Datasheet for MITSUBISHI ELECTRIC models including: PKA-A30KA8 Wall Mounted Indoor Unit Btu Cooling Only Outdoor, PKA-A30KA8, Wall Mounted Indoor Unit Btu Cooling Only Outdoor, Indoor Unit Btu Cooling Only Outdoor, Unit Btu Cooling Only Outdoor, Cooling Only Outdoor


File Info : application/pdf, 7 Pages, 3.06MB

PDF preview unavailable. Download the PDF instead.

A SUBMITTAL PKA-A30KA8 PUY-A30NHA7 en M1
PKA-A30KA8 & PUY-A30NHA7
30,000 BTU/H WALL-MOUNTED INDOOR UNIT 30,000 BTU/H COOLING ONLY OUTDOOR
Job Name: System Reference:

Indoor Unit Outdoor Unit

Date:

PKA-A30KA8 PUY-A30NHA7

INDOOR UNIT FEATURES · Sleek, compact design · Simple installation · Vane setting for air flow direction control · Auto fan speed mode · Ideal for spaces such as server rooms, daycare centers, classrooms, churches, small offices, and more · Multiple control options available:  kumo cloud® smart device app for remote access  Third-party interface options  Wired or wireless controllers
OUTDOOR UNIT FEATURES · Variable speed INVERTER-driven compressor · Pre-charged with refrigerant volume for piping length up to 70 ft · Low ambient cooling down to -40°F providing 100% capacity (with wind baffles) · 24-hour continuous operation (cooling mode) · High pressure protection · Fast restart · Superior energy and operational efficiency · Seacoast protection*  External Outer Panel: Phosphate coating + Acrylic-Enamel coating  Fan Motor Support: Epoxy resin coating (at edge face)  Separator Assembly Valve Bed: Epoxy resin coating (at edge face)  Blue Fin treatment is an anti-corrosion treatment that is applied to the Heat exchanger coil to protect it against airborne contaminants.  Heat exchanger coil and base panel rated for 2,000 hours in accordance with ASTM B117 testing *Seacoast protection standard from 2022 production

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PKA-A30KA8 & PUY-A30NHA7

test
Cooling at 95°F1 Efficiency Electrical
Indoor Unit
Indoor Unit Operating Temperature Range
Outdoor Unit
Outdoor Unit Operating Temperature Range

Maximum Capacity Rated Capacity Minimum Capacity Maximum Power Input Rated Power Input Moisture Removal Sensible Heat Factor Power Factor [208V / 230V] SEER2 EER21 HSPF2 [IV] Voltage, Phase, Frequency Guaranteed Voltage Range Voltage: Indoor - Outdoor, S1-S2 Voltage: Indoor - Outdoor, S2-S3 Short-circuit Current Rating [SCCR] Recommended Fuse/Breaker Size (Oudoor) Recommended Wire Size [Indoor - Outdoor] Power Supply MCA Fan Motor Full Load Amperage Fan Motor Output Fan Motor Type Airflow Rate at Cooling, Dry Airflow Rate at Cooling, Wet Airflow Rate at Heating, Dry Sound Pressure Level [Cooling] Sound Pressure Level [Heating] Drain Pipe Size Coating on Heat Exchanger External Finish Color Unit Dimensions Package Dimensions Unit Weight Package Weight
Cooling Intake Air Temp [Maximum / Minimum]*
MCA MOCP Fan Motor Full Load Amperage Fan Motor Output Airflow Rate [Cooling / Heating] Refrigerant Control Defrost Method Coating on Heat Exchanger Sound Pressure Level, Cooling1 Compressor Type Compressor Model Compressor Rated Load Amps Compressor Locked Rotor Amps Compressor Oil [Type // Charge] External Finish Color Base Pan Heater Unit Dimensions Package Dimensions Unit Weight Package Weight
Cooling Air Temp [Maximum / Minimum]*

BTU/H BTU/H BTU/H
W W Pints/h
%
V AC V AC V DC
kA A AWG
A A W
CFM CFM CFM dB[A] dB[A] In. [mm]
W x D x H: In. [mm] W x D x H: In. [mm]
Lbs. [kg] Lbs. [kg]
°F A A A W CFM
dB(A)
A A oz.
W x D x H: In. [mm] W x D x H: In. [mm]
Lbs. [kg] Lbs. [kg]
°F

