Indoor Unit Features
- Space-efficient ductless installation
- Equipped with 3D i-see Sensor® for enhanced comfort and energy efficiency
- Airflow settings for high and low ceiling applications
- Individual vane settings for direct/indirect airflow control or variable airflow patterns
- Knockouts for outside-air intake and branch-duct run
- Filter indicator signal
- Easy-to-clean, washable filter (optional high-efficiency filter available - requires multi-function casement)
- Built-in condensate lift mechanism
- Ideal for retail shops, classrooms, office spaces, conference centers, building lobbies, and more
Indoor Unit Dimensions & Installation Notes: The indoor unit (PLA-A42EA7) has approximate dimensions of 33-1/16" (840 mm) width, 33-1/16" (840 mm) depth, and 11-3/4" (298 mm) height. Installation requires adequate ceiling space, including clearance above the unit (e.g., a minimum of 1/4" or 7mm between the unit top and ceiling slab). Suspension bolts (M10 or W3/8) have a pitch of approximately 5-11/16 inches. The drain pipe should be VP-25 (1-1/4" O.D.) PVC tube, with a maximum condensate lift of 33-7/16" (850mm) from the ceiling. Proper insulation of branch ducts is recommended to prevent condensation. The electrical box is accessible for service purposes.
Outdoor Unit Features
- Variable speed INVERTER-driven compressor
- Power receiver pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30)
- Low ambient cooling down to -40°F providing 100% capacity (only for PUY models with wind baffles installed)
- 24-hour continuous operation (cooling mode)
- High pressure protection
- Fast restarts in cooling mode (15 seconds for 12/18/36/42; 50 seconds for 24/30)
- Superior energy and operational efficiency
Outdoor Unit Dimensions & Installation Notes: The outdoor unit (PUY-A42NKA7/-BS) requires specific free space around it for proper airflow and maintenance, as well as dedicated service access space (minimum 150mm or approx. 6 inches on sides and rear). The unit must be secured with M10 or W3/8 foundation bolts. Piping and wiring connections can be made from four directions: front, right, rear, and below. Key pipe sizes are Gas Pipe O.D. 5/8" (15.88 mm) and Liquid Pipe O.D. 3/8" (9.52 mm). Knockout holes are provided for conduit connections, with specific sizes noted for different pipe and wiring access points.
Specifications
Indoor Unit Specifications (PLA-A42EA7)
Parameter | Unit | Value |
---|---|---|
Maximum Capacity | BTU/H | 42,000 |
Rated Capacity | BTU/H | 42,000 |
Minimum Capacity | BTU/H | 16,000 |
Maximum Power Input | W | 3,590 |
Rated Power Input | W | 3,590 |
Moisture Removal | Pints/h | 7.9 |
Sensible Heat Factor | 0.79 | |
Power Factor | % | 94.6 |
SEER | 21.0 | |
EER¹ | 11.6 | |
Voltage, Phase, Frequency | 208/230V, 1-phase, 60 Hz | |
Guaranteed Voltage Range | V AC | 198 - 253 |
Voltage: Indoor - Outdoor, S1-S2 | V AC | 208/230 |
Voltage: Indoor - Outdoor, S2-S3 | V DC | 24 |
Short-circuit Current Rating (SCCR) | kA | 12 |
