Schneider Electric RNF22R2MMW
This document provides technical specifications, functional descriptions, and setup instructions for the Schneider Electric RNF22R2MMW relay.
Product Overview and Indicators
The RNF22R2MMW is a versatile relay with multiple functions. It features several LED indicators for status monitoring.
LED Indicators
Indicator | Color | Status | Description |
---|---|---|---|
Pairing Indication | Green | Constantly ON | Connection established |
Output 2 Indication | Amber | Constantly ON | Output 2 closed |
Output 1 Indication | Amber | Constantly ON | Output 1 closed |
Power Supply Indication | Green | Constantly ON | Power supply available |
Output 1 Indication | Amber | Constantly OFF | Output 1 open |
Output 2 Indication | Amber | Constantly OFF | Output 2 open |
Power Supply Indication | Green | Constantly OFF | Power supply not available |
Output 1 Indication | Amber | Slow Blinking | Output 1 open - Timing in progress |
Output 2 Indication | Amber | Slow Blinking | Output 2 open - Timing in progress |
Output 1 Indication | Amber | Fast Blinking | Relay Output open: 15-18, 25/21-28/24 opened |
Output 2 Indication | Amber | Fast Blinking | Relay Output closed: 15-18, 25/21-28/24 closed |
Notes on Product Usage
The default function for this product is Function A (Power on-delay) with a time setting of T=3s. To utilize this product, a mobile device with Android OS v7.0 or later, or iOS v14.5 or later is required. The companion app, "Ecostruxure Industrial Device", can be downloaded from the Google Play Store or Apple Store.
Wiring and Connections
The relay can be wired using shielded cables. The terminal designations are A1, A2, Y1, R1, R2, and numbered terminals 15, 18, 16, 25/21, 26/22, 28/24.
Sensor Wiring Diagram
The diagram shows connections for power supply (A1-A2) and control input (Y1). Outputs R1 and R2 are also indicated.
Wire Sizes and Torque
Parameter | Value |
---|---|
Wire size (mm²) | 0.5 to 3.33 |
Wire size (AWG) | 20 to 12 |
Torque (N·m) | 0.6 to 1 |
Torque (lb-in) | 5.3 to 8.8 |
Wire diameter | Ø 3.5 mm / 0.14 in. |
Environmental Specifications
Parameter | Value |
---|---|
Operating Temperature | -20 °C to +60 °C (-4 °F to +140 °F) |
Functions
The RNF22R2MMW supports a wide range of functions, each detailed with timing diagrams illustrating input and output behavior. These functions include various types of delays, flashing relays, and specialized relays.
Function A: Power on-delay
Description: When power is applied to A1-A2, the output R1/R2 activates after a delay period (T). The timing period (T) is adjustable.
Function At: Power on-delay with pause / summation control
Description: Similar to Function A, but includes pause and summation control capabilities for the timing period.
Function Ac: On-delay & Off-delay with control signal
Description: This function combines on-delay and off-delay behavior controlled by an external signal on Y1.
Function Ad: Pulse delayed relay with control signal
Description: A pulse is generated with a delay upon receiving a control signal.
Function Ah: Pulse delayed relay (single cycle) with control signal
Description: A single-cycle pulse is delayed upon receiving a control signal.
Function Ak: Asymmetrical on-delay & off-delay with control signal
Description: Asymmetrical on-delay and off-delay behavior controlled by an external signal.
Function B: Interval Relay (Single Shot) With Control Signal
Description: A single-shot interval relay activated by a control signal.
Function Bw: Double Interval Relay With Control Signal
Description: A double interval relay activated by a control signal.
Function C: Off-delay relay with control signal
Description: The output deactivates after a delay when the control signal is removed.
Function D: Symmetrical flashing relay (starting pulse off)
Description: Provides symmetrical flashing output where the OFF state starts first.
Function Dt: Symmetrical flashing relay (starting pulse off) & with pause / summation control
Description: Symmetrical flashing with pause and summation control.
Function Di: Symmetrical flashing relay (starting pulse on)
Description: Provides symmetrical flashing output where the ON state starts first.
Function Dit: Symmetrical flashing relay (starting pulse on) & with pause / summation control
Description: Symmetrical flashing with pause and summation control, starting with the ON state.
Function H: Interval relay
Description: A basic interval relay function.
Function Ht: Interval relay & with pause / summation control
Description: Interval relay functionality enhanced with pause and summation control.
Function L: Asymmetrical flashing relay (starting pulse off)
Description: Asymmetrical flashing output, starting with the OFF state.
Function Lt: Asymmetrical flashing relay (starting pulse off) & with pause / summation control
Description: Asymmetrical flashing with pause and summation control, starting with the OFF state.
Function Li: Asymmetrical flashing relay (starting pulse on)
Description: Asymmetrical flashing output, starting with the ON state.
Function Lit: Asymmetrical flashing relay (starting pulse on) & with pause / summation control
Description: Asymmetrical flashing with pause and summation control, starting with the ON state.
Function N: Safe-Guard Relay
Description: A safety relay designed for protection applications.
Function O: Delayed Safe-Guard Relay
Description: A safety relay with a delayed activation.
Function P: Pulse Delayed Relay With Fixed Pulse Length
Description: A pulse relay with a delayed output and a fixed pulse duration.
Function Pt: Pulse Delayed Relay With Fixed Pulse Length & With Pause / Summation Control
Description: Combines fixed pulse length, delay, and pause/summation control.
Function Q: Star-delta relay (2 CO output with split common)
Description: A star-delta relay with two change-over outputs and a split common terminal. Diagnostic features are not available.
Function Qt: Star-delta relay (2 CO output with split common)
Description: Star-delta relay with pause/summation control. Diagnostic features are not available.
Function Qtt: Star-delta relay (2 CO output with split common) with pause / summation control
Description: Star-delta relay with two change-over outputs and a split common terminal, including pause/summation control. Diagnostic features are not available.
Function TL: Bi-Stable Relay With Control Signal ON
Description: A bi-stable relay that activates with a control signal.
Function Tt: Retriggerable Bi-Stable Relay With Control Signal ON
Description: A retriggerable bi-stable relay activated by a control signal.
Function W: Interval relay with control signal off
Description: An interval relay that operates when the control signal is OFF.
Mobile Device Setup (NFC)
To set up the relay using a mobile device:
- Ensure your mobile device has NFC enabled.
- Launch the "Ecostruxure Industrial Device" app and select the "+" button, then choose "Discovery".
- Hold your NFC-enabled phone near the device. The pairing indication LED should light up. Successful detection will display the relay settings page.
The app interface includes sections for Setting, Diagnose, and Protection.
Safety Precautions
WARNING: HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH.
- Always disconnect all power before servicing the equipment.
- Verify that the product's power supply voltage and its tolerances are compatible with the network.
- Install a fuse or circuit breaker before turning on power.
Failure to follow these instructions can result in death or serious injury.
Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. Schneider Electric is not responsible for consequences arising from the use of this material. Installation in locked cabinets is recommended for added security.
Manufacturer Information
Schneider Electric Industries SAS
35, rue Joseph Monier
CS 30323
F - 92506 Rueil-Malmaison Cedex
Manufacturing facility information is also provided.