Blue Ridge XL1 FC Ceiling & Floor Regular Series Submittal Data Sheet
Location: [Not Specified]
Approval: [Not Specified]
Engineer: [Not Specified]
Date: [Not Specified]
Submitted to: [Not Specified]
Construction: [Not Specified]
Submitted by: [Not Specified]
Unit #: [Not Specified]
Reference: [Not Specified]
Drawing #: [Not Specified]
Efficiency
Category | Metric | Value |
---|---|---|
Cooling | SEER2 | 20.0 |
EER2 | 10.1 | |
Heating | HSPF2-4 | 10.0 |
COP | 3.34 |
Performance - Cooling
Rated Capacity: 36000 Btu/hr
Min/Max Capacity: 7300 ~ 39500 Btu/hr
Moisture Removal: 3.23 L/h
Standard Operating Range: -13°F to 122°F (-25°C to 50°C)
Conditions:
- Indoor: 80°F DB / 67°F WB
- Outdoor: 95°F DB / 75°F WB
Performance - Heating
1. @ 47°F Rated: 38000 Btu/hr
1. @ 47°F Min/Max Capacity: 14100 ~ 40400 Btu/hr
2. @ 17°F Rated: 26400 Btu/hr
3. @ 5°F Rated: Capacity / COP: 26000 / 2.17
3. @ 5°F Max Capacity: 26000 Btu/hr
Standard Operating Range: -13°F to 75°F (-25°C to 24°C)
Conditions:
- 1. Indoor: 70°F DB / 60°F WB; Outdoor: 47°F DB / 43°F WB
- 2. Indoor: 70°F DB / 60°F WB; Outdoor: 17°F DB / 15°F WB
- 3. Indoor: 70°F DB / 60°F WB; Outdoor: 5°F DB / 5°F WB
Indoor Unit Specifications
Indoor Air Flow (Turbo/H/M/L/Si): 1224.3 / 1088.9 / 988.8 / 765.2 / 653.3 CFM
Indoor Noise Level (Turbo/H/M/L/Si): N/A / 49.5 / 44.5 / 37.0 / 33.0 dBA
Dimensions (W x D x H): 64.96in (1650.0mm) x 26.57in (675.0mm) x 9.25in (235.0mm)
Package Dimensions (W x D x H): 67.91in (1725mm) x 29.72in (755mm) x 12.52in (318mm)
Net/Gross Weight: 88.85 lbs (40.3 kg) / 104.94 lbs (47.6 kg)
Outdoor Unit Specifications
Compressor Type: ROTARY
Compressor Model: KTF310D43UMT
Refrigerant: R454B
Refrigerant Oil Charge: 1000 mL
Refrigerant Oil: VG74
Outdoor Air Flow (Max): 2413.3 CFM
Outdoor Noise Level: 64.0 dBA
Dimensions (W x D x H): 37.24in (946.0mm) x 16.14in (410.0mm) x 31.89in (810.0mm)
Package Dimensions (W x D x H): 42.91in (1090mm) x 19.68in (500mm) x 34.84in (885mm)
Net/Gross Weight: 152.34 lbs (69.1 kg) / 162.48 lbs (73.7 kg)
Electrical Specifications
Power Supply: 208/230V, 60Hz, 1Ph
System MCA (Min. circuit amps): 33.00 A
Connection Wiring: 14#x3
System MOCP (Max. over current protection): 35 A
Compressor RLA (Rated load amps): 21.5 A
Outdoor Fan Motor RLA: 1.4 A
Outdoor Fan Motor W (Rated output): 120 W
Indoor Fan Motor RLA: 1.0 A
Indoor Fan Motor W (Rated output): 90 W
System Power Input @ Cooling: 3529W (560 ~ 4180W)
System Power Input @ Heating: 3334W (855 ~3500W)
Piping
Throttle type (Indoor): N/A
Throttle type (Outdoor): EXV + Throttle valve
Liquid Size: 9.52mm (3/8in)
Gas Size: 19mm (3/4in)
Max. Piping Length: 246.00 ft (75 m)
Max. Height Difference: 98.40 ft (30 m)
Max. Pre-charged Length: 24.6 ft (7.5 m)
Refrigerant Pre-charged Amount: 91.71 oz (2.60 kg)
Additional Charge of Refrigerant: 0.32 oz/ft (30 g/m)
Connection Method: Flared
Indoor Unit Dimensions
The indoor unit dimensions are detailed in the provided diagrams, showing width, depth, and height for various models.
Dimensions for 18K/24K Models:
- A: 42in (1068mm)
- B: 26-1/2in (675mm)
- C: 9-1/4in (235mm)
- D: 38-3/4in (983mm)
Dimensions for 36K/48K/60K Models:
- A: 65in (1650mm)
- B: 26-1/2in (675mm)
- C: 9-1/4in (235mm)
- D: 61-5/8in (1565mm)
Diagrams illustrate:
- Top view with drain discharge port (1-1/2in / Ø40), fresh air intake (4-3/4in / Ø120), wiring connection port (1-1/8in / Ø33), and refrigerant pipe hole.
- Side views showing refrigerant pipe hole (Floor), wiring connection port (7/8in / Ø22) for US models, and fresh air intake (2in / Ø53).
- Front view with dimensions A, B, and C.
- Rear view with dimension D and hanging arm indication.
Outdoor Unit Dimensions & Installation Clearance
The outdoor unit dimensions and required installation clearances are provided in the diagrams.
Outdoor Unit Dimensions:
- Width: 37-7/8in (810mm)
- Depth: 16-1/8in (410mm)
- Height: 31-7/8in (810mm)
Installation Clearance Requirements:
- Front and sides: 20in (500mm) or more when clear.
- Left, right, and rear: 20in (500mm) or more when any 2 sides are clear.
- Top: 1.38in (35mm) or more clearance on sides.
- Rear: 14in (350mm) or more clearance.
- Minimum clearance between unit and wall: 1.38in (35mm).
- Minimum clearance from wall to unit: 1.38in (35mm).
- Overall height clearance: 38.4in (1000mm).
Diagrams show the outdoor unit from front, side, and top views, indicating dimensions and clearance requirements.
Features
- 2 Style Installation
- 3D Airflow
- Refrigerant leakage detection sensor
- Humidity sensor
- "88" display tube
- 1 ~ 100% fan speed setting
- WiFi capability (via WiFi dongle or wired controller with built-in WiFi)
- OTA (Over-The-Air) updates via WiFi dongle
- 2-pin connector (HA/HB) for programmable wired controller
- Multiple control options available:
- Two-way communication wired controller: 120N(X6)
- Two-way communication wired controller with built-in WiFi: 120N(X6W)
- Infrared wired controller: 120L
- Wireless remote controller
- Third-Party 24V Thermostat* (*24V interface is required)