Trane NTXMSM60A182BA 5-Ton Multi-Zone Inverter Heat-Pump System
Product Overview
The Trane NTXMSM60A182BA is a 5-ton, multi-zone inverter heat-pump system designed for efficient and versatile climate control. It is compatible with NV- and P-Series and CITY MULTI® indoor units, requiring a branch box for connection.
Key Features
- Compatible with NV-, P-Series, and CITY MULTI® indoor units.
- Variable speed INVERTER-driven compressor.
- Seacoast protection on heat exchanger and base panel (rated for 2,000 hrs in accordance with ASTM B117 testing).
- Thermal Differential 1°F (with TAC-MKA32/52BC only).
- Optional base pan heater.
- Quiet outdoor unit operation, rated sound pressure as low as 58 dB(A).
- High pressure protection.
- Compressor thermal protection.
- Compressor overcurrent detection.
- Fan motor overheating/voltage protection.
Specifications
Cooling
Capacity Type | Unit | Value |
Maximum Capacity | BTU/H | 60,000 |
Rated Capacity | BTU/H | 60,000 |
Minimum Capacity | BTU/H | 25,600 |
Maximum Power Input | W | 5,770 |
Rated Power Input | W | 5,770 |
Power Factor (208V, 230V) | % | 98.9 |
Heating at 47°F
Capacity Type | Unit | Value |
Maximum Capacity | BTU/H | 66,000 |
Rated Capacity | BTU/H | 66,000 |
Minimum Capacity | BTU/H | 31,000 |
Maximum Power Input | W | 5,690 |
Rated Power Input | W | 5,690 |
Power Factor (208V, 230V) | % | 98.9 |
Heating at 17°F
Capacity Type | Unit | Value |
Maximum Capacity | BTU/H | 65,000 |
Rated Capacity | BTU/H | 41,000 |
Maximum Power Input | W | 9,075 |
Rated Power Input | W | 4,750 |
Power Factor (208V, 230V) | % | 98.9 |
Heating at 5°F
Capacity Type | Unit | Value |
Maximum Capacity | BTU/H | 46,500 |
Rated Capacity | BTU/H | 7,575 |
Maximum Power Input | W | 4,750 |
Rated Power Input | W | 4,750 |
Efficiency
Efficiency Type | Unit | Value |
SEER2 | BTU/W·h | 20.0 |
EER21 | BTU/W·h | 13.3 |
HSPF2 (IV) | BTU/W·h | 10.5 |
COP at 47°F2 | 4.1 | |
COP at 17°F at Maximum Capacity³ | 2.3 | |
COP at 5°F at Maximum Capacity4 | 2.2 | |
ENERGY STAR® Certified | Yes |
Electrical Power Requirements
Parameter | Unit | Value |
Voltage, Phase, Frequency | VAC, Phase, Hz | 208/230, 1, 60 |
Guaranteed Voltage Range | VAC | 187-253 |
Voltage: Indoor - Outdoor, S1-S2 | VAC | 208/230 |
Voltage: Indoor Outdoor, S2-S3 | V DC | 24 |
Short-circuit Current Rating (SCCR) | KA | 5 |
Recommended Fuse/Breaker Size if Branch Box Powered by Outdoor Unit | A | 50 |
Recommended Fuse/Breaker Size without Branch Box or Branch Box Powered Separate | A | 40 |
Recommended Wire Size (Indoor - Outdoor) if Branch Box Powered by Outdoor Unit | AWG | 6 |
Recommended Wire Size (Indoor - Outdoor) without Branch Box or Branch Box Powered Separate | AWG | 8 |
MCA if Branch Box Powered by Outdoor Unit | A | 55.0 |
MOCP if Branch Box Powered by Outdoor Unit | A | 90 |
MCA without Branch Box or Branch Box Powered Separate | A | 45 |
MOCP without Branch Box or Branch Box Powered Separate | A | 80 |
Fan Motor Full Load Amperage | A | 0.8+0.8 |
Outdoor Unit Details
Parameter | Unit | Value |
Airflow Rate (Cooling / Heating) | CFM | 4,875/4,555 |
Refrigerant Control | LEV | |
Defrost Method | Reverse Cycle | |
Heat Exchanger Type | Plate fin coil | |
Heat Exchanger Coating | Blue Fin Coating | |
Sound Pressure Level, Cooling¹ | dB(A) | 58 |
Sound Pressure Level, Heating² | dB(A) | 59 |
Compressor Type | Hermetic | |
Compressor Model | ANB52FYDMT | |
Compressor Motor Output | kW | 3.9 |
Compressor Rated Load Amps | A | 19 |
Compressor Locked Rotor Amps | A | 22.0 |
Compressor Oil Type // Charge | OZ. | FVC68D // 78 |
Base Pan Heater | Optional (PAC-SJ20BH-E) | |
Unit Dimensions (W x D x H) | In. [mm] | 41-11/32 [1,050] x 13 [330] x 52-11/16 [1,338] |
Package Dimensions (W x D x H) | In. [mm] | 43 [1,090] x 18 [450] x 57 [1,430] |
Unit Weight | Lbs.[kg] | 302 [137] |
Package Weight | Lbs.[kg] | 326 [148] |
Outdoor Unit Operating Temperature Range
Parameter | Unit | Value |
Cooling Intake Air Temp (Maximum / Minimum) | °FDB | 115/50 |
Cooling Thermal Lock-out / Re-start Temperatures | °FDB | 59/-13 |
Heating Intake Air Temp (Maximum / Minimum) | °FDB | -24/-14 |
Heating Thermal Lock-out / Re-start Temperatures | °FDB | -24/-14 |
Refrigerant
Parameter | Unit | Value |
Pre-Charged Refrigerant Amount | Lbs, oz | 11.0, 4.0 |
Indoor Unit Connection
