SUBMITTAL DATA: PKA-A36KA7 & PUZ-A36NKA7(-BS)

https://genscocustomer.com/docs/PKA-A36KA7 PUZ-A36NKA7-BS Product Data Sheet-en

Puz A36nka7 Installation Manual

Mitsubishi PKZ-A36NHA Submittal

Mitsubishi PUZ-A36NKA7 PKA-A36KA7 - 36k BTU Cooling Heating - P-Series Wall Mounted Air Conditioning System - 18.8 SEER

Mitsubishi PKZ-A36NHA - 36k BTU Cooling Heating - P-Series Wall Mounted Air Conditioning System - 18.8 SEER

PDF preview unavailable. Download the PDF instead.

mitsubishi-07ac77dda1c6ed78c9fec855ba3cef5f
P-SERIES
Job Name: System Reference:

SUBMITTAL DATA: PKA-A36KA7 & PUZ-A36NKA7(-BS)
36,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM
Date:

Indoor Unit: PKA-A36KA7

Outdoor Unit:  PUZ-A36NKA7  PUZ-A36NKA7-BS

INDOOR UNIT FEATURES · Sleek, compact design · Simple installation · Vane setting for air flow direction control · Auto fan speed mode · Ideal for spaces such as server rooms, daycare centers, classrooms, churches, small offices, and more
OUTDOOR UNIT FEATURES · Variable speed INVERTER-driven compressor · Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30) · 24-hour continuous operation (cooling mode) · High pressure protection · Fast restart due to bypass valve make it ideal for equipment cooling applications, such as data centers · Superior energy and operational efficiency

Specifications are subject to change without notice.

© 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PKA-A36KA7 & PUZ-A36NKA7(-BS)

Model Number Cooling1 Heating at 47°F2 Heating at 17°F3 Efficiency Electrical
Indoor Unit

Indoor Unit
Outdoor Unit
Maximum Capacity Rated Capacity Minimum Capacity Maximum Power Input Rated Power Input Moisture Removal Sensible Heat Factor Power Factor Maximum Capacity Rated Capacity Minimum Capacity Maximum Power Input Rated Power Input Power Factor Maximum Capacity Rated Capacity Maximum Power Input Rated Power Input SEER EER *1 HSPF (IV) COP at 47°F2 COP at 17°F3 Voltage, Phase, Frequency Guaranteed Voltage Range Voltage: Indoor - Outdoor, S1-S2 Voltage: Indoor - Outdoor, S2-S3 Voltage: Indoor - Remote controller Recommended Fuse/Breaker Size Recommended Wire Size (Indoor - Outdoor) MCA Fan Motor Full Load Amperage Fan Motor Output Airflow Rate, Dry Airflow Rate, Wet External Static Pressure Sound Pressure Level Drain Pipe Size

Btu/h Btu/h Btu/h
W W Pints/h
% Btu/h Btu/h Btu/h
W W % Btu/h Btu/h W W
V AC V AC V DC V DC
A AWG
A A W CFM CFM in.WG dB(A) In. (mm)

PKA-A36KA7 PUZ-A36NKA7 PUZ-A36NKA7-BS
36,000 36,000 16,000 3,330 3,330
9.70 0.70 96.50 40,000 38,000 18,200 3,700 2,460 95.50 25,900 22,400 2,670 2,610 18.80 10.80 9.20 4.52 2.51 208 / 230V, 1-phase, 60 Hz 198 ­ 253 208 / 230 24 12 30 14 1.00 0.57 56 705-810-920 635-730-830 n/a 43-46-49 5/8 (16)

Specifications are subject to change without notice.

