Product Data Sheet: Altivar Process ATV630D11Y6

Main Specifications

AttributeValue
Range of ProductAltivar Process ATV600
Product Specific ApplicationProcess and utilities
Product or Component TypeVariable speed drive
VariantStandard version
Device short nameATV630
Mounting ModeWall mount
Communication Port ProtocolEthernet, Modbus serial, Modbus TCP
[Us] rated supply voltage500...690 V - 15...10%
Relative symmetric mains voltage tolerance10%
Relative symmetric network frequency tolerance5%
Nominal output current13.5 A
IP degree of protectionIP21 (with optional kit)
Product destinationAsynchronous motors, Synchronous motors
EMC filterIntegrated 82.02 ft (25 m) IEC 61800-3 category C3
IP degree of protectionIP00 (IEC 61800-5-1), IP00 (IEC 60529), IP20 with kit VW3A9705 (IEC 61800-5-1), IP20 with kit VW3A9705 (IEC 60529)
Type of coolingForced convection
Supply frequency50...60 Hz - 5...5%
Motor power kW7.5 kW (500 V normal duty), 5.5 kW (500 V heavy duty), 11 kW (690 V normal duty), 7.5 kW (690 V heavy duty)
Maximum Horse Power Rating10 hp (500 V normal duty), 7.5 hp (500 V heavy duty), 15 hp (690 V normal duty), 10 hp (690 V heavy duty)
Line current13.6 A (500 V normal duty), 14.7 A (690 V normal duty), 10.4 A (500 V heavy duty), 10.5 A (690 V heavy duty)
Continuous output current13.5 A (4 kHz normal duty), 9.5 A (4 kHz heavy duty)

Complementary Specifications

AttributeValue
Speed drive output frequency0.1...500 Hz
Safety functionSTO (safe torque off) SIL 3
Option cardSlot A communication module (Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen, Ethernet IP/Modbus TCP/MD-Link, BACnet MS/TP, Ethernet Powerlink), Slot A/slot B digital and analog I/O extension module, Slot A/slot B output relay extension module
Discrete input number8
Discrete input typeDI1...DI8 programmable as pulse input (0...30 kHz, 24 V DC <= 30 V)
Discrete input logic16 preset speeds, Positive logic (source), Negative logic (sink)
Discrete output number0
Discrete output typeRelay outputs R1A, R1B, R1C (250 V AC 3000 mA, 30 V DC 3000 mA), Relay outputs R2A, R2C (250 V AC 5000 mA, 30 V DC 5000 mA), Relay outputs R3A, R3C (250 V AC 5000 mA, 30 V DC 5000 mA)
Analogue input number3
Analogue input typeAl1, Al2, Al3 software-configurable voltage (0...10 V DC, -10...10 V DC) or current (0...20 mA)
Analogue output number2
Analogue output typeSoftware-configurable voltage (0...10 V DC) or current (0...20 mA), Software-configurable current DQ-, DQ+ (30 V DC, 100 mA)
Relay output number3
Relay output typeConfigurable relay logic R1 fault relay (NO/NC 100000 cycles), Configurable relay logic R2 sequence relay (NO 100000 cycles), Configurable relay logic R3 sequence relay (NO 100000 cycles)
Maximum switching current3 A (250 V AC, 30 V DC resistive, cos phi = 1), 2 A (250 V AC, 30 V DC inductive, cos phi = 0.4, 7 ms)
Minimum switching current5 mA (24 V DC)
Phase3 phase
Physical interfaceEthernet, 2-wire RS 485
Method of accessSlave Modbus TCP
Transmission Rate10, 100 Mbits
Transmission frame4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Output voltage<= power supply voltage
Permissible temporary current boost1.1 x In (60 s normal duty), 1.5 x In (60 s heavy duty)
Data format8 bits, configurable odd, even or no parity