30,000 30,000 9,000 3,150 3,150
8.1 0.70 96.4 / 96.4 20.0 9.5 --
208/230, 1, 60 198 - 253 208/230 24 5 25 14
Indoor unit is powered by the outdoor unit 1.0 0.265 69
DC Motor 635­705­775 635­705­775 635­705­775
39­42­45 39­42­45
5/8 [16] --
White Munsell 1.0Y 9.2/0.2 46-1/16 x 11-5/8 x 14-3/8 [1,170 x 295 x 365] 51-3/16 x 14-11/64 x 18-1/2 [1,300 x 360 x 470]
46 [21] 51 [23.2]
90 DB, 73 WB / 66 DB, 59 WB
19.0 26 0.4 86 1940 LEV Reverse Cycle Blue Fin Coating*** 47 INVERTER-driven twin rotary SNB172FWHM1 7 11.0 FV50S // 23 Ivory Munsell 3Y 7.8/1.1 N/A 37-13/32 x 13 (+1-3/16) x 37-1/8 [950 x 330 (+30) x 943] 40-15/16 x 17-11/16 x 40-11/16 [1040 x 450 x 1033] 151 [68] 176 [80]
115 DB / -40 DB

NOTES: AHRI Rated Conditions

1Cooling (Indoor // Outdoor)

°F 80 DB, 67 WB // 95 DB, 75 WB

Select high sensible versus high latent capacity mode via function setting mode 08, "Fan speed" (accessible through Touch MA, Deluxe MA, kumo touch and kumo cloud app control options): · "High ceiling" mode = high sensible capacity » Mode 08, setting 3 (factory default) ·"Standard" mode = high latent capacity » Mode 08, setting 2

*Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): · Wind baffles required to operate below 23°F DB in cooling mode. · Heat pump system with wind baffle: 0°F - 115°F. · Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): · System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

***Blue Fin Coating Standard from 2022 production: · PU(Y/Z)-A(12/18)NKA7 - Beginning with serial number 12U***** · PU(Y/Z)-A(24/30/36/42)NKA7 - Beginning with serial number 1ZU*****

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

SPECIFICATIONS: PKA-A30KA8 & PUY-A30NHA7

test
Refrigerant
Piping

Type Pre-Charged Refrigerant Amount Maximum Pre-Charged Piping Length Additional Refrigerant Charge Per Additional Piping Length Gas Pipe Size O.D. [Flared] Liquid Pipe Size O.D. [Flared] Maximum Piping Length Maximum Height Difference Maximum Number of Bends

Lbs, oz Ft. [m] oz./Ft. [g/m] In.[mm] In.[mm] Ft. [m] Ft. [m]

R410A 7.0, 11.0 70.0 [20.0] 0.3 [22.5] 5/8 [15.88] 3/8 [9.52] 225 [68] 100 [30]
15

NOTES: AHRI Rated Conditions

1Cooling (Indoor // Outdoor)

°F 80 DB, 67 WB // 95 DB, 75 WB

Select high sensible versus high latent capacity mode via function setting mode 08, "Fan speed" (accessible through Touch MA, Deluxe MA, kumo touch and kumo cloud app control options): · "High ceiling" mode = high sensible capacity » Mode 08, setting 3 (factory default) ·"Standard" mode = high latent capacity » Mode 08, setting 2

*Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]): · Wind baffles required to operate below 23°F DB in cooling mode. · Heat pump system with wind baffle: 0°F - 115°F. · Refer to wind baffle documentation for further information.