Parameter | Unit | Value |
Maximum Number of Connected IDU with Branch Box | 8 (6) | |
Maximum Number of Connected IDU without Branch Box | 12 | |
Minimum Connected Capacity with Branch Box | BTU/H | 12,000 |
Minimum Connected Capacity without Branch Box | BTU/H | 30,000 |
Maximum connected capacity | BTU/H | 78,000 |
Piping
Parameter | Unit | Value |
Liquid Pipe Size O.D. (Flared) | In.[mm] | 3/8 [9.52] |
Gas Pipe Size O.D. (Flared) | In.[mm] | 3/4 [19.05] |
Total Piping Length when using Branch Box | Ft. [m] | 492 [150] |
Total Piping Length without Branch Box | Ft. [m] | 492 [150] |
Maximum Height Difference*B, ODU above IDU | Ft. [m] | 164 [50] |
Maximum Height Difference B, ODU below IDU | Ft. [m] | 131 [40] |
Maximum Height Differences, between branch boxes | Ft. [m] | 49 [15] |
Maximum Piping Length between ODU and Branch Box | Ft. [m] | 180 [55] |
Farthest Piping Length from ODU to IDU with Branch Box | Ft. [m] | 262 [80] |
Farthest Piping Length from ODU to IDU without Branch Box | Ft. [m] | 262 [80] |
Farthest Piping Length after Branch Box | Ft. [m] | 82 [25] |
Total Piping Length between Branch Boxes and IDU | Ft. [m] | 311 [95] |
Maximum Number of Bends for IDU | 15 |
Outdoor Unit Accessories
Accessory Type | Description | Model Number |
Branch Box | 5 Port Branch Box | PAC-MKA53BC |
Control/Service Tool | Maintenance Tool Interface | PAC-USCMS-MN-1 |
Drain Socket | Drain Socket | PAC-SG60DS-E |
Wind Baffle | Front Wind Baffle | WB-PA3 (two pieces are required) |
Branch Box | 3 Port Branch Box | PAC-MKA33BC |
Control Wire | M-Net Control Wire, 250' Roll (16-AWG, Standard, Twisted Pair, Shielded, Jacketed-Plenum rated) | QSMS1202M |
Condenser Wall Bracket | Stainless Steel Finish | QSMS2402M |
Outdoor Unit Stand | 12" High | QSMS1802M |
Stand | 24" Dual Fan Stand | CW162S-1000 |
Control Wire | M-Net Control Wire, 1,000' Roll (16-AWG, Standard, Twisted Pair, Shielded, Jacketed-Plenum rated) | QSWB2000M-1 |
Stand | Condenser Wall Bracket | QSWBSS |
Control Wire | CW162S-250 | |
Mini-Split Wire | 14 Gauge, 4 wire MiniSplit Cable-50 ft. roll | S144-50 |
Mini-Split Wire | 14 Gauge, 4 wire MiniSplit Cable-250 ft. roll | S144-250 |
Branch Box | Branch Box Enclosure | BBE-1 |
Mini-Split Wire | 16 Gauge, 4 wire MiniSplit Cable-250 ft. roll | S164-250 |
Ball Valve | Refrigeration Ball Valve - 1/2" | BV12FFS12 |
Mounting Pad | Condensing Unit Mounting Pad: 24" x 42" x 3" | MSDD-50BR-E |
Mini-Split Wire | 16 Gauge, 4 wire MiniSplit Cable-50 ft. roll | S164-50 |
Distribution pipe | Brazed Connection | PAC-493PI |
Port Adaptor | Adaptor: 1/4" x 3/8" | TAC-MKA32BC |
Branch Box | 3 Port Branch Box | TAC-MKA52BC |
Air Outlet Guide | Air Outlet Guide (1 Piece) | PAC-SH96SG-E (two pieces are required) |
Port Adaptor | Adaptor: 3/8" x 5/8" | PAC-SH97DP-E |
Optional Defrost Heater | Optional Defrost Heater | PAC-SG76RJ-E |
Centralized Drain Pan | Central Drain Pan | PAC-SJ20BH-E |
Port Adaptor | Adaptor: 3/8" x 1/2" | PAC-SH97DP-E |
Distribution pipe | Adaptor: 1/2" x 3/8" | MAC-A454JP-E |
Air Deflector | Vertical Air Deflector | MAC-A455JP-E |
Ball Valve | Refrigeration Ball Valve - 1/4" | MAC-A456JP-E |
Mini-Split Wire | 14 Gauge, 4 wire MiniSplit Cable-250 ft. roll | MSDD-50AR-E |
Ball Valve | Refrigeration Ball Valve - 3/8" | ADV-1 |
Mini-Split Wire | 16 Gauge, 4 wire MiniSplit Cable-250 ft. roll | SW144-250 |
Ball Valve | Refrigeration Ball Valve - 5/8" | BV58FFS12 |
Stand | Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic | DSD-400P |
Hail Guards | Hail Guard | HG-A2 |
Outdoor Unit Dimensions
The following diagram illustrates the dimensions of the outdoor unit. Key dimensions include:
- Unit Dimensions (W x D x H): 41-11/32" [1,050 mm] x 13" [330 mm] x 52-11/16" [1,338 mm]
- Package Dimensions (W x D x H): 43" [1,090 mm] x 18" [450 mm] x 57" [1,430 mm]
- Service Space: Minimum 19-11/16" [500 mm]
- Foundation Bolts: M10 (3/8")
Diagram Description: The diagram shows a detailed view of the outdoor unit with various dimensions indicated in both inches and millimeters. It highlights air intake and discharge points, service access areas, foundation bolt locations, and piping/wiring connection points. Specific dimensions are provided for width, depth, and height, as well as for knock-out holes for piping and conduit.