Electrical Connection and Characteristics

AttributeValue
Type of polarizationNo impedance
Frequency resolutionDisplay unit 0.1 Hz, Analog input 0.012/50 Hz
Electrical connectionControl removable screw terminals (0.5...1.5 mm² AWG 20...AWG 16), Motor screw terminal (4...10 mm² AWG 12...AWG 8), Line side screw terminal (4...10 mm² AWG 12...AWG 8)
Connector typeRJ45 on the remote graphic terminal (Ethernet/Modbus TCP, Modbus serial)
Exchange modeHalf duplex, full duplex, autonegotiation (Ethernet/Modbus TCP)
Number of addresses1...247 (Modbus serial)
SupplyExternal supply for digital inputs (24 V DC, 19...30 V), <1.25 mA overload/short-circuit protection; Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5%, <10 mA overload/short-circuit protection; Internal supply for digital inputs and STO (24 V DC, 21...27 V), <200 mA overload/short-circuit protection
Local signalling3 LEDs for local diagnostic, 3 LEDs (dual colour) for embedded communication status, 4 LEDs (dual colour) for communication module status, 1 LED (red) for presence of voltage
Input compatibilityDI1...DI6 discrete input level 1 (PLC IEC 61131-2), DI5, DI6 discrete input level 1 (PLC IEC 65A-68), STOA, STOB discrete input level 1 (PLC IEC 61131-2)
Discrete input logicPositive logic (source) DI1...DI8 (< 5 V, > 11 V), Negative logic (sink) DI1...DI8 (> 16 V, < 10 V)
Sampling duration2 ms +/- 0.5 ms (DI1...DI4), 5 ms +/- 1 ms (DI5, DI6), 5 ms +/- 0.1 ms (Al1, Al2, Al3), 10 ms +/- 1 ms (AO1)
Accuracy+/- 0.6% (Al1, Al2, Al3) for temperature variation 60 °C, +/-1% (AO1, AO2) for temperature variation 60 °C
Linearity errorAl1, Al2, Al3 +/- 0.15% of maximum value, AO1, AO2 +/- 0.2%
Refresh timeRelay output R1, R2, R3: 5 ms +/- 0.5 ms
IsolationBetween power and control terminals
Enclosure mountingWall mounted
4 quadrant operation possibleFalse

Asynchronous Motor Control Profile

  • Optimized torque mode
  • Constant torque standard
  • Variable torque standard

Synchronous Motor Control Profile

  • Permanent magnet motor
  • Synchronous reluctance motor
AttributeValue
Maximum output frequency500 kHz
Acceleration and deceleration rampsS, U or customized, Linear adjustable separately from 0.01...9999 s
Motor slip compensationNot available in permanent magnet motor law, Automatic whatever the load, Adjustable, Can be suppressed
Switching frequency2...8 kHz adjustable, 4...8 kHz with derating factor
Nominal switching frequency4 kHz
Braking to standstillBy DC injection
Brake chopper integratedFalse

Input and Output Current

AttributeValue
Maximum Input Current per Phase14.7 A
Maximum output voltage690.0 V
Apparent power17.6 kVA (690 V normal duty), 12.5 kVA (690 V heavy duty)
Maximum transient current14.9 A (60 s normal duty), 14.3 A (60 s heavy duty)
Network Frequency50-60 Hz
Prospective line Isc70 kA
Base load current at high overload9.5 A
Base load current at low overload13.5 A
Power dissipation in WNatural convection 98 W (500 V, 4 kHz), Forced convection 198 W (500 V, 4 kHz)

Safety Functions

  • With safety function Safely Limited Speed (SLS): False
  • With safety function Safe brake management (SBC/SBT): False
  • With safety function Safe Operating Stop (SOS): False
  • With safety function Safe Position (SP): False
  • With safety function Safe programmable logic: False
  • With safety function Safe Speed Monitor (SSM): False
  • With safety function Safe Stop 1 (SS1): False
  • With sft fct Safe Stop 2 (SS2): False
  • With safety function Safe torque off (STO): True
  • With safety function Safely Limited Position (SLP): False
  • With safety function Safe Direction (SDI): False