**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures): · System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

***Blue Fin Coating Standard from 2022 production: · PU(Y/Z)-A(12/18)NKA7 - Beginning with serial number 12U***** · PU(Y/Z)-A(24/30/36/42)NKA7 - Beginning with serial number 1ZU*****

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

INDOOR UNIT ACCESSORIES: PKA-A30KA8

Control Interface
Remote Sensor Wired Remote Controller Wireless Remote Controller Condensate Disconnect Switch Lineset Mini-Split Wire

3-Pin Connector IT Extender kumo station® for kumo cloud® Procon BACnet® and Modbus® Interface Thermostat Interface USNAP Adapter Wireless Interface for kumo cloud® Flush Mount Remote Temperature Sensor Flush Mount Temperature Sensor Remote Temperature Sensor Wireless temperature and humidity sensor for kumo cloud® Deluxe Wired MA Remote Controller Simple Ductless Wired Remote Controller Simple MA Remote Controller Touch MA Controller kumo touchTM RedLINKTM Wireless Controller Lockdown bracket for remote controller Wireless MA Receiver Wireless MA Remote Controller Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended] Blue Diamond (MegaBlue Advanced) Condensate Pump w/ Reservoir & Sensor Drain Pan Level Sensor/Control Refco Condensate Pump (100-240 VAC) Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H (30A/600V/UL) [fits 2" X 4" utility box] - Black 10' x 3/8" x 10' x 5/8" Lineset (Twin-Tube Insulation) 100' x 3/8" x 100' x 5/8" Lineset (Twin-Tube Insulation) 15' x 3/8" x 15' x 5/8" Lineset (Twin-Tube Insulation) 30' x 3/8" x 30' x 5/8" Lineset (Twin-Tube Insulation) 50' x 3/8" x 50' x 5/8" Lineset (Twin-Tube Insulation) 65' x 3/8" x 65' x 5/8" Lineset (Twin-Tube Insulation) 14 Gauge, 4 wire MiniSplit Cable--250 ft. roll 14 Gauge, 4 wire MiniSplit Cable--50 ft. roll 16 Gauge, 4 wire MiniSplit Cable--250 ft. roll 16 Gauge, 4 wire MiniSplit Cable--50 ft. roll

 PAC-715AD  PAC-WHS01IE-E  TAC-WHS01HC-E  PAC-UKPRC001-CN-1  PAC-US445CN-1  PAC-WHS01UP-E  PAC-USWHS002-WF-2  PAC-USSEN002-FM-1  PAC-USSEN001-FM-1  PAC-SE41TS-E  PAC-USWHS003-TH-1  AAR-40MAAU  PAC-SDW01RC-1  PAC-YT53CRAU-J  PAR-CT01MAU-SB  MHK2  RCMKP1CB  PAR-SR32MA-E  PAR-FL32MA-E  X87-721  X87-835  SS610E  GOBI-II  COMBI  TAZ-MS303  MPLS385812T-10  MPLS385812T-100  MPLS385812T-15  MPLS385812T-30  MPLS385812T-50  MPLS385812T-65  SW144-250  SW144-50  SW164-250  SW164-50

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

Air Outlet Guide Centralized Drain Pan Control/Service Tool Hail Guards M-NET Converter
Mini-Split Wire Mounting Pad
Stand
Wind Baffle

OUTDOOR UNIT ACCESSORIES: PUY-A30NHA7
Air Outlet Guide (1 Piece) Centralized Drain Pan Drain Pan Control/Service Tool M- & P-Series Maintenance Tool Cable Set USB/UART Conversion Cable (Required for all laptop connection) Hail Guard M-NET Converter M-NET Converter 14 Gauge, 4 wire MiniSplit Cable--250 ft. roll 14 Gauge, 4 wire MiniSplit Cable--50 ft. roll 16 Gauge, 4 wire MiniSplit Cable--250 ft. roll 16 Gauge, 4 wire MiniSplit Cable--50 ft. roll Condensing Unit Mounting Pad: 24" x 42" x 3" 18" Single Fan Stand 24" Single Fan Stand Condenser Wall Bracket Condenser Wall Bracket - Stainless Steel Finish Outdoor Unit Stand -- 12" High Front Wind Baffle Rear Wind Baffle Side Advanced Wind Baffle

