User Manual for TRANE models including: 4WCA4036C1000A RunTru Heat Pump Package Unit, 4WCA4036C1000A, RunTru Heat Pump Package Unit, Heat Pump Package Unit, Pump Package Unit, Package Unit

4WCA4036C-SUB-1A-EN

4WCA4036C Specification Manual

3 Ton 13.4 SEER2 Trane RunTru Heat Pump Package Unit - 4WCA4036C1000A • Ingrams Water & Air


File Info : application/pdf, 10 Pages, 1.46MB

PDF preview unavailable. Download the PDF instead.

4WCA4036C-specfications
Submittal
Single Packaged Heat Pump
4WCA4036C1000A
Note: "Graphics in this document are for representation only. Actual model may differ in appearance."

October 2022

4WCA4036C-SUB-1A-EN

Product Specifications

MODEL RATED Volts/PH/Hz Performance Cooling BTUH (a) Indoor Airflow (CFM) Power Input (KW) EER2/SEER2 (BTU/Watt-Hr.) (b) Sound Power Rating [dB(A)] (c) PERFORMANCE HEATING (High Temp.) BTUH Power Input (KW) (Low Temp.) BTUH Power Input (KW) HSPF2 (BTUH/Watt-Hr) POWER CONN. -- V/Ph/Hz Min. Brch. Cir. Ampacity (d) Fuse Size -- Max. (amps) Fuse Size -- Recmd. (amps) COMPRESSOR VOLTS/PH/HZ R.L. Amps -- L.R. Amps OUTDOOR COIL -- TYPE Rows/F.P.I Face Area (sq. ft.) Tube Size (in.) Refrigerant Control INDOOR COIL -- TYPE Rows/F.P.I Face Area (sq. ft.) Tube Size (in.) Refrigeration Control Drain Conn. Size (in.) OUTDOOR FAN -- TYPE

4WCA4036C1000A 208­230/1/60 34200 1105 3.77 10.6/13.4 79.3
30200 2.53 18000 2.2 6.7 208/230/1/60
25 35 35 SCROLL 208/230/1/60 14.1/87.4 PLATE FIN 1/22 13.2 5/16 EXPANSION VALVE PLATE FIN 3/16 4.56 5/16 EXPANSION VALVE 3/4 MALE NPT PROPELLER

DIA. (IN.)

23

DRIVE/NO. SPEEDS

DIRECT / 1

CFM @ 0.0 in. w.g. (e)

3540

Motor -- HP/R.P.M

1/5 / 825

Volts/Ph/Hz

200/230 / 1 / 60

F.L. Amps/L.R Amps

1.10/2.51

INDOOR FAN -- TYPE

CENTRIFUGAL

Dia. x Width (in.)

11 X 8

Drive/No. Speeds

DIRECT / 3

CFM @ 0.0 in. w.g. (f)

SEE FAN PERFORMANCE TABLE

Motor -- HP/R.P.M.

3/4 / VARIABLE

Volts/Ph/Hz

208­230/1/60

F.L. Amps

6.3

FILTER / FURNISHED

NO

Type Recommended

THROWAWAY

Recmd. Face Area (sq. ft) (g)

4.0

REFRIGERANT

R-410A

Charge (lbs.)

4.88

CHARGING SPECIFICATIONS

Subcooling DIMENSIONS Crated (in.)

14° HXWXL 40 7/8 x 36 3/8 x 61 1/8

WEIGHT

Shipping (lbs.) / Net (lbs.)

475

(a) Rated in accordance with AHRI Standard 210/240. (b) Rated in accordance with D.O.E. test procedure. (c) Sound Power values are not adjusted for AHRI 270­95 tonal
corrections. (d) Calculated in accordance with currently prevailing Nat'l Electrical
Code. (e) Standard Air -- Dry Coil -- Outdoor. (f) Standard Air -- Dry Coil -- Indoor (g) Filters must be installed in return air stream. Square footages listed
are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05" W.C.