Protection Type

  • Thermal protection motor
  • Safe torque off motor
  • Motor phase break motor
  • Thermal protection drive
  • Safe torque off drive
  • Overheating drive
  • Overcurrent between output phases and earth drive
  • Overload of output voltage drive
  • Short-circuit protection drive
  • Motor phase break drive
  • Overvoltages on the DC bus drive
  • Line supply overvoltage drive
  • Line supply undervoltage drive
  • Line supply phase loss drive
  • Overspeed drive
  • Break on the control circuit drive

Dimensions

Dimension Drawings: The document includes detailed dimension drawings for the drives. These show various views (front, side, top) with measurements in millimeters (mm) and inches (in.).

Drives Without Top Cover, With EMC Plate: Shows front, left, and rear views with specific dimensions provided.

Drives Without Top Cover, Without EMC Plate: Shows front, left, and rear views with specific dimensions provided.

Drives With IP20 Top Cover: Shows front, left, and rear views with specific dimensions provided.

AttributeValue
Quantity per Set1
Width9.7 in (246 mm)
Height16.5 in (420 mm)
Depth9.5 in (242 mm)
Net Weight48.5 lb(US) (22 kg)

Environment

AttributeValue
Insulation resistance> 1 MOhm 500 V DC for 1 minute to earth
Noise level52 dB (86/188/EEC)

Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via its ongoing "Use Better, Use Longer, Use Again" campaign to extend product lifetimes and recyclability.

Environmental footprint

  • Carbon footprint (kg CO2 eq, Total Life cycle): 4729
  • Environmental Disclosure: Product Environmental Profile available

Materials and Substances

  • Packaging made with recycled cardboard: Yes
  • Packaging without single use plastic: No
  • EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
  • SCIP Number: 075941f9-bf60-4e63-ae5c-6fe3c8035357
  • REACH Regulation: REACH Declaration
  • California proposition 65: WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Energy efficiency

  • Product contributes to saved and avoided emissions: Yes

Repack and remanufacture

  • Circularity Profile: End of Life Information
  • Take-back: No
  • WEEE: The product must be disposed of in European Union markets following specific waste collection and never end up in rubbish bins.

Mounting and Clearance

Clearances: The diagram illustrates required clearances for mounting. X1 (front/rear) must be ≥ 100 mm (3.94 in.), X2 (sides) must be ≥ 100 mm (3.94 in.), and X3 (bottom) must be ≥ 10 mm (0.39 in.).

Mounting Types:

  • Mounting Type A: Individual IP21 configuration, showing spacing 'a' between units.
  • Mounting Type B: Side by Side IP20 configuration.
  • Mounting Type C: Individual IP20 configuration.

Connections and Schema

Three-Phase Power Supply with Upstream Breaking via Line Contactor: This diagram shows the power connection with a line contactor (KM1), circuit breakers (Q2, Q3), pushbuttons (S1, S2), and a transformer (T1) for the control part. It conforms to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 per IEC/EN 60204-1.

Three-Phase Power Supply with Downstream Breaking via Contactor: Similar to the upstream breaking diagram, this shows power connection with a line contactor (KM1), circuit breakers (Q2, Q3), pushbuttons (S1, S2), and a transformer (T1), conforming to the same standards.

Control Block Wiring Diagram: This diagram illustrates the internal wiring and connections. It shows terminals for digital inputs (DI1-DI6), digital outputs (R1A, R1B, R1C for fault relay; R2A, R2C; R3A, R3C for sequence relay), analog outputs (AQ1, AQ2), analog inputs (AI1, AI2, AI3), and safety functions like STOA/STOB for Safe Torque Off. It also indicates connections for a reference potentiometer.

