Quick Reference Guide: Trane Foundation™ Packaged Rooftop Units
Cooling and Gas/Electric, 15 to 25 Tons
Copyright and Trademarks
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
All trademarks referenced in this document are the trademarks of their respective owners.
Model Numbers: EDK, GDK
Used With: Cooling Only (Electric Heat Optional), Gas Heat Unit
Publication Date: September 2024
Document ID: RT-PRC127A-EN
List of Options
Note: Most Factory Installed Options are available for downflow air discharge units only. Verify with ordering system for availability.
Table 1: List of Options
Factory Installed Options
- 2-in. MERV 13 Pleated Filters
- Barometric Relief (a), (b)
- Complete Coat™ Microchannel Condenser Coil
- Condensate Overflow Switch
- Economizer - Standard/Downflow(b)
- Economizer - Low Leak/Downflow(b)
- Electric Heaters
- High Static Motor
- Manual Outside Air Damper
- Motorized Outside Air Damper
- Multi-Speed Motor
- Reference or Comparative Enthalpy Economizer
- Single Zone VAV
- Stainless Steel Heat Exchanger with 10 Year Warranty
- Through-the-Base Electrical Access
- Through-the-Base Gas Piping(b)
- Unit Mounted Non-Fused Disconnect Switch(c)
(a) Requires an economizer. (b) Some field set up required. (c) Must be ordered with Through-the-Base Electrical option.
Field Installed Options
- 2-in. MERV 13 Pleated Filters
- Barometric Relief(a)(b)
- Condensate Overflow Switch
- Condenser Coil Guard
- Customer Connection Module
- Demand controlled Ventilation
- Differential Drybulb Economizer
- Economizer - Standard/Downflow(b)
- Economizer - Low Leak/Downflow(b)
- Economizer - Standard/Horizontal
- Economizer - Low Leak/Horizontal
- Electric Heaters
- Fresh Air Options Module
- Hail Guard
- High Altitude Kit
- High and Low Static Drive Kit
- Indoor Options Module
- Low Ambient Control
- LP Conversion Kit
- Manual Outside Air Damper
- Motorized Outside Air Damper
- Power Exhaust
- Reference or Comparative Enthalpy Economizer
- Roof Curb
- Thermostat
- Through-the-Base Electrical Access
- Through-the-Base Gas Piping(b)
- Unit Mounted Non-Fused Disconnect Switch(c)
Performance Data
Table 2: 15 to 25 Tons Packaged Rooftop Performance Data (Gas or Electric Heat)
E/GDK | Nominal Size (Ton) | Cooling Performance(a) Gross Cooling Capacity | Cooling Performance(a) AHRI Net Cooling Capacity | Cooling Performance(a) Nominal Airflow CFM / AHRI Rated CFM | Cooling Performance(a) EER | Cooling Performance(a) IEER (Multi-Speed Fan) | Gas Heating Performance(b) Low Heat (Input/Output) - (MBh) | Gas Heating Performance(b) Medium Heat (Input/Output) - (MBh) | Gas Heating Performance(b) High Heat (Input/Output) - (MBh) | Other Information Net Weight (Lbs) - Gas Heat | Other Information Net Weight (Lbs) - Electric Heat | Other Information Filters - Type Furnished(c) | Other Information Number and Size Recommended |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
EDK180 | 15 | 188,000 | 182,000 | 6000 | 11 | 14.2 | 240,000/194,000 | 320,000/259,000 | 350,000/283,500 | 2054 | 1891 | Throwaway | (8) 20x24x2 |
GDK180 | 15 | 188,000 | 182,000 | 6000 | 10.8 | 14 | 240,000/194,000 | 320,000/259,000 | 350,000 (Horizontal)/307,800 (Downflow), 283,500 (Horizontal)(b) | 2054 | 1891 | Throwaway | (8) 20x24x2 |
EDK210 | 17.5 | 212,000 | 206,000 | 5600 | 11 | 14.2 | 240,000/194,000 | 320,000/259,000 | 380,000 (Downflow), 350,000 (Horizontal)/307,800 (Downflow), 283,500 (Horizontal)(b) | 2069 | 1896 | Throwaway | (8) 20x24x2 |
GDK210 | 17.5 | 212,000 | 206,000 | 5600 | 10.8 | 14 | 240,000/194,000 | 320,000/259,000 | 380,000/308,000 | 2069 | 1896 | Throwaway | (8) 20x24x2 |
EDK240 | 20 | 250,000 | 240,000 | 8000 | 10 | 13.2 | 240,000/194,000 | 320,000/259,000 | 380,000/307,800 | 2067 | 1902 | Throwaway | (8) 20x24x2 |
GDK240 | 20 | 250,000 | 240,000 | 8000 | 9.8 | 13 | 240,000/194,000 | 320,000/259,000 | 380,000/307,800 | 2067 | 1902 | Throwaway | (8) 20x24x2 |
EDK300 | 25 | 280,000 | 266,000 | 9000 | 10 | 13.2 | 240,000/194,000 | 320,000/259,000 | 380,000/308,000 | 2103 | 1938 | Throwaway | (8) 20x24x2 |
GDK300 | 25 | 280,000 | 266,000 | 9000 | 9.8 | 13 | 240,000/194,000 | 320,000/259,000 | 380,000/307,800 | 2103 | 1938 | Throwaway | (8) 20x24x2 |
(a) Units are AHRI Certified to AHRI Standard 340-360 (I-P). Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°F entering wet bulb with minimum external static pressure as determined by rating standard.