2

4WCA4036C-SUB-1A-EN

Outline Drawings

Figure 1. 2 ­ 5 Tons

4WCA4036C-SUB-1A-EN

3

Outline Drawings

Figure 2. 2 ­ 5 Tons

MODEL
4WCA4024C 4WCA4030C 4WCA4036C 4WCA4042C 4WCA4048C 4WCA4060C

HEIGHT MM/IN . A
918.8 [36-5/32] 918.8 [36-5/32] 918.8 [36-5/32] 918.8 [36-5/32] 1045.8 [41-5/32] 1045.8 [41-5/32]

DRAIN PAN CONNECTION THROUGH HOLE

W1 383.9 [15 1/8] 383.9 [15 1/8] 383.9 [15 1/8] 383.9 [15 1/8] 460.1 [18 1/8] 460.1 [18 1/8]

W2 460.1 [18 1/18] 460.1 [18 1/18] 460.1 [18 1/18] 460.1 [18 1/18] 510.9 [20 1/8] 510.9 [20 1/8]

W3 568.8 [22 13/32] 568.8 [22 13/32] 568.8 [22 13/32] 568.8 [22 13/32] 645.0 [25 13/32] 645.0 [25 13/32]

W4 636.1 [25 1/32] 636.1 [25 1/32] 636.1 [25 1/32] 636.1 [25 1/32] 712.3 [28 1/32] 712.3 [28 1/32]

NET WEIGHT/LBS 410 410 430 440 460 460

4

4WCA4036C-SUB-1A-EN

Indoor Fan Performance (230v)

Table 1. Heater Table

Heater

BAYHTR1V05LUGAA BAYHTR1H08LUGAA BAYHTR1H10LUGAA BAYHTR1H15BRKAA

Table 2. Airflow Table

4WCA4036C Low
Medium High

ESP CFM WATTS CFM WATTS CFM WATTS

0.1 1369 202

0.2 1278 210

0.3 1178 220 1334 322

0.4 1078 230 1288 332

Note: Airflow must not exceed 1350 CFM due to condensate blowoff.

0.5 977 242 1241 343

Minimum Heater Airflow CFM 4WCA4036C1000A 1000 1000 1100 1400

0.6

0.7

0.8

0.9

1193 353

1147 364

1103 374

1050 384 1392 686

1
1284 708

4WCA4036C-SUB-1A-EN

5

Full Perimeter Roof Mounting Curb
Figure 3. 2.0 -- 5.0 Ton Models
BAYCURB060A Full Perimeter Roof Mounting Curb

14.000

57.531 TOP O.D.
55.406 I.D.

8.750

17.000
RETURN

16.813
SUPPLY

20.000

31.969 TOP O.D.
29.844 I.D.

WOOD NAILER CHANNEL SIDE

32.469 HOLD DOWN
CLIP O.D.
35.844 BOTTOMO.D.

D C

A RETURN
SUPPLY
B

61.406 BOTTOM O.D.
The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use.
CHANNEL END

HOLE IN ROOF

SERVICE CLEARANCE DIMENSIONS

A

B

C

D

12

42

42

36

6

4WCA4036C-SUB-1A-EN

Supplementary Electric Heaters

Table 3. HP Models Only

UNIT MODEL

ELECTRIC HEATER MODEL

RATED VOLT-
AGE

PHASE

AMPS

HEATER CAPACITY

KW

BTUH

NO. OF STAGES

KW/STAGE

1

2

4WCA4024*1000A BAYHTR1V05LUGA* 208/240

1

4WCA4030*1000A

17/ 3.6/ 12300/

20

4.8

16400

1

3.6/ 4.8

4WCA4036*1000A 4WCA4042*1000A

BAYHTR1H08LUGA* 208/240

1

28/ 5.76/ 19700/

32

7.68 26200

1

5.76/ 7.68

4WCA4048*1000A

4WCA4060*1000A BAYHTR1H10LUGA* 208/240

1

35/ 7.2/ 24600/

40

9.6

32800

1

7.2/ 9.6

4WCA4036*1000A

4WCA4042*1000A 4WCA4048*1000A

BAYHTR1H15BRKA* 208/240

1

52/ 10.8/ 36900/

60

14.4 49100

2

7.2/ 9.6

4WCA4060*1000A

4WCA4060*1000A BAYHTR1H20BRKA* 208/240

1

69/ 14.4/ 49100/

80

19.2 65500

2

7.2/ 9.6

1. Any power supply and circuits must be wired and protected in accordance with local electrical codes. 2. The values listed in the above table are for the electric heater only. 3. Field wiring must be rated at least 75° C. 4. * indicates an alpha character

