ProSense FMM Series (-1001) Magnetic-Inductive Flow Meters

For the latest prices, please check AutomationDirect.com.

Overview

AutomationDirect's ProSense FMM Series (-1001) Magmeter is designed to reliably detect the flow rate of conductive media up to 160 gallons per minute. The stainless steel, mechanically-robust design mounts directly in-line providing a compact, low-profile installation for process control. A 4-digit numeric display with pushbutton setup indicates flow rate, fluid temperature and total flow volume with selectable engineering units. Two outputs are available to remotely monitor the binary or analog status of flow rate/volume and temperature parameters. Simple to setup, easy to install and with no moving parts, the FMM is a reliable alternative to traditional flow meters and mechanical flow switches.

Features

Output Function Selections

Output 1:

Output 2:

ProSense FMM Series (-1001) Magnetic Flow Meters

Model FMM50-1001 FMM75-1001 FMM100-1001 FMM150-1001 FMM200-1001
Price $00?vx: $00?vy: $00?vz: $;;000?v]: $;;000?v[:
Weight 1.09 lb 1.18 lb 1.30 lb 6.74 lb 6.75 lb
Range 0 to 6.6 GPM 0 to 13.2 GPM 0 to 26.4 GPM 0 to 80.0 GPM 0 to 160.0 GPM
Process Connection 1/2" FNPT 3/4" FNPT 1" FNPT 1-1/2" FNPT 2" FNPT
Application Conductive liquids: ≥ 20 µS/cm (micro Siemens per centimeter) liquids / viscosity: < 70cSt (centiStoke) at 104°F
Pressure Rating 232 PSIG [16 bar]
Medium Temperature 14 to 158°F [-10 to 70°C]
Operating Voltage 18 to 30 VDC
Current Consumption < 120mA < 150mA
Insulation Resistance > 100MΩ (500 VDC)
Protection Class III
Reverse Polarity Protection YES
Output Type / Function OUT1: switch (N.O. or N.C. / PNP or NPN) / flow rate, volumetric flow totalizer preset, empty pipe detection (1-1/2 and 2") or pulse / volumetric flow totalizer or frequency / flow rate (1-1/2 and 2")
OUT2: switch (N.O. or N.C. / PNP or NPN) / flow rate, temperature, empty pipe detection (1-1/2 and 2") or analog / flow rate, temperature or reset input / volumetric flow totalizer reset
Switch/Pulse/Frequency Outputs PNP/NPN Selectable
N.O./N.C. Selectable
Current Rating: 2 x 200mA
Voltage Drop: < 2V
Short-circuit protection: Yes (non-latching)
Overload protection: Yes
Switch hysteresis or window function
PNP/NPN Selectable
N.O./N.C. Selectable
Current Rating: 2 x 250mA
Voltage Drop: < 2V
Short-circuit protection: Yes (non-latching)
Overload protection: Yes
Switch hysteresis or window function
0.1 to 10000 Hz frequency
Analog Output 4-20 mA max 22mA or 0-10 VDC selectable
Max. load: 500Ω (4-20 mA)
Min. load: 2000Ω (0-10 VDC)

Technical Specifications

Model FMM50-1001 FMM75-1001 FMM100-1001 FMM150-1001 FMM200-1001
Measuring Range 0.030 to 6.604 GPM 0.060 to 13.200 GPM 0.100 to 26.400 GPM 1.300 to 80.000 GPM 1.300 to 160.000 GPM
Display Range -7.925 to 7.925 GPM -15.840 to 15.840 GPM -31.700 to 31.700 GPM -96.000 to 96.000 GPM -190.000 to 190.000 GPM
Resolution 0.010 GPM 0.020 GPM 0.050 GPM 0.100 GPM 0.100 GPM
Set Point, SP 0.060 to 6.600 GPM 0.120 to 13.200 GPM 0.250 to 26.400 GPM 1.700 to 80.000 GPM 2.100 to 160.000 GPM
Reset Point, rP 0.300 to 6.570 GPM 0.060 to 13.140 GPM 0.100 to 26.250 GPM 1.300 to 79.600 GPM 1.300 to 159.200 GPM
Analog Start Point, ASP 0.000 to 5.300 GPM 0.000 to 10.600 GPM 0.000 to 21.200 GPM 0.000 to 64.000 GPM 0.000 to 128.000 GPM
Analog End Point, AEP 1.300 to 6.600 GPM 2.600 to 13.200 GPM 5.200 to 26.400 GPM 16.000 to 80.000 GPM 32.000 to 160.000 GPM
In Steps Of 0.010 GPM 0.020 GPM 0.050 GPM 0.100 GPM 0.100 GPM
Pulse Value 0.010 to 30,300,000 GAL 0.010 to 99,990,000 GAL 0.010 to 100,000,000 GAL 0.020 to 80,000,000 GAL 0.020 to 160,000,000 GAL
Pulse Length 0.0025 to 2s 0.0025 to 2s 0.005 to 2s 0.016 to 2s 0.008 to 2s
Measuring Range -4 to 176°F [-20 to 80°C]**
Resolution 0.1°F 0.5°F
Set Point, SP -2.5 to 176°F -3.5 to 175.0°F -4.0 to 140.5°F
Reset Point, rP -3.5 to 175.0°F -4.0 to 140.5°F 31.5 to 176.0°F
Analog Start Point, ASP -4.0 to 140.5°F 31.5 to 176.0°F 32.0 to 176°F
Analog End Point, AEP 31.5 to 176.0°F 32.0 to 176°F
In Steps Of 0.5°F
Flow Monitoring Accuracy* ± 0.8% MW + 0.5% VMR
Repeatability* ± 0.2% VMR
Temperature Monitoring Accuracy ± 4.5°K (Q > 0.26 GPM) ± 1°K (Q > 4.0 GPM)
Power-On Delay Time 5s
Start-Up Delay N/A 0 to 50s
Response Time < 0.150s (dAP = 0) < 0.350s (dAP = 0)
Display Damping, dAP 0.0 to 5.0s
Response Time T09 = 3s (Q > 4.0 GPM)
Ambient Temperature 14 to 140°F [-10 to 60°C]
Storage Temperature -13 to 176°F [-25 to 80°C]
Protection IP 67 IP 65, IP 67