(b) For 17.5T high heat option, input rate will de-rate from downflow to horizontal.
(c) Optional field-installed and factory MERV 13 filters available.
Table 3: Unit MCA and MOP Electrical Data (Standard Indoor Fan Motor - Cooling or Gas Heat)
E/GDK | Volts | Minimum Circuit Ampacity(a) | Maximum Fuse Size or Maximum Circuit Breaker |
---|---|---|---|
180 | 208-230 | 70 | 100 |
460 | 35 | 45 | |
575 | 28 | 40 | |
210 | 208-230 | 91 | 125 |
460 | 44 | 60 | |
575 | 36 | 50 | |
240 | 208-230 | 104 | 125 |
460 | 51 | 70 | |
575 | 39 | 50 | |
300 | 208-230 | 121 | 150 |
460 | 58 | 80 | |
575 | 43 | 50 |
(a) Values do not include power exhaust values.
Table 4: Unit Indoor Fan Data
E/GDK | Volts | Standard HP - RPM | Oversized HP - RPM |
---|---|---|---|
180 | 208-230/3 | 3 - 1750 | 5 - 3450 |
460/3 | 5 - 3450 | 7.5 - 3450 | |
575/3 | 5 - 3450 | 7.5 - 3450 | |
210 | 208-230/3 | 5 - 3450 | 7.5 - 3450 |
460/3 | 7.5 - 3450 | 10 - 1750 | |
575/3 | 7.5 - 3450 | 10 - 1750 | |
240 | 208-230/3 | 7.5 - 3450 | 10 - 1750 |
460/3 | 7.5 - 3450 | 10 - 1750 | |
575/3 | 7.5 - 3450 | 10 - 1750 | |
300 | 208-230/3 | 7.5 - 3450 | 10 - 1750 |
460/3 | 7.5 - 3450 | 10 - 1750 | |
575/3 | 7.5 - 3450 | 10 - 1750 |
Unit Dimensions and Clearances
Illustration of a Trane Foundation Packaged Rooftop Unit.
The following diagram illustrates the unit dimensions and clearance requirements.
Diagram illustrating unit dimensions and clearance zones. Labels include: UL (Unit Length), UW (Unit Width), UH (Unit Height), SL (Supply Length), SW (Supply Width), RL (Return Length), RW (Return Width), CL (Curb Length), CW (Curb Width). Clearances are marked as C1, C2, C3, C4, C5.
Diagram showing clearance directions C1 through C5 relative to the unit.
Table 5: Unit Dimensional Data (15 to 25 Tons)
Dimension | Value (inches) |
---|---|
Unit Length UL | 123 1/8 |
Unit Width UW | 86 15/16 |
Unit Height UH | 58 5/8 |
Clearance C1 | 60 |
Clearance C2 | 48 |
Clearance C3 | 36 |
Clearance C4 | 68 |
Clearance C5 | 72 |
Curb Length CL | 117 3/16 |
Curb Width CW | 81 |
Supply Length SL(a) | 28 9/16 |
Supply Width SW(a) | 69 1/2 |
Return Length RL(a) | 22 1/4 |
Return Width RW(a) | 77 |
(a) Dimensions are for curb openings and not duct inserts. Reference the product catalog for duct insert dimensions.
Curb Compatibility Matrices
Table 6: Curb Compatibility Matrix - Gas Heat(a)
Foundation Tons | Foundation Model No. | Carrier Model No. |
---|---|---|
15 | G*K180 | 48TJD016, 48TJE016, 48TJF016, 48HJD017, 48HJF017, 48TMD016, 48TMF016, 48DP016, 48DR016 |
17.5 | G*K210 | 48TJD020, 48TJF020, 48TMD020, 48TMF020, 48DP020 |
20 | G*K240 | 48TJD024, 48TJE024, 48TJF024, 48TMD025, 48TMF025, 48HJD025, 48HJF025 |
25 | G*K300 | 48TJD028, 48TJE028, 48TJF028, 48TMD028, 48TMF028 |
(a) Data is subject to change. Data pulled from publicly available data via competitive websites.
Table 7: Curb Compatibility Matrix - Electric Heat(a)
Foundation Tons | Foundation Model No. | Carrier Model No. |
---|---|---|
15 | E*K180 | 50TJ016, 50TM016, 50DP016, 50HJ017 |
17.5 | E*K210 | 50DP020, 50TJ020, 50TM020 |
20 | E*K240 | 50TJ024, 50TM025, 50HJ025 |
25 | E*K300 | 50TJ028, 50TM028 |
(a) Data is subject to change. Data pulled from publicly available data via competitive websites.