Recommended Fuse/Breaker Size (Outdoor) | A | 30 |
Recommended Wire Size (Indoor - Outdoor) | AWG | 14 |
MCA | A | 2.00 |
Fan Motor Full Load Amperage | A | 0.95 |
Fan Motor Output | W | 120 |
Airflow Rate, Dry | CFM | 740-920-1060-1200 |
Airflow Rate, Wet | CFM | 700-880-1020-1160 |
External Static Pressure | in.WG | n/a |
Sound Pressure Level | dB(A) | 34-38-42-45 |
Drain Pipe Size | In. (mm) | 1-1/4 (32) |
Condensate Lift Mechanism, Max. Distance | In. | 33-7/16 |
Heat Exchanger Type | Plate fin coil | |
External Finish Color | White Munsell 6.4Y 8.9/0.4 | |
Unit Dimensions // Grille Dimensions | W: In. (mm) D: In. (mm) H: In. (mm) | 33-1/16 (840) // 37-13/32 (950) 33-1/16 (840) // 37-13/32 (950) 11-3/4 (298) // 1-9/16 (40) |
Package Dimensions // Grille Dimensions | W: In. (mm) D: In. (mm) H: In. (mm) | 35-9/16 // 39-6/16 34-5/16 // 38-3/16 16-9/16 // 4-12/16 |
Unit Weight // Grille Weight | Lbs. (kg) | 56 (25) // 11 (5) |
Package Weight | Lbs. (kg) | 77 (35) |
Indoor Unit Operating Temperature Range (Cooling Intake Air Temp Max / Min) | °F | 90 DB, 73 WB / 66 DB, 59 WB |
Outdoor Unit Specifications (PUY-A42NKA7/-BS)
Parameter | Unit | Value |
---|---|---|
Fan Motor Output | W | 74 + 74 |
Airflow Rate | CFM | 3,880 |
Refrigerant Control | Electronic Expansion Valve | |
Heat Exchanger Type | Cross fin | |
Sound Pressure Level, Cooling¹ | dB(A) | 52 |
Compressor Type | INVERTER-driven twin rotary | |
Compressor Model | MNB33FBRMC-L | |
Compressor Rated Load Amps | A | 8 |
Compressor Locked Rotor Amps | A | 13 |
Compressor Oil Type // Charge | oz. | FV50S // 45 |
External Finish Color | Ivory Munsell 3Y 7.8/1.1 | |
Base Pan Heater | n/a | |
Unit Dimensions | W: In. (mm) D: In. (mm) H: In. (mm) | 41-5/16 (1050) 13+1-3/16 (330 + 30) 52-11/16 (1338) |
Package Dimensions | W: In. (mm) D: In. (mm) H: In. (mm) | 42-15/16 17-11/16 56-4/16 |
Unit Weight | Lbs. (kg) | 211 (96) |
Package Weight | Lbs. (kg) | 243 (110) |
Outdoor Unit Operating Temperature Range (Cooling Intake Air Temp Max / Min) | °F | 115 DB / -40* DB |
Refrigerant Type | R410A | |
Refrigerant Charge | Lbs, oz | 10 lbs, 6 oz |
Gas Pipe Size O.D. (Flared) | In.(mm) | 5/8 (15.88) |
Liquid Pipe Size O.D. (Flared) | In.(mm) | 3/8 (9.52) |
Maximum Piping Length | Ft. (m) | 225 (69) |
Maximum Height Difference | Ft. (m) | 100 (30) |
Maximum Number of Bends | 15 | |
Notes: AHRI Rated Conditions (Rated data is determined at a fixed compressor speed) Cooling (Indoor // Outdoor) | °F | 80 DB, 67 WB // 95 DB, 75 WB |
*Wind baffles required to operate below 23°F DB in cooling mode. For PUY models, wind baffles can be utilized to extend the cooling operation range to -40F. Please refer to the wind baffle submittals to determine which baffles are required to meet the desired operation range. | ||
**System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures. | ||
SEACOAST PROTECTION: External Outer Panel: Phosphate coating + Acrylic-Enamel coating; Fan Motor Support: Epoxy resin coating (at edge face); Separator Assembly; Valve Bed: Epoxy resin coating (at edge face); "Blue Fin" treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants. |