Mechanical Data

Model FMM50-1001 FMM75-1001 FMM100-1001 FMM150-1001 FMM200-1001
Process Connection 1/2" NPT female 3/4" NPT female 1" NPT female 1-1/2" NPT female 2" NPT female
Materials (wetted parts) Stainless steel 316L / 1.4404; PEEK (polyether ether ketone); FKM Stainless steel 316L / 1.4404; PBT-GF 20; PC; EPDM/X Stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti); PEEK; FKM
Housing Materials Stainless steel 316L / 1.4404; PEEK (polyether ether ketone); FKM Stainless steel 316L / 1.4404; PBT-GF 20; PC; EPDM/X Stainless steel 316L / 1.4404; stainless steel 316Ti / 1.4571; PEI; FKM; PBT-GF 20; elastolan

Display / Operating Elements

FMM50-1001, FMM75-1001, FMM100-1001 FMM150-1001, FMM200-1001
Display unit: 6 x LED green (GPM, GPH, GAL, °F, 103, 106) 6 x LED green (GPM, GPH, GAL, °F, 103, 106)
Switching Status: 2 x LED yellow 2 x LED yellow
Measured values: 4-digit alphanumeric display (7.5 mm) 4-digit alphanumeric display (7.5 mm)
Programming: 4-digit alphanumeric display (7.5 mm) 4-digit alphanumeric display (7.5 mm)

Electrical Connection

M12 connector; gold-plated contacts

Tests / Approvals

* To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number's web page at www.automationdirect.com

Note: Check the chemical compatibility of the sensor's wetted parts with the medium to be measured.

Wiring Diagram

Cable Assembly Wiring Colors:

Colors to DIN EN 60947-5-2

For additional wiring details see individual product manuals.

Use FMM-GND1 if meter is installed in ungrounded pipe system.

Output Function Selections

Models: FMM50-1001, FMM75-1001, FMM100-1001

Models: FMM150-1001, FMM200-1001

Note: Wiring colors are based on AutomationDirect CD12L and CD12M 4-pole cable assemblies.

Pressure Loss/Flow Rate*

*when used with water @ 68°F [20°C]

FMM50-1001

FMM75-1001

FMM100-1001

FMM150-1001

FMM200-1001

Dimensions

mm [inches]

Part No. FMM50-1001

Part No. FMM75-1001

Part No. FMM100-1001

Part No. FMM150-1001

Part No. FMM200-1001

Video Links

Click on the thumbnail or go to https://www.automationdirect.com/VID-FL-0003 for a short Quick Start video for the 0.5”, 0.75 and 1" FMM Series Magnetic-Inductive Flow Meters

Click on the thumbnail or go to https://www.automationdirect.com/VID-FL-0004 for a short Quick Start video for the 1.5" and 2.0" FMM Series Magnetic-Inductive Flow Meters

Click on the thumbnail or go to https://www.automationdirect.com/VID-FL-0005 for a short Parameter Setup video of the FMM Series Magnetic-Inductive Flow Meters using live demos.