--
--
--
3.6/ 4.8
7.2/ 9.6

ALL VALUES ARE FOR THE ELECTRIC HEATER ONLY

MCA
22/ 25 35/ 40 43/ 50

MAX. OVER CURRENT PROTEC-
TION DEVICE
25/ 25
35/ 40
45/ 50

65/

70/

75

80

87/

90/

100

100

Table 4. BAYSPEK - Single Power Entry Kit

UNIT MODEL 4WCA4036C

SINGLE CIRCUIT POWER AMPACITY AND OVER CURRENT PROTECTION

SINGLE POWER ENTRY KIT

HEATER MODEL

MIN CKT AMP

MAX OVER-CURRENT DEVICE

BAYHTR1H08

65

70

BAYSPEK070

BAYHTR1H10

75

80

BAYSPEK071

BAYHTR1H15

100

100

BAYSPEK072

BAYHTR1V05

50

50

4WCA4036C-SUB-1A-EN

7

Mechanical Specifications
General
The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped, internally wired and fully charged with refrigerant. Units shall be certified to UL Standard 1995. All units shall be factory run tested to check cooling operation, fan and blower rotation and control or TXV sequence. Units shall be designed to operate at ambient temperatures between 115°F and 55°F in cooling as manufactured. Cooling performance shall be rated in accordance with AHRI standards.
Unit Casing
All components shall be mounted in a weatherresistant steel cabinet with an enamel finish. Access panels shall be provided for unit controls and indoor coil and fans. Indoor air section compartment shall be completely insulated with fireproof, permanent, odorless fiber material. Knockouts shall be provided for utility and control connections. Drain connections shall be provided to accommodate indoor water runoff.
Compressor (2 and 2 1/2 Ton Models)
The compressor shall be hermetically sealed, high efficiency rotary compressors. Internal overcurrent and over temperature protection, internal pressure relief shall be standard. Other features include centrifugal oil pump, low vibration and noise.
Compressor (3­5 Ton Models)
The compressor shall be hermetically sealed, high efficiency scroll compressors. Internal overcurrent and over temperature protection, internal pressure relief shall be standard. Other features include centrifugal oil pump, low vibration and noise.
Refrigeration System
All units shall have refrigerant control. Service pressure tap ports and a refrigerant line filter shall be standard.
Evaporator Coil Internally enhanced 3/8" OD seamless copper tubing mechanically bonded to aluminum fins, factory pressure and leak tested at 480 ­ 650 psig. All units have TXV to control refrigerant flow.
Condenser Coil
All aluminum micro channel, extruded tubes, mechanically bonded to aluminum fins, and factory pressure and leak tested at 480 ­ 650 psig.
Indoor Air Fan

Constant Torgue, forward-curved, centrifugal wheel in a Metallic Blower housing. Motor shall have thermal overload protection and permanently lubricated motor bearings. Motor/blower assembly isolated from unit with rubber mounts.
Outdoor Fan
One direct-drive, statically and dynamically balanced propeller fan shall be used in a draw-through vertical discharge configuration. Permanently lubricated weather proof motor shall have built-in thermal overload protection.
System Controls
System controls include condenser fan, evaporator fan and compressor contactors.
Accessories Roof Curb
The roof curb shall be designed to mate with the unit and provide support and complete weathertight installation when properly installed. Adhesive back polyurethane sealing strips shall be provided to ensure an airtight seal between supply and return openings of the curb and unit. The roof curb design allows field fabricated ductwork to be connected directly to the curb. Curb ships knocked down for field assembly, and includes factory installed wood nailer strips.
Electric Heaters
Each heater assembly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat limiters for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage wiring. Electric heat modules shall be UL listed.
Single Source Power Entry
This accessory when used with electric heat accessory shall allow single source power connection to unit and heater combination. Single source power entry kits shall have specific matching heater(s). Kit shall include high voltage terminal blocks, fuse blocks and fuses, cut-to-length interconnecting wiring, and junction box (if required) to provide power sources with fuse protection as required for both the unit and accessory heater. Kit components shall install within the heater cabinet in the heater access section. Single source branch power circuit shall be protected and wired in accordance with local codes.

8

4WCA4036C-SUB-1A-EN

Mechanical Specifications

Start Kit
Extra compressor starting capacity for single phase equipment.
Control Options Standard Indoor Thermostats
Two stage heating/cooling or one stage heating/ cooling thermostats shall be available in either manual or automatic changeover.

Programmable Electronic Night Setting Thermostat
Programmable electronic thermostat shall provide heating setback and cooling setup with 7­day programming capability. 1H/1C or 2H/2C models available.

4WCA4036C-SUB-1A-EN

9

About Trane and American Standard Heating and Air Conditioning Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com.

The AHRI Certified mark indicates company participation in the AHRI Certification program. For verification of individual certified products, go to ahridirectory.org.

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

4WCA4036C-SUB-1A-EN 28 Oct 2022 Supersedes (New)

©2022



References

PTC Arbortext Publishing Engine PDFlib PDI 9.0.6 (C /Win64); modified using iText 2.1.7 by 1T3XT