Accessories
Accessories for PLA-A42EA7
- High-efficiency Filter Element: PAC-SH59KF-E
- Wireless Remote Receiver: PAR-FA32MA-W
- Wireless Remote Receiver: PAR-FA32MA-E
- Signal Receiver: PAR-SR3LA-E
- kumo touch™ RedLINK™ Wireless Controller: MHK2
- Deluxe MA Remote Controller: PAR-40MAAU
- Simple MA Controller: PAC-YT53CRAU-J
- Touch MA Controller: PAR-CT01MAU-SB
- Wired Remote Sensor: PAC-SE41TS-E
- Lockdown Bracket for Wireless, Hand-held, Remote Controller: RCMKP1CB
- Wireless Temperature and Humidity Sensor: PAC-USWHS003-TH-1
- Flush Mount Remote Temperature Sensor: PAC-USSEN001-FM-1
- Wireless Interface 2: PAC-USWHS002-WF-2
- Thermostat Interface: PAC-US444CN-1
- kumo station®: PAC-WHS01HC-E
- USNAP Interface: PAC-WHS01UP-E
- IT Extender: PAC-WHS01IE-E
- BACnet® and MODBUS® Interface: PAC-UKPRC001-CN-1
- External Fan / Heater Control Relay Adapter: CN24RELAY-KIT-CM3
- Connector for CN32 (remote on/off): PAC-SE55RA-E
- Remote Operation Adapter (with wire terminals for remote ON/OFF and operation status/ error)¹: PAC-SF40RM-E
- Grille (required): PLP-40EAEU
- Multi-Function Casement: PAC-SJ41TM-E
- Installation/Trim Panels: PLFY-ITP1
- Space Panel: PAC-SJ38AS-E
- Air Outlet Shutter Plate: PAC-SJ37SP-E
- Blue Diamond Sensor Extension Cable--15 Ft.: C13-103
- MegaBlue Advanced Blue Diamond Condensate Pump w/ Reservoir & Sensor: X87-835 - 110 to 250V
- MaxiBlue Advanced Blue Diamond Mini Condensate Pump w/ Reservoir & Sensor (208/230V) up to 48,000 BTU/H [recommended]: X87-721 - 208/230V
- 3 Pole Disconnect Switch (30A/600VUL) [fits 2"X4" utility] - Black: TAZ-MS303
- 3 Pole Disconnect Switch (30A/600VUL) [fits 2"X4" utility] - White: TAZ-MS303W
Accessories for PUY-A42NKA7(-BS)
- Air Outlet Guide: PAC-SH96SG-E (two pieces are required)
- Front Wind Baffle: WB-PA3 (two pieces are required)
- Side Advanced Wind Baffle: WB-SD6
- Rear Advanced Wind Baffle: WB-RE6
- Drain Socket: PAC-SG61DS-E
- M-NET Converter: PAC-SJ85MA-E
- M-NET Converter: PAC-SJ95MA-E
- Control/Service Tool: PAC-SK52ST
- Condensing Unit Mounting Pad 24" x 42" x 3": ULTRILITE2
- Outdoor Unit Stand--12" High: QSMS1202M
- Outdoor Unit Stand--18" High: QSMS1802M
- Outdoor Unit Stand--24"High: QSMS2402M
- Heavy Duty Wall Mounting Bracket for Outdoor Units--Coated Steel: QSWB2000M-1
- Heavy Duty Wall Mounting Bracket for Outdoor Units--316 Series Stainless Steel: QSWBSS
- 3/8" x 5/8" x 10' / 1/2" Lineset (Twin-Tube Insulation): MPLS385812T-10
- 3/8" x 5/8" x 15' / 1/2" Lineset (Twin-Tube Insulation): MPLS385812T-15
- 3/8" x 5/8" x 30' / 1/2" Lineset (Twin-Tube Insulation): MPLS385812T-30
- 3/8" x 5/8" x 50' / 1/2" Lineset (Twin-Tube Insulation): MPLS385812T-50
- 3/8" x 5/8" x 65' / 1/2" Lineset (Twin-Tube Insulation): MPLS385812T-65
- 3/8" x 5/8" x 100' / 1/2" Lineset (Twin-Tube Insulation): MPLS385812T-100