Click or scan the above QR code to be taken to the installation insert for the FMM 50 and 75-1001 Series Magnetic Flow Meters

Click or scan the above QR code to be taken to the installation insert for the FMM 150 and 200-1001 Series Magnetic Flow Meters

Magnetic-Inductive Flow Meter Application

Magnetic-inductive flow meters (Magmeters) are one of the most widely used technologies for liquid flow monitoring in industrial process markets such as wastewater, mining and minerals, utilities, food and beverage, and pharmaceuticals. To ensure reliable and accurate operation, some important application requirements should be considered. Meeting the minimum conductivity of the liquid and properly installing with a full pipe are required in order to avoid significant error or the meter not functioning at all. Additionally, the presences of air bubbles should be avoided as they will affect the accuracy of the meter's measurements. Installation location in the piping is important because disturbances in the flow caused by bends in the pipe, valves, reductions, etc. can cause inaccuracies. The Endress+Hauser Picomag series has no minimum inlet or outlet pipe run requirements making it ideal for small confined spaces. Refer to the magmeter's specifications and operating instruction documents for specific information regarding application and installation requirements.

ProSense FMM Series

Endress+Hauser Picomag Series

Magnetic-Inductive Flow Meter Measuring Principle

Magmeters operate by using the magnetic-inductive measuring principle in which a magnetic field is generated in the specified measuring pipe by current-carrying coils. When the media flows through the pipe, the ions of the conductive media are diverted perpendicularly to the magnetic field with the positive and negative charge carriers flowing in opposite directions. The two electrodes that are in contact with the medium then measure the voltage that is induced. The measured signal voltage is proportional to the average flow velocity. By knowing the inside pipe diameter of the unit, the volumetric flow rate is determined. Magmeters are suitable for use with a variety of conductive liquids in industrial process applications such as those in the following graph:

Types of medium with electrical conductivity

ProSense FMM Series Magnetic Flow Meter Selection Guide

Model Price Process Connection Flow Range Temperature Range Display Units Output 1 Output 2 Empty Pipe Detection
FMM50-1001 $00?vx: 1/2" FNPT 0 to 6.6 GPM GPM, GPH, GAL, or °F Switch or pulse (flow) Switch, analog or reset input (flow or temperature) No
FMM75-1001 $00?vy: 3/4" FNPT 0 to 13.2 GPM GPM, GPH, GAL, or °F Switch, analog or reset input (flow or temperature) Switch, analog or reset input (flow or temperature) No
FMM100-1001 $00?vz: 1" FNPT 0 to 26.4 GPM GPM, GPH, GAL, or °F Switch, pulse or frequency (flow) Switch, analog or reset input (flow or temperature) Yes
FMM150-1001 $;;000?v]: 1-1/2" FNPT 0 to 80 GPM GPM, GPH, GAL, or °F Switch, pulse or frequency (flow) Switch, analog or reset input (flow or temperature) Yes
FMM200-1001 $;;000?v[: 2" FNPT 0 to 160 GPM -4 to 176°F [-20 to 80°C] GPM, GPH, GAL, or °F Switch, pulse or frequency (flow) Switch, analog or reset input (flow or temperature) Yes
FMM50-1002 $00?vq: 1/2" FNPT 0 to 6.6 GPM GPM, GPH, LPM, m³/h, °F, °C Analog 4-20 mA (flow) Analog 4-20 mA (temperature) No
FMM75-1002 $00?vs: 3/4" FNPT 0 to 13.2 GPM GPM, GPH, LPM, m³/h, °F, °C Analog 4-20 mA (flow) Analog 4-20 mA (temperature) No
FMM100-1002 $;00?vt: 1" FNPT 0 to 26.4 GPM GPM, GPH, LPM, m³/h, °F, °C Analog 4-20 mA (flow) Analog 4-20 mA (temperature) Yes
FMM150-1002 $;000?vu: 1-1/2" FNPT 0 to 79.3 GPM GPM, GPH, LPM, m³/h, °F, °C Analog 4-20 mA (flow) Analog 4-20 mA (temperature) Yes
FMM200-1002 $;000?vv: 2" FNPT 0 to 158.5 GPM -4 to 176°F [-20 to 80°C] GPM, GPH, LPM, m³/h, °F, °C Analog 4-20 mA (flow) Analog 4-20 mA (temperature) Yes

Endress+Hauser Picomag Magnetic-Inductive Liquid Flow Meter Selection

Part No. Price Process Connection Flow Range Temperature Range Totalizer Range Conductivity Range Output 1 Output 2 Empty Pipe Detection
DMA15-AAACA1 $-05#jd: 1/2" FNPT 0 to 9.2 GPM 14 to 158°F [-10 to 70°C] 20 to 30,000 liters 20 to 30,000 µS/cm • Flow rate, analog or switch
• Temperature, analog or switch
• Conductivity, analog or switch
• Flow rate, analog or switch
• Temperature, analog or switch
• Conductivity, analog or switch
Yes
DMA20-AAACA1 $-05#je: 3/4" FNPT 0 to 19.8 GPM +/-3.436E10 • Volumetric flow totalizer pulse
• Empty pipe detection switch
• Flow totalizer reset digital input Yes
DMA25-AAACA1 $;-05#jf: 1" FNPT 0 to 39.6 GPM • Empty pipe detection switch • Flow totalizer reset digital input Yes
DMA50-AAACA1 $;-005#jg: 2" FNPT 0 to 198.1 GPM • Flow override digital input • Flow override digital input Yes

Magnetic Flow Meter Accessories

The FMM-GND1 Grounding Clamp is used when an FMM series Magnetic-Inductive Flow Meter is installed in an ungrounded pipe system (e.g. PVC pipe).