 PAC-SG59SG-E  PAC-SG63DP-E  PAC-SG64DP-E  PAC-SK52ST  M21EC0397  M21EC1397  HG-A6  PAC-SJ85MA-E  PAC-SJ95MA-E  S144-250  S144-50  S164-250  S164-50  ULTRILITE2  QSMS1801M  QSMS2401M  QSWB2000M-1  QSWBSS  QSMS1201M  WB-PA5  WB-RE5  WB-SD5

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

INDOOR UNIT DIMENSIONS: PKA-A30KA8

16-11/16(423.7)

Top side

17(431.7)

Unit: inch (mm)

2-9/16(65.2)

5-17/32(140.3)

7/16(11)

2-3/32(53) 1-1/4(32) 23/32(18)

Left side
Knockout hole for left piping
2-29/32(74) A
1-3/16(30) 1-3/8(35) 2-19/32(66)

14-3/8(365)

Front side

Right side Mount board

33-21/32(855) 46-1/16(1170)
Front side(Grille open)

Filter hook
Drain hose 3

17-15/32(444)Gas pipe 18-31/32(482)Liquid pipe
Under side

C

9-1/2(241)
2 1

11-5/8(295)

3/16(5)

Operation lamp

Knockout hole for right piping

DEFROST/STAND BY lamp Receiver

Terminal block for Outdoor unit Terminal block for power supply (option) Terminal block for MA-remote controller Emergency operation switch (cooling/heating)

4-27/32(123) 6-1/16(154) 5-9/32(134)

Min.9/32(7)

Vane(auto) B

Sleeve (purchased locally)
[ 2-15/16 ([ 75)

Through hole
[ 2-15/16~[ 3-5/32 ([ 75~[ 80)

Required space(Indoor unit)

Louver(manual) Knockout hole for lower piping
Air inlet

Min.8-21/32(220) Min.2-1/16(52.3)

Air outlet Min.3-31/32(100.5)
Center measurement hole [ 3/32([ 2.5)

Piping connection

B

1 Liquid pipe Refrigerant pipe: 3/8 O.D([ 9.52) Flared connection: 3/8F

Refrigerant pipe: 5/8 O.D([ 15.88) 2 Gas pipe Flared connection: 5/8F

3 Drain hose 5/8([ 16) O.D Effective length: 23-1/32 (585)

Knockout hole for piping

C

B

A

5/16(7.8) 3-1/32(77) 2-5/8(67)

2-9/16(65)

3-1/32(77) 3-7/16(87)
13/32(10.7)

2-9/16(65)

0 2-1/8(54) 1/8(3)
Min.9-27/32(250) Min.1-7/8(48) 2-5/8(67) 3-1/32(77)
5/16(7.8) 2-9/16(65)

23-1/32(585) 20-7/8(530.5) 16-15/16(430.5)
15-1/8(384) 13-11/32(339)
7-7/16(189) 0
8-17/32(216.5) 13-11/32(339) 13-3/4(349.2)
15-1/8(384) 17-11/16(449.2)
23-1/32(585)

20-3/8(517.4) 17-7/8(454) 17-9/32(439) 16-3/32(408.5) 15-1/8(384) 14-11/32(364) 12-3/8(314)

4-[ 11/32([ 9) Bolt hole
75-[ 3/16([ 5.1) Tapping screw hole
5/8(15.5) 0
31/32(25) 1-31/32(50) 2-15/16(75) 3-15/16(100) 4-19/32(117) 4-29/32(125) 5-19/32(142) 7-9/16(192) 9-17/32(242)
11(279.5) 11-1/2(292)

Mount board

R1-15/32(R37.5)

Knockout hole for rear piping

Wall hole for right rear piping

4-11/32(110) 2-3/8(60) 13/32(10) 0 13/32(10) 2-3/8(60) 4-11/32(110) 12-3/8(314) 14-11/32(364) 15-1/8(384.5) 16-3/32(408.5) 17-9/32(439) 17-7/8(454) 18-5/16(465.5)

Indoor unit outline
2-1/8(54) 1-1/4(32) 31/32(25) 1/2(12.5) 0 1/2(12.5) 1-15/32(37.5) 2-15/32(62.5) 3-7/16(87.5) 4-1/8(104.5)
5-3/32(129.5)
6-9/16(167) 8-17/32(217) 9-1/32(229.5) 10-13/32(264)
11-1/2(292)
12-5/32(308.5) 12-1/4(311)

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.