© 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PKA-A36KA7 & PUZ-A36NKA7(-BS)

Model Number

Indoor Unit
Outdoor Unit
Condensate Lift Mechanism, Max. Distance Heat Exchanger Type External Finish Color

Unit Dimensions

Package Dimensions

Indoor Unit Operating Temperature Range
Outdoor Unit

Unit Weight Package Weight Cooling Intake Air Temp (Maximum / Minimum) Heating Intake Air Temp (Maximum / Minimum) MCA MOCP Fan Motor Full Load Amperage Fan Motor Output Airflow Rate Refrigerant Control Defrost Method Heat Exchanger Type Sound Pressure Level, Cooling1 Sound Pressure Level, Heating2 Compressor Type Compressor Model Compressor Rated Load Amps Compressor Locked Rotor Amps Compressor Oil Type // Charge External Finish Color Base Pan Heater

Unit Dimensions

Package Dimensions
Unit Weight Package Weight

Ft. (m)
W: In. (mm) D: In. (mm) H: In. (mm)
W: In. D: In. H: In. Lbs. (kg) Lbs.
°F °F A A A W CFM
dB(A) dB(A)
A A oz.
W: In. (mm) D: In. (mm) H: In. (mm)
W: In. D: In. H: In. Lbs. (kg) Lbs. (kg)

PKA-A36KA7 PUZ-A36NKA7 PUZ-A36NKA7-BS
n/a Plate fin coil White Munsell 1.0Y 9.2/0.2 46-1/16 (1170) 11-5/8 (295) 14-3/8 (365)
51 18-8/16 14-4/16 46 (21)
53 90 DB, 73 WB / 66 DB, 59 WB
82 DB / 50 DB 25 31
0.5 + 0.5 74 + 74 3,880 Electronic Expansion Valve Reverse Cycle Cross fin
52 53 INVERTER-driven twin rotary MNB33FBRMC-L 8 13 FV50S // 45 Ivory Munsell 3Y 7.8/1.1 n/a 1050 [41-5/16] 330 + 30 [13+1-3/16] 1338 [52-11/16] 42-15/16 17-11/16 56-4/16 214 (97) 245 (111)

Specifications are subject to change without notice.

© 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PKA-A36KA7 & PUZ-A36NKA7(-BS)

Model Number

Indoor Unit Outdoor Unit

Outdoor Unit Operating Temperature Range

Cooling Intake Air Temp (Maximum / Minimum) Heating Intake Air Temp (Maximum / Minimum) Thermal Lock-out / Re-start Temperatures**

Refrigerant

Type Charge

Gas Pipe Size O.D. (Flared)

Liquid Pipe Size O.D. (Flared)

Piping

Maximum Piping Length

Maximum Height Difference

Maximum Number of Bends

°F °F °F
Lbs, oz In.(mm) In.(mm) Ft. (m) Ft. (m)

PKA-A36KA7 PUZ-A36NKA7 PUZ-A36NKA7-BS 115 DB / 0* DB 70 DB, 59 WB / -4 DB, -4 WB
-8 / -4 DB R410A
10 lbs, 6 oz 5/8 (15.88) 3/8 (9.52)
165 (50) 100 (30)
15

Notes

AHRI Rated Conditions (Rated data is determined at a fixed compressor speed)

1Cooling (Indoor // Outdoor) 2Heating at 47°F (Indoor // Outdoor) 3Heating at 17°F (Indoor // Outdoor)

°F

80 DB, 67 WB // 95 DB, 75 WB

°F

70 DB, 60 WB // 47 DB, 43 WB

°F

70 DB, 60 WB // 17 DB, 15 WB

Conditions

4Heating at 5°F (Indoor // Outdoor)

°F

70 DB, 60 WB // -4 DB, -5 WB

*Wind baffles required to operate below 23°F DB in cooling mode. PUZ with wind baffle: 0°F - 115°F. **System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

SEACOAST PROTECTION · External Outer Panel: Phosphate coating + Acrylic-Enamel coating · Fan Motor Support: Epoxy resin coating (at edge face) · Separator Assembly; Valve Bed: Epoxy resin coating (at edge face) · "Blue Fin" treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants.

Specifications are subject to change without notice.