Simply place the FMM-GND1 Grounding Clamp around the base of the M12 connector and attach a grounded wire to FMM-GND1 Grounding Clamp with the supplied machine screw and nut.

Note: Improper grounding may cause inaccurate readings

Part No. Description Price Weight
FMM-GND1 ProSense 316 stainless steel grounding clamp for magnetic flow meters with an M12 connector. $10_c: 0.015 lb

Dimensions

mm [inches]

Part No. FMM-GND1

Grounding Clamp Installation

The ProSense magnetic flow meter grounding clamp is installed as shown above. Note: the ground wire shown above is not included.

PDF preview unavailable. Download the PDF instead.

psfmm1001magmeter

Related Documents

Preview ProSense FMM Series (-1002) Magnetic-Inductive Flow Meters
Explore the ProSense FMM Series (-1002) Magnetic-Inductive Flow Meters, designed for reliable liquid flow rate detection. This document provides an overview, features, specifications, and selection guides for these robust and compact flow meters.
Preview ProSense FMM Series (-1002) Magnetic-Inductive Flow Meters
Automation Direct's ProSense FMM Series (-1002) Magmeters offer reliable detection of conductive liquid flow rates up to 158.5 GPM. These compact, stainless steel meters feature a 4-digit display, selectable engineering units, and two analog outputs for remote monitoring of flow and temperature. They are suitable for various industrial process applications.
Preview ProSense DPM3-P Series 1/8 DIN Digital Panel Meters
The ProSense DPM3-P series digital panel meters offer a simple, feature-packed solution for counter, chronometer, frequency, tachometer, rate, and pulse width modulated (PWM) applications. These 1/8 DIN meters feature a 5-digit tri-color LED display, selectable decimal points, and accept various input types including AC voltage, magnetic sensors, NPN/PNP sensors, NAMUR sensors, TTL/24V encoders, and switched contacts. They are available with optional dual SPDT relay outputs and a 4-20mA analog output. The meters are powered by an external AC or DC supply and feature an IP65 rated front panel. Configuration parameters can be locked to prevent unauthorized changes. The series is backed by a 3-year warranty.
Preview ProSense DPM1 Series 1/32 DIN Digital Panel Meters
ProSense DPM1 Series 1/32 DIN digital panel meters offer a simple, low-cost solution for displaying analog process signals. These meters feature a 4-digit red LED display, selectable decimal point, and manual or teach mode scaling for linear and non-linear processes. They include two SPST relay outputs with hysteresis or time delay operation and are available with a 0/4-20mA analog output. The meters are powered by external AC or DC, provide 20VDC for sensor excitation, and have an IP65 rated front panel. Configuration can be locked out, and they include memory for min/max display values, a tare function, and display filtering. ProSense digital panel meters come with a 3-year warranty.
Preview ProSense DPM4 Advanced High Speed Process Panel Meters User Manual
User manual for the ProSense DPM4 Advanced High Speed Process Panel Meters, covering installation, operation, programming, and technical specifications. Includes details on input configuration, output options, and troubleshooting.
Preview ProSense Field Device Configurator Software Help File
This document provides a comprehensive help file for the ProSense Field Device Configurator Software, detailing its features, operation, and configuration parameters for XTH2-0-UNV and XTD2-0-UNV temperature transmitters.
Preview ProSense 10K-3 Thermistor Probes with Lead Wire Transition
ProSense 10K-3 thermistor probes feature a 1/4 inch diameter, 316 stainless steel sheath for harsh environments. Available in 6", 12", or 18" probe lengths with a 4-point crimp and sleeve transition to a 6-foot PVC cable. These probes are made in the USA and offer a temperature sensing range of -40 to 125°C (-40 to 257°F). Technical specifications include a 10kΩ no-load resistance at 25°C and an accuracy of ± 0.2°C from 0°C to 70°C. Accessories such as brass and stainless steel compression fittings are also available.
Preview ProSense Float Level Switch Kits - Product Overview and Specifications
Detailed information on ProSense Float Level Switch Kits, including specifications, components, assembly instructions, and agency approvals. Covers models like FLS-VK-200 and FLS-VK-300.