OUTDOOR UNIT DIMENSIONS: PUY-A30NHA7

FREE
Min. 500 <19-11/16>
Min. 100 <3-15/16> Max. 30 <1-3/16>

1 FREE SPACE (Around the unit)
The diagram below shows a basic example. Explantion of particular details are given in the installation manuals etc.

2 SERVICE SPACE
Dimensions of space needed for service access are shown in the below diagram.

Min. 10mm <3/8> Min. 500mm <19-11/16>

Min. 10mm <3/8>
Min.100mm <3-15/16>

Min. 10 <13>
Service space Min. 500 <19-11/16>

Example of Notes

Handle for moving

1 ... Refrigerant GAS pipe connection (FLARE) ø15.88(5/8F) 2 ... Refrigerant LIQUID pipe connection (FLARE) ø 9.52(3/8F) *1... Indication of STOP VALVE connection location.
Air Intake

3 FOUNDATION BOLTS

4 PIPING-WIRING DIRECTIONS

Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts and washers must be purchased locally.)

Piping and wiring connections can be made from 4 directions: FRONT,Right,Rear and Below.

<Foundation bolt height>

175 <6-7/8>
Side Air Intake

Rear Air Intake
600<23-5/8> Installation Feet

2-U Shaped notched holes (Foundfation Bolt M10<W3/8>) 175<6-7/8>

19 <3/4> 370<14-9/16> 417 <1-1/32>

330 <13>

FOUNDATION
Rear Air Intake Handle for moving

28<1-3/32>

25 <31/32>

Air Discharge

70 <2-3/4> 57<2-1/4>

61<2-13/32> 40<19/32> 0 53<2-3/32>
41 <1-5/8>

2-12×36 oval holes (Foundation Bolt M10<W3/8>)

Handle Side Air Intake for moving

950 <37-13/32> 322<12-11/16> Earth terminal

Terminal Connections Left ... Power supply wiring Reight ... Indoor/Outdoor wiring Service panel Handle for moving

1 2

*1 431<16-31/32> *1 447<17-5/8>
669<26-11/32>

943 <37-1/8> 473 <18-5/8> 23 <29/32>

Piping knockout Hole Details

Power supply wiring hole (2-ø27knockout) Front trunking hole 40<1-9/16> (knockout)

45 <1-25/32>

Right piping hole (knockout)
75 <2-31/32>

Power supply wiring hole (2- ø27knockout)

Right trunking hole (knockout)

40<1-9/16>

45<1-25/32>

Power supply wiring hole (2- ø27<1-1/16>knockout) 40<1-9/16> Rear trunking hole (knockout)

Set the attachment to the When installing the conduit, inner side of each panel.

2-ø22.2<7/8>

1/2 Conduit attachment

73 <2-7/18> 63 <2-1/2>
55 <2-3/16>

63 <2-1/2>

63<2-1/2> 55 <2-3/16>

73 <2-7/8>

31<1-7/32>

Front piping hole (knockout)

ø92 <3-5/8>
92<3-5/8> 65 <2-9/16>

19<3/4>

ø 92 <3-5/8>
92 <3-5/8> 55 <2-3/16>

ø92 <3-5/8>
Rear piping hole (knockout)
92 <3-5/18> 65 <2-9/16>

40<1-9/16> 74<2-19/32>

71 <2-13/16>

71<2-13/16>

Front piping cover Rear piping cover

Bottom piping hole (knockout)

219 <8-5/8>

81<3-3/16>

30 <1-3/16>

220

145

145

145

<8-21/32> <5-23/32><5-23/32><5-23/32>

Drain hole (5- ø33<1-5/16>)

27 23 <29/32> <1-1/16> 92 <3-5/8>

23 <29/32> 27<1-1/16>

73 <2-7/18>

27<1-1/16>

23 <29/32>

FORM# PKA-A30KA8 & PUY-A30NHA7 - 202310 Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.


Adobe PDF Library 16.0.7 Adobe InDesign 17.4 (Windows)