© 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

ACCESSORIES: PKA-A36KA7

Signal Receiver Wireless Remote Controller Wireless Remote Receiver Backlit, Wall-mounted, Wireless Controller Portable Central Controller Wired MA Controller Simple MA Controller Touch MA Controller Wired Remote Sensor Lockdown Bracket for Wireless, Hand-held, Remote Controller Wireless Temperature and Humidity Sensor Outside Air Sensor for MHK1 Flush Mount Remote Temperature Sensor Wireless Interface Thermostat Interface kumo station® USNAP Interface IT Extender BACnet® and Modbus Interface Connector for CN32 (remote on/off) External Drain Pump External Drain Pump Blue Diamond Sensor Extension Cable--15 Ft. Mini Condensate Pump--230V application MegaBlue Advanced Blue Diamond Condensate Pump w/ Reservoir & Sensor MaxiBlue Advanced Blue Diamond Mini Condensate Pump w/ Reservoir & Sensor (208/230V) up to 48,000 Btu/h [recommended] Drain Pan Level Sensor (Control for indoor unit shut off to prevent drain pan overflow) 3 Pole Disconnect Switch (30A/600VUL) [fits 2"X4" utility] - Black 3 Pole Disconnect Switch (30A/600VUL) [fits 2"X4" utility] - White

 PAR-SA9CA-E  PAR-FL32MA-E  PAR-FA32MA-E  MHK1  MCCH1  PAR-33MAA  PAC-YT53CRAU  PAR-CT01MAU-SB  PAC-SE41TS-E  RCMKP1CB  PAC-USWHS003-TH-1  MOS1  PAC-USSEN001-FM-1  PAC-USWHS002-WF-1  PAC-US444CN-1  PAC-WHS01HC-E  PAC-WHS01UP-E  PAC-WHS01IE-E  PAC-UKPRC001-CN-1  PAC-SE55RA-E  PAC-KE07DM-E  PAC-SH94DM-E  C13-103  SI30-230  X87-835 - 110 to 250V  X87-721 - 208/230V
 DPLS2  TAZ-MS303  TAZ-MS303W

Specifications are subject to change without notice.

© 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

ACCESSORIES: PUZ-A36NKA7(-BS)
Twinning Distribution Pipe (50:50) Air Outlet Guide
Front Wind Baffle
Drain Socket M-NET Converter M-NET Converter Control/Service Tool Condensing Unit Mounting Pad 24" x 42" x 3" Outdoor Unit Stand--12" High Outdoor Unit Stand--18" High Outdoor Unit Stand--24"High Heavy Duty Wall Mounting Bracket for Outdoor Units--Coated Steel Heavy Duty Wall Mounting Bracket for Outdoor Units--316 Series Stainless Steel 3/8" x 5/8" x 10' / 1/2" Lineset (Twin-Tube Insulation) 3/8" x 5/8" x 15' / 1/2" Lineset (Twin-Tube Insulation) 3/8" x 5/8" x 30' / 1/2" Lineset (Twin-Tube Insulation) 3/8" x 5/8" x 50' / 1/2" Lineset (Twin-Tube Insulation) 3/8" x 5/8" x 65' / 1/2" Lineset (Twin-Tube Insulation) 3/8" x 5/8" x 100' / 1/2" Lineset (Twin-Tube Insulation)

 MSDD-50TR-E  PAC-SH96SG-E (two pieces are required)  WB-PA3 (two pieces are required)  PAC-SG61DS-E  PAC-SF83MA-E  PAC-SJ95MA-E  PAC-SK52ST  ULTRILITE2  QSMS1202M  QSMS1802M  QSMS2402M  QSWB2000M-1  QSWBSS  MPLS385812T-10  MPLS385812T-15  MPLS385812T-30  MPLS385812T-50  MPLS385812T-65  MPLS385812T-100

Specifications are subject to change without notice.

© 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

DIMENSIONS: PKA-A36KA7 & PUZ-A36NKA7 (-BS)
6 OUTLINES AND DIMENSIONS
PKA-A36KA7

16-11/16(423.7)

Top side

17(431.7)

Unit: inch (mm)

2-9/16(65.2)

5-17/32(140.3)

7/16(11)

Knockout hole for left piping

Left side

2-29/32(74) A

2-3/32(53) 1-1/4(32) 23/32(18)

1-3/16(30) 1-3/8(35) 2-19/32(66)

14-3/8(365)

Front side

Right side Mount board

33-21/32(855) 46-1/16(1170)
Front side(Grille open)

Filter hook
Drain hose 3

17-15/32(444)Gas pipe 18-31/32(482)Liquid pipe
Under side

C

9-1/2(241)
2 1

11-5/8(295)

