P-SERIES SUBMITTAL DATA

Job Name: [Not Specified]

System Reference: [Not Specified]

Date: [Not Specified]

Product: Mitsubishi Electric PKA-A12HA7 & PUY-A12NKA7(-BS) - 12,000 BTU/H Wall-Mounted Air-Conditioning System

Indoor Unit Features

  • Sleek, compact design
  • Simple installation
  • Vane setting for air flow direction control
  • Auto fan speed mode
  • Ideal for spaces such as server rooms, daycare centers, classrooms, churches, small offices, and more

Outdoor Unit Features

  • Variable speed INVERTER-driven compressor
  • Power receiver pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30)
  • Low ambient cooling down to -40°F providing 100% capacity (only for PUY models with wind baffles installed)
  • 24-hour continuous operation (cooling mode)
  • High pressure protection
  • Fast restarts in cooling mode (15 seconds for 12/18/36/42; 50 seconds for 24/30)
  • Superior energy and operational efficiency

Specifications

Indoor Unit

FeatureValue
Maximum Capacity12,000 BTU/H
Rated Capacity12,000 BTU/H
Minimum Capacity5,800 BTU/H
Maximum Power Input1,000 W
Rated Power Input1,000 W
Moisture Removal2.0 Pints/h
Sensible Heat Factor0.81
Power Factor94.5 %
SEER20.8
EER12.0
Voltage, Phase, Frequency208/230V, 1-phase, 60 Hz
Guaranteed Voltage Range198-253 V AC
Voltage: Indoor - Outdoor, S1-S2208/230 V AC
Voltage: Indoor - Outdoor, S2-S324 V DC
Short-circuit Current Rating (SCCR)12 kA
Recommended Fuse/Breaker Size (Outdoor)15 A
Recommended Wire Size (Indoor - Outdoor)14 AWG
MCA1 A
Fan Motor Full Load Amperage0.33 A
Fan Motor Output30 W
Airflow Rate, Dry320-370-425 CFM
Airflow Rate, Wet290-335-380 CFM
External Static Pressuren/a in.WG
Sound Pressure Level36-40-43 dB(A)
Drain Pipe Size5/8 (16) in. (mm)
Condensate Lift Mechanism, Max. Distancen/a in. (mm)
Heat Exchanger TypePlate fin coil
External Finish ColorWhite Munsell 1.0Y 9.2/0.2
Unit Dimensions (W x D x H)35-3/8 (898) x 9-13/16 (249) x 11-5/8 (295) in. (mm)
Package Dimensions (W x D x H)39-6/16 x 15-12/16 x 13-6/16 in.
Unit Weight29 (13) Lbs. (kg)
Package Weight33 Lbs.
Cooling Intake Air Temp (Max / Minimum)90°F DB / 66°F DB, 73°F WB / 59°F WB
MCA (Outdoor Unit)11 A
MOCP (Outdoor Unit)28 A
Fan Motor Full Load Amperage (Outdoor Unit)0.50 A

Outdoor Unit

FeatureValue
Fan Motor Output46 W
Airflow Rate1,590 CFM
Refrigerant ControlElectronic Expansion Valve
Heat Exchanger TypeCross fin
Sound Pressure Level, Cooling44 dB(A)
Compressor TypeINVERTER-driven twin rotary
Compressor ModelSNB092FNCM
Compressor Rated Load Amps7 A
Compressor Locked Rotor Amps12 A
Compressor Oil Type // ChargeFV50S // 12 oz.
External Finish ColorIvory Munsell 3Y 7.8/1.1
Base Pan Heatern/a
Unit Dimensions (W x D x H)31-13/16 + 7/16 (809+62) x 11-3/16 (300) x 24-13/16 (630) in. (mm)
Package Dimensions (W x D x H)37-1/16 x 16-3/16 x 27-7/16 in.
Unit Weight92 (41) Lbs. (kg)
Package Weight104 (47) Lbs. (kg)
Cooling Intake Air Temp (Maximum / Minimum)115°F DB / -40°F DB
Refrigerant TypeR410A
Refrigerant Charge4 lbs, 7 oz
Gas Pipe Size O.D. (Flared)1/2 (12.7) in.(mm)
Liquid Pipe Size O.D. (Flared)1/4 (6.35) in.(mm)
Maximum Piping Length165 (50) Ft. (m)
Maximum Height Difference100 (30) Ft. (m)
Maximum Number of Bends15

Key Notes

  • AHRI Rated Conditions (Cooling): Indoor: 80°F DB, 67°F WB; Outdoor: 95°F DB, 75°F WB.
  • Low Ambient Operation: Wind baffles are required for operation below 23°F DB in cooling mode. For PUY models, wind baffles can extend the cooling operation range to -40°F.
  • System Protection: The system may cut out in heating mode to prevent thermistor errors and will automatically restart.
  • Seacoast Protection: Features include Phosphate coating + Acrylic-Enamel coating on the external outer panel, Epoxy resin coating on the fan motor support and separator assembly/valve bed, and "Blue Fin" treatment on the condenser coil for enhanced corrosion resistance.

