Blue Ridge XL1 FC R454B Ceiling & Floor Regular System Submittal Data Sheet
General Information
Location: [Not Specified]
Engineer: [Not Specified]
Submitted to: [Not Specified]
Submitted by: [Not Specified]
Reference: [Not Specified]
Approval: [Not Specified]
Date: [Not Specified]
Construction: [Not Specified]
Unit #: [Not Specified]
Drawing #: [Not Specified]
Logos include AR CERTIFIED and Intertek.
Product image shows an indoor unit and an outdoor unit.
Efficiency
Cooling | Heating | |
---|---|---|
SEER2 | 19.5 | HSPF2-4 |
EER2 | 9.5 | COP |
3.05 |
Performance of Cooling
Cooling (Btu/hr):
- Rated Capacity: 54000
- Min/Max Capacity: 15000~54500
- Moisture Removal (L/h): 7.48
- Standard Operating Range (°F/°C): -13~122 (-25~50)
- Conditions: Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB
Performance of Heating
Heating (Btu/hr):
- 1. @ 47°F Rated: 60000
- 1. @ 47°F Min/Max Capacity: 20200~60000
- 2. @ 17°F Rated: 37200
- 3. @ 5°F Rated: Capacity / COP: 35000 / 2.01
- 3. @ 5°F Max: Capacity: 35000
- Standard Operating Range (°F/°C): -13~75 (-25~24)
- 1. Conditions: Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB
- 2. Conditions: Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB
- 3. Conditions: Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB
Indoor Specifications
Specification | Value |
---|---|
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 1365.6 / 1236.1 / 1118.3 / 882.9 / 777.0 |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | N/A / 54.5 / 49.5 / 41.5 / 38.5 |
Dimension (W×D×H) (inch) | 64.96 x 26.57 x 9.25 |
Dimension (W×D×H) (mm) | 1650.0×675.0×235.0 |
Package (W×D×H) (inch) | 67.91 x 29.72 x 12.52 |
Package (W×D×H) (mm) | 1725×755×318 |
Net/Gross Weight (lbs) | 95.24 / 111.33 |
Net/Gross Weight (kg) | 43.2 / 50.5 |
Outdoor Specifications
Specification | Value |
---|---|
Compressor Type | ROTARY |
Compressor Model | KTQ420D1UMU |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 1400 |
Refrigerant Oil | VG74 |
Outdoor Air Flow (Max) (CFM) | 4237.9 |
Outdoor Noise Level (dBA) | 63.5 |
Dimension (W×D×H) (inch) | 37.48 x 16.34 x 52.48 |
Dimension (W×D×H) (mm) | 952.0×415.0×1333.0 |
Package (W×D×H) (inch) | 43.11 x 19.49 x 58.27 |
Package (W×D×H) (mm) | 1095×495×1480 |
Net/Gross Weight (lbs) | 209.44 / 240.08 |
Net/Gross Weight (kg) | 95 / 108.9 |
Electrical
Specification | Value |
---|---|
Power Supply | 208/230V, 60Hz, 1Ph |
System MCA | 42.00 |
Connection Wiring | 14#x3 |
System MOCP | 45 |
Compressor RLA | 25.0 |
Outdoor Fan Motor RLA | 2.2 |
Outdoor Fan Motor W | 85 |
Indoor Fan Motor RLA | 2.0 |
Indoor Fan Motor W | 160 |
System Power Input @ Cooling (W) | 5625 (1400 ~ 6050) |
System Power Input @ Heating (W) | 5765 (1150 ~ 5765) |
Piping
Specification | Value |
---|---|
Throttle type (Indoor) | N/A |
Throttle type (Outdoor) | EXV + Throttle valve |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 246.00 (75) |
Max. Height Difference (ft/m) | 98.40 (30) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg) | 144.62 (4.10) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.32 (30) |
Connection Method | Flared |
Indoor Unit Dimensions
Indoor Unit Dimension Diagram: Illustrates the indoor unit's side and front views, indicating dimensions A, B, C, D, and connection ports. Key connections include a 1-1/8in (33mm) wiring port, a 1-1/2in (40mm) drain discharge port, and 4-3/4in (120mm) fresh air intake. A refrigerant pipe hole is shown on the floor, along with a wiring connection port (US models). The unit features a hanging arm.
Model | A | B | C | D |
---|---|---|---|---|
18K/24K | 42in (1068mm) | 26-1/2in (675mm) | 9-1/4in (235mm) | 38-3/4in (983mm) |
36K/48K/60K | 65in (1650mm) | 26-1/2in (675mm) | 9-1/4in (235mm) | 61-5/8in (1565mm) |
Installation Instructions & Outdoor Unit Dimensions
Indoor Unit Installation Clearance: Diagram shows minimum clearances required around the indoor unit: ≥ 1.38 inches (35mm) on the sides and ≥ 38.4 inches (1000mm) above.
Outdoor Unit Dimension Diagram: Provides detailed front, side, and top views of the outdoor unit, with dimensions labeled A, B, C, and D. Detail A highlights piping connection points.
Outdoor Unit Required Clearance
Outdoor Unit Required Clearance Diagram: Depicts the outdoor unit on a base, with arrows indicating necessary clearances. Specifications: *1 20 inches (500mm) or more for front and sides when clear. 4 inches (100mm) or more on sides. 14 inches (350mm) or more on one side. *2 20 inches (500mm) or more when any two sides (left, right, and rear) are clear.
Features
- 2 Style Installation
- 3D Airflow
- Refrigerant leakage detection sensor
- Humidity sensor
- "88" display tube
- 1~100% fan speed setting
- WiFi capability: through WiFi dongle or wired controller with built-in WiFi
- OTA (by using WiFi dongle)
- 2-pin connector (HA/HB) for programmable wired controller
- Multiple control options available:
- Two way communication wired controller: 120N(X6)
- Two way communication wired controller with built-in WiFi: 120N(X6W)
- Infrared wired controller: 120L
- Wireless remote controller
- Third-Party 24V Thermostat* (*24V interface is required.)