3/16(5)

Operation lamp

Knockout hole for right piping

DEFROST/STAND BY lamp Receiver

Terminal block for Outdoor unit Terminal block for power supply (option) Terminal block for MA-remote controller Emergency operation switch (cooling/heating)

4-27/32(123) 6-1/16(154) 5-9/32(134)

Min.9/32(7)

Vane(auto) B

Sleeve (purchased locally)
[2-15/16 ([75)

Through hole [2-15/16~[3-5/32 ([75~[80)

Required space(Indoor unit)

Louver(manual) Knockout hole for lower piping
Air inlet

Min.8-21/32(220) Min.2-1/16(52.3)

Air outlet Min.3-31/32(100.5)
Center measurement hole [3/32([2.5)

Piping connection

B

1 Liquid pipe Refrigerant pipe: 3/8 O.D([9.52) Flared connection: 3/8F

2 Gas pipe

Refrigerant pipe: 5/8 O.D([15.88) Flared connection: 5/8F

3 Drain hose 5/8([16) O.D Effective length: 23-1/32 (585)

Knockout hole for piping

C

B

A

5/16(7.8) 3-1/32(77) 2-5/8(67)

2-9/16(65)

3-1/32(77) 3-7/16(87)
13/32(10.7)

2-9/16(65)

0 2-1/8(54) 1/8(3)
Min.9-27/32(250) Min.1-7/8(48) 2-5/8(67) 3-1/32(77)
5/16(7.8) 2-9/16(65)

23-1/32(585) 20-7/8(530.5) 16-15/16(430.5)
15-1/8(384) 13-11/32(339)
7-7/16(189) 0
8-17/32(216.5) 13-11/32(339) 13-3/4(349.2)
15-1/8(384) 17-11/16(449.2)
23-1/32(585)

20-3/8(517.4) 17-7/8(454) 17-9/32(439) 16-3/32(408.5) 15-1/8(384) 14-11/32(364) 12-3/8(314)

4-[11/32([9) Bolt hole
75-[3/16([5.1) Tapping screw hole
5/8(15.5) 0
31/32(25) 1-31/32(50) 2-15/16(75) 3-15/16(100) 4-19/32(117) 4-29/32(125) 5-19/32(142) 7-9/16(192) 9-17/32(242)
11(279.5) 11-1/2(292)

Mount board

R1-15/32(R37.5)

Knockout hole for rear piping

Wall hole for right rear piping

4-11/32(110) 2-3/8(60) 13/32(10) 0 13/32(10) 2-3/8(60) 4-11/32(110) 12-3/8(314) 14-11/32(364) 15-1/8(384.5) 16-3/32(408.5) 17-9/32(439) 17-7/8(454) 18-5/16(465.5)

Indoor unit outline
2-1/8(54) 1-1/4(32) 31/32(25) 1/2(12.5) 0 1/2(12.5) 1-15/32(37.5) 2-15/32(62.5) 3-7/16(87.5) 4-1/8(104.5)
5-3/32(129.5)
6-9/16(167) 8-17/32(217) 9-1/32(229.5) 10-13/32(264) 11-1/2(292)
12-5/32(308.5) 12-1/4(311)

Specifications are subject to change without notice.

© 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

PUZ-A36NKA7 PUZ-A36NKA7-BS

OCH636

PUZ-A42NKA7 PUZ-A42NKA7-BS

DIMENSIONS: PKA-A36KA7 & PUZ-A36NKA7 (-BS)

PUZ-A36NKA7(-BS)

FREE

1 FREE SPACE (Around the unit)
The diagram below shows a basic example. Explantion of particular details are given in the installation manuals etc.

2 SERVICE SPACE
Dimensions of space needed for service access are shown in the below diagram.

Min. 150 <5-29/32>

3 FOUNDATION BOLTS
Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts and washers must be purchased locally.)

4 PIPING-WIRING DIRECTIONS
Piping and wiring connections can be made from 4 directions: FRONT, Right, Rear and Below.

<Foundation bolt height>

Side Air Intake

Unit: mm<in>

Rear Air Intake

225 <8-27/32>

600 <23-5/8> Installation Feet

225 <8-27/32>

2-U Shaped notched holes (Foundation Bolt M10<W3/8>)

19 <3/4>

370 <14-9/16> 417 <16-13/32>

330 <13>

Min. 15mm <3/5>

Min. 15mm <3/5>

Min. 1000mm <39-3/8>

Min. 150mm <5-29/32>

Min. 15 <3/5>

Service space

Min.