Available Accessories

A comprehensive range of accessories is available for the PKA-A12HA7 indoor unit and PUY-A12NKA7(-BS) outdoor unit, including various remote controllers, sensors, condensate pumps, mounting brackets, and piping kits. Specific part numbers are listed in the original documentation.

Dimensions and Clearances

Indoor Unit (PKA-A12HA7)

Unit Dimensions: Width: 35-3/8 inches (898 mm), Depth: 9-13/16 inches (249 mm), Height: 11-5/8 inches (295 mm).

Package Dimensions: Width: 39-6/16 inches, Depth: 15-12/16 inches, Height: 13-6/16 inches.

Required Space: Specific clearances are indicated in diagrams for air inlet and outlet, as well as piping access. For example, minimum air inlet clearance is 1-31/32 inches (50 mm) and minimum air outlet clearance is 8-5/8 inches (220 mm).

Outdoor Unit (PUY-A12NKA7(-BS))

Unit Dimensions: Width: 809 mm (31-7/8 inches), Depth: 300 mm (11-13/16 inches), Height: 630 mm (24-13/16 inches).

Installation Clearances: The unit requires free space around it for proper operation. Generally, 100mm (3-15/16 inches) or more is recommended on the rear and sides if there are no obstacles. Piping and wiring connections are made from the rear.

Foundation: The unit must be secured firmly with 4 foundation bolts (M10, W 3/8). Recommended foundation bolt height is a minimum of 100mm (3-15/16 inches).

PDF preview unavailable. Download the PDF instead.

PKA-A12HA7 PUY-A12NKA7 AH XSL Formatter V6.6 R1 for Linux64 : 6.6.1.34539 (2018/08/29 13:12JST) Antenna House PDF Output Library 6.6.1307 (Linux64)

Related Documents

Preview Mitsubishi Electric PLA-A12EA7 & PUY-A12NKA7(-BS) Ceiling Cassette Air Conditioner Specifications
Detailed specifications and features for the Mitsubishi Electric PLA-A12EA7 3'x3' Ceiling Cassette Indoor Unit and PUY-A12NKA7(-BS) Outdoor Unit, a 12,000 BTU/H cooling-only system.
Preview Mitsubishi P-Series PKA-A24KA7 & PUY-A24NHA7(-BS) Air Conditioning System Specifications
Detailed submittal data and specifications for the Mitsubishi P-Series PKA-A24KA7 indoor unit and PUY-A24NHA7(-BS) outdoor unit, a 24,000 BTU/H wall-mounted air conditioning system.
Preview Mitsubishi Electric P-Series PKA-A18HA7 & PUY-A18NKA7 Submittal Data Sheet
Comprehensive submittal data sheet for the Mitsubishi Electric P-Series PKA-A18HA7 indoor unit and PUY-A18NKA7 outdoor unit. This document details technical specifications, electrical requirements, operating ranges, efficiency ratings, refrigerant information, and precise dimensions for an 18,000 BTU/h wall-mounted air-conditioning system.
Preview Mitsubishi Electric PEAD-A18AA9 & PUY-A18NKA7: Mid Static Ducted Air Conditioner Specifications
Explore the technical specifications, features, and dimensions of the Mitsubishi Electric PEAD-A18AA9 indoor unit and PUY-A18NKA7 outdoor unit. This 18,000 BTU/H cooling-only system offers a mid static horizontal-ducted design with advanced features like seacoast protection and inverter technology.
Preview Mitsubishi Electric P-SERIES PLA-A24EA7 & PUY-A24NHA7 Ceiling Cassette Air Conditioning System Specifications and Submittal Data
Comprehensive submittal data, features, specifications, and accessories for the Mitsubishi Electric P-SERIES PLA-A24EA7 indoor unit and PUY-A24NHA7 outdoor unit, a 24,000 BTU/H ceiling cassette air conditioning system. Includes technical details and installation information.
Preview Mitsubishi Electric PKA-A30KA8 Indoor Unit & PUY-A30NHA7 Outdoor Unit: Specifications and Dimensions
Comprehensive technical specifications, features, accessories, and dimensional data for the Mitsubishi Electric PKA-A30KA8 wall-mounted indoor unit and PUY-A30NHA7 cooling-only outdoor unit, designed for efficient climate control in various spaces.
Preview Mitsubishi Electric P-Series PLA-A42EA7 & PUY-A42NKA7 Ceiling Cassette Air Conditioner Submittal Data
Detailed submittal data for the Mitsubishi Electric P-Series 42,000 BTU/H Ceiling Cassette Air Conditioning System, including indoor unit (PLA-A42EA7) and outdoor unit (PUY-A42NKA7/-BS) features, specifications, and accessories.
Preview Mitsubishi P-Series PKA-A36KA7 & PUZ-A36NKA7 Heat Pump System Submittal Data
Detailed submittal data, specifications, features, and dimensions for the Mitsubishi Electric P-Series PKA-A36KA7 indoor unit and PUZ-A36NKA7/(-BS) outdoor unit, a 36,000 BTU/h wall-mounted heat pump system.