ASCO 300 Series 2000 Ampere G Frame Transfer Switch Outline Drawing
This document provides an outline drawing and technical specifications for the ASCO 300 Series 2000 Ampere "G" Frame Front Connected Transfer Switches, Type 3R/3RX Secure Enclosure.
Views and Dimensions
Top View
Dimensions: 46.63 inches (width) x 42.50 inches (depth). Features a 28.0 x 32.0 inch Top Conduit Area.
Front View
Dimensions: 42.50 inches (width) x 95.48 inches (height). Features two front doors with louvers.
Front View Without Exterior Doors
Dimensions: 41.0 inches (width) x 95.48 inches (height). Shows internal components including a Controller User Interface and Field Connections Terminal Block (TB).
Left Side View
Dimensions: 46.63 inches (width) x 95.48 inches (height). Shows internal cabling routing. Overall depth is 29.13 inches.
Right Side View
Dimensions: 46.63 inches (width) x 95.48 inches (height).
Plan View
Dimensions: 41.0 inches (width) x 46.6 inches (depth). Features a 28.0 x 32.0 inch Bottom Conduit Area. Includes 0.625 inch diameter mounting holes (required, 2 places).
General Notes
- Type 3R enclosure: Free standing, floor mounted, code gauge formed frame construction.
- Interior pan type doors and removable covers with padlockable handles and 3-point latch.
- Construction complies with UL 1008 requirements.
- Finish: Type 3R: ANSI 61 Gray Polyester Semi Gloss Electrostatic Powder. Type 3RX: Code gauge Type 304 Stainless Steel exterior.
- Recommended Clearances: Front: 45 inches; Rear: None.
- Bus material: Silver-plated copper, rated for 1000A per sq. in. density.
- Neutral connection options: Solid (copper bus) neutral (standard) or Switched Neutral Pole (optional).
- Designed for front access only.
- Refer to operator's manual for specified transfer switch.
- Exterior vents supplied with polyester dust filters.
- Lifting plates are supplied; inspect for damage and torque to 45 ft-lbs before use. Refer to ANSI/NEMA PB 2.1 for handling. Remove after installation and reinstall bolts to exterior holes (approx. 20 ft-lbs).
Cabling Notes
- Standard mechanical (screw type) lugs are supplied.
- Lug Material: Aluminum Alloy 6061-T6 with electro tin plated finish.
- Screw Material: Aluminum Alloy 6262-19 with electro tin plated finish.
- UL Listed, CSA Certified.
- Lug screw tightening torque per UL 486B: 19 ft-lbs.
- Suitable wire bending space is provided (see amp size below).
- Ground lugs are provided standard as follows (see amp size below).
- Customer Terminal Blocks: For 300 series units, TB will be mounted on the transfer switch frame.
Notes for 2000 Amps
- Standard mechanical (screw type) lugs on Normal, Emergency & Load bus stabs.
- Each lug suitable for connection of six (6) 1/0 -750MCM CU/AL cables.
- Suitable wire bending space provided for up to six (6) 750MCM cables per terminal, per NEC.
- Ground lugs provided standard: (18) 1/0 - 750MCM CU/AL cable.
Document Information
Project Name: MOUNTING
Outline: G3ATS 2000 AMPS FRONT CONNECTED, LIFTING EYES
Type: 3R/3RX SECURE 96 X 41 X 47
Drawing Number: 1001395-002
Manufacturer: ASCO Power Technologies, L.P., Florham Park, New Jersey 07932 U.S.A.