Min.

500

50

<19-11/16> <2>

Min. 500 <19-11/16>

Max. 30 <1-3/16>

FOUNDATION

Rear Air Intake

Side Air Intake

25 <31/32>

Air Discharge

70 <2-3/4>

2-12×36 Oval holes (Foundation Bolt M10<W3/8>)

60 <2-3/8>

362 <14-1/4>

1050 <41-11/32> Earth terminal

40<1-9/16>

56 <2-7/32> 0
53 <2-3/32> 42 <1-21/32>
( ) LRTeeigfrtmh.t.i.n..Pa. lIoncwdoeonronsre/uOcptuipotlndyowoirriwngiring

28 <1-3/32>

Example of Notes
1 ... Refrigerant GAS pipe connection (FLARE) ø15.88(5/8F) 2 ... Refrigerant LIQUID pipe connection (FLARE) ø9.52(3/8F) *1 ... Indication of STOP VALVE connection location.
Handle for moving

Handle for moving

Hmaonvdinleg for

1338 <52-11/16> 632 <24-7/8>

Service panel Handle for moving

21

Air intake

*1 442 <17-2/5> *1 450 <17-23/32>
1063 <41-7/8>

369 <14-17/32> 26 <1-1/32>

Piping Knockout Hole Details

73 <2-7/8>

60 <2-3/8> Conduit hole (ø 37<1-15/32>knockout) Front trunking hole (Knockout)
<3ø-59/28>

55 <2-3/16>

55 <2-3/16>

53 <2-3/32>

Conduit hole (ø 24<15/16>knockout)

Right piping hole (Knockout)

27 <1-1/16> 92
<3-5/8>

26 <1-1/32>

26 <1-1/32>

Front piping hole (Knockout)

75 <2-15/16> 92 <3-5/8>

27 <1-1/16>

55 <2-3/16> 29 <1-5/32> 92 <3-5/8>

60 <2-3/8> Conduit hole (ø 24<15/16>knockout)
Conduit hole (ø 37<1-15/32>knockout)

55 <2-3/16> Rear trunking hole (Knockout)

<3ø-59/82>
Right trunking hole (Knockout)

73 <2-7/8> 26 <1-1/32> 27 <1-1/16>

5 <3/16> 61 <2-3/8> 73 <2-7/8> 60 <2-3/8> 5 <3/16> 55 <2-3/16>

<5-11/32> <6-1/16>

60 <2-3/8> Conduit hole (ø 24<15/16>knockout)
Conduit hole (ø 37<1-15/32>knockout)

When installing the conduit. Set the attachment to the inner side of each panel.

60 <2-3/8>
ø 27.8<1-3/32> ø 22.2<7/8>

22.5 <7/8> 3/4 Conduit attachment

154

136

<3ø-952/8>

92 <3-5/8> 75 <2-15/16>

Rear piping hole (Knockout)

1/2 Conduit attachment

100 <3-15/16>

Scale 1:5

5 <3/16> 24.7 <31/32>

45 <1-25/32> 110 <14-11/32>

160

160

160

<6-5/16> <6-5/16> <6-5/16>

81 <3-3/16>
Drain hole (5-ø33<1-5/16>)

86 <3-3/8>

Front piping cover Rear piping cover
Bottom piping hole (Knockout)

PUY-A36NKA7 PUY-A36NKA7-BS

16

PUY-A42NKA7 PUY-A42NKA7-BS

FORM# PKA-A36KA7 / PUZ-A30NKA7(-BS) - 201810
Specifications are subject to change without notice.

1340 Satellite Boulevard, Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com
© 2018 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.


AH XSL Formatter V6.6 R1 for Linux64 : 6.6.1.34539 (2018/08/29 13:12JST) Antenna House PDF Output Library 6.6.1307 (Linux64)