirements, product specifications, quality assurance, submittals, and execution for indoor or outdoor installation, adhering to industry standards like AHRI 1060 and UL 723. |
![]() |
Ventilateurs à Récupération d'Énergie Série HE RenewAire Découvrez les ventilateurs à récupération d'énergie (ERV) de la série HE de RenewAire, conçus pour améliorer la qualité de l'air intérieur (QAI), réduire les coûts énergétiques et favoriser des environnements sains et productifs dans les bâtiments commerciaux. Ces unités offrent une récupération totale d'énergie, des moteurs à haut rendement, et une conception flexible pour diverses applications. |
![]() |
RenewAire CA-3XIN Air-to-Air Energy Recovery Ventilator Specifications Comprehensive CSI specifications for the RenewAire CA-3XIN ERV, detailing product features, quality assurance, installation, and execution requirements for HVAC systems. |
![]() |
RenewAire HE 10RT Energy Recovery Ventilator EC Motor Specifications and Dimensions Detailed specifications, dimensions, and performance data for the RenewAire HE 10RT Energy Recovery Ventilator with EC Motor. Includes airflow ranges, static pressure, power consumption, and electrical data. |
![]() |
RenewAire Yaskawa Variable Frequency Drives (VFDs) Supplemental Manual for Commercial Units This supplemental manual provides essential information on the installation, operation, and parameter settings for Yaskawa Variable Frequency Drives (VFDs) factory-installed in RenewAire commercial Energy Recovery Ventilators (ERVs). It covers wiring, control principles, motor protection, and specific parameter configurations for AC induction and EC-Titanium motors. |
![]() |
RenewAire HE 1.5XIN Energy Recovery Ventilator Specifications and Dimensions Detailed specifications, dimensions, airflow performance, and electrical data for the RenewAire HE 1.5XIN series of Energy Recovery Ventilators (ERVs) for indoor unit applications, including standard and bypass economizer models. |
![]() |