Sensor Connection: It is possible to connect either 1 or 3 sensors on terminals Al2 or Al3.

Sink / Source Switch Configuration

The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.

  • Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
  • Set the switch to Ext if using PLC outputs with NPN transistors.

The document shows four configurations:

  • Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs.
  • Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs.
  • Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs.
  • Switch Set to EXT Position Using an External Power Supply for the DIs.

Performance Curves

Derating Curves: This section presents derating curves that illustrate how the nominal drive current (In) is affected by switching frequency (SF) at different ambient temperatures. The curves show derating for Mounting types A, B, and C at 40°C (104°F), 50°C (122°F), and 60°C (140°F) for types B and C.

Ordering and Shipping Details

AttributeValue
CategoryUS1CP4E22276
Discount ScheduleCP4E
GTIN3606481325143
ReturnabilityYes
Country of originIN

Packing Units

AttributeValue
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height29.53 in (75.000 cm)
Package 1 Width23.62 in (60.000 cm)
Package 1 Length31.50 in (80.000 cm)
Package 1 Weight46.297 lb(US) (21.000 kg)

PDF preview unavailable. Download the PDF instead.

Generatepdf.aspx?salesorgid=78&dist=849&lang=42&form=no&documenttype=plain&productid=ATV630D11Y6 cairo 1.15.12 (http://cairographics.org)

Related Documents

Preview Schneider Electric Altivar Process ATV630 Variable Speed Drive - Product Data Sheet
Detailed technical specifications, dimensions, environmental data, and connection diagrams for the Schneider Electric Altivar Process ATV630 variable speed drive, including models ATV600, ATV630, 55kW, 75hp, 500-690V, IP00.
Preview Schneider Electric Altivar Process ATV630D18Y6 Variable Speed Drive - 18.5kW, 690V
Technical data sheet for the Schneider Electric Altivar Process ATV630D18Y6 variable speed drive, detailing specifications, features, dimensions, environmental data, and ordering information for this 18.5kW (25hp), 690V industrial AC drive.
Preview Schneider Electric Altivar Process ATV630 Variable Speed Drive - 2.2kW, 3hp, 500-690V, IP00
Detailed product data sheet for the Schneider Electric Altivar Process ATV630 variable speed drive. Includes specifications, electrical data, environmental information, dimensions, mounting types, connection diagrams, and performance curves for the ATV630U22Y6 model.
Preview Schneider Electric Altivar Process ATV630D30Y6 Variable Speed Drive Data Sheet
Detailed technical specifications and data for the Schneider Electric Altivar Process ATV630D30Y6 variable speed drive, including electrical characteristics, performance curves, dimensions, and environmental data.
Preview Schneider Electric Altivar Process ATV900 ATV930 Variable Speed Drive Data Sheet
Comprehensive data sheet for the Schneider Electric Altivar Process ATV900 series, specifically the ATV930 model with 90kW/125hp, 500-690V, IP00 rating. Details include main specifications, electrical connections, environmental data, performance curves, and mounting information.
Preview Schneider Electric Altivar Process ATV900 ATV930 Variable Speed Drive Data Sheet
Detailed technical specifications, features, and environmental data for the Schneider Electric Altivar Process ATV900 ATV930 variable speed drive, 5.5kW, 5hp, 500 to 690V, IP00.
Preview Schneider Electric Altivar Process ATV930U22Y6 Variable Speed Drive - Technical Specifications
Detailed technical specifications for the Schneider Electric Altivar Process ATV930U22Y6 variable speed drive, including electrical, mechanical, and environmental data, as well as connection diagrams and mounting information.
Preview Schneider Electric Altivar Process ATV630U55S6X Variable Speed Drive Data Sheet
Comprehensive data sheet for the Schneider Electric Altivar Process ATV630U55S6X variable speed drive, detailing specifications, features, dimensions, environmental data, and electrical connections for a 7.5hp, 600V, IP21 rated drive.