Notes and Application Guidelines
- AHRI Rated Conditions for Cooling: 80°F DB, 67°F WB (Indoor) // 95°F DB, 75°F WB (Outdoor).
- AHRI Rated Conditions for Heating at 47°F: 70°F DB, 60°F WB (Indoor) // 47°F DB, 43°F WB (Outdoor).
- AHRI Rated Conditions for Heating at 17°F: 70°F DB, 60°F WB (Indoor) // 17°F DB, 15°F WB (Outdoor).
- AHRI Rated Conditions for Heating at 5°F: 70°F DB, 60°F WB (Indoor) // 5°F DB, 4°F WB (Outdoor).
- Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
- The maximum connectable capacity is 130%, but the outdoor unit cannot provide more than 100% of the rated capacity. This over-capacity capability is for load shedding or applications where not all connected units operate simultaneously.
- Mid and high external static pressure tests were conducted at 0.3 and 0.5 in.w.g. respectively, according to AHRI 210/240.
Related Documents
![]() |
Trane 15 SEER Convertible Single Packaged Heat Pump Product Data Comprehensive product data, specifications, optional equipment, and wiring information for Trane's 15 SEER Convertible Single Packaged Heat Pump units, covering models 4WCY5024A1000A through 4WCY5060A1000A. |
![]() |
Trane 4WCA4036C1000A Single Packaged Heat Pump Submittal and Specifications Detailed submittal and technical specifications for the Trane 4WCA4036C1000A Single Packaged Heat Pump. This document covers performance data, dimensions, electrical requirements, and features for residential HVAC applications, highlighting its 3-ton capacity and 13.4 SEER2 efficiency. |
![]() |
Trane 4WCZ6024A1000A 2-Ton Convertible Heat Pump Packaged Unit Specifications Detailed product specifications, dimensional data, and performance charts for the Trane 4WCZ6024A1000A 2-Ton Convertible Heat Pump Packaged Unit, including cooling and heating performance, electrical requirements, and optional accessories. |
![]() |
Trane & Mitsubishi Electric NTXDKS18A112AA & NTXSKS18A112AA Heat Pump Specifications Detailed specifications for the Trane and Mitsubishi Electric NTXDKS18A112AA 18,000 BTU/H low static horizontal-ducted indoor unit and the NTXSKS18A112AA 18,000 BTU/H heat pump universal outdoor unit. Includes features, electrical specifications, dimensions, and accessories. |
![]() |
Trane Nv-Series Ductless HVAC Catalog: Zoned Comfort Solutions Explore Trane's Nv-Series ductless HVAC systems, offering advanced zoned comfort solutions for residential applications. Discover features like inverter technology, Pro-Heat, and smart controls for energy efficiency and personalized climate control. |
![]() |
Trane Convertible Air Handlers 2-5 Ton Product Data Product data for Trane Convertible Air Handlers, 2-5 Ton series, including model numbers 5TEM6B02AV21SA through 5TEM6D07AV51SA. This document details features, specifications, electrical data, airflow performance, and dimensions. |
![]() |
Trane Foundation Packaged Rooftop Units: 15-25 Ton Cooling & Gas/Electric Specifications Comprehensive quick reference guide for Trane Foundation™ packaged rooftop units (15-25 tons) covering cooling and gas/electric performance, electrical data, fan specifications, dimensions, clearances, and curb compatibility. |
![]() |
Trane TPEFYW027MA1W0A Medium Static HVRF Ducted Indoor Unit Specifications Detailed specifications and dimensions for the Trane TPEFYW027MA1W0A, a medium static HVRF ducted indoor unit from Mitsubishi Electric Trane HVAC US LLC. Includes features, electrical data, airflow, sound levels, and accessory information. |