Quick Reference Guide: Trane Foundation™ Packaged Rooftop Units

Cooling and Gas/Electric, 15 to 25 Tons

Copyright and Trademarks

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

All trademarks referenced in this document are the trademarks of their respective owners.

Model Numbers: EDK, GDK

Used With: Cooling Only (Electric Heat Optional), Gas Heat Unit

Publication Date: September 2024

Document ID: RT-PRC127A-EN

List of Options

Note: Most Factory Installed Options are available for downflow air discharge units only. Verify with ordering system for availability.

Table 1: List of Options

Factory Installed Options

(a) Requires an economizer. (b) Some field set up required. (c) Must be ordered with Through-the-Base Electrical option.

Field Installed Options

Performance Data

Table 2: 15 to 25 Tons Packaged Rooftop Performance Data (Gas or Electric Heat)

E/GDKNominal Size (Ton)Cooling Performance(a) Gross Cooling CapacityCooling Performance(a) AHRI Net Cooling CapacityCooling Performance(a) Nominal Airflow CFM / AHRI Rated CFMCooling Performance(a) EERCooling Performance(a) IEER (Multi-Speed Fan)Gas Heating Performance(b) Low Heat (Input/Output) - (MBh)Gas Heating Performance(b) Medium Heat (Input/Output) - (MBh)Gas Heating Performance(b) High Heat (Input/Output) - (MBh)Other Information Net Weight (Lbs) - Gas HeatOther Information Net Weight (Lbs) - Electric HeatOther Information Filters - Type Furnished(c)Other Information Number and Size Recommended
EDK18015188,000182,00060001114.2240,000/194,000320,000/259,000350,000/283,50020541891Throwaway(8) 20x24x2
GDK18015188,000182,000600010.814240,000/194,000320,000/259,000350,000 (Horizontal)/307,800 (Downflow), 283,500 (Horizontal)(b)20541891Throwaway(8) 20x24x2
EDK21017.5212,000206,00056001114.2240,000/194,000320,000/259,000380,000 (Downflow), 350,000 (Horizontal)/307,800 (Downflow), 283,500 (Horizontal)(b)20691896Throwaway(8) 20x24x2
GDK21017.5212,000206,000560010.814240,000/194,000320,000/259,000380,000/308,00020691896Throwaway(8) 20x24x2
EDK24020250,000240,00080001013.2240,000/194,000320,000/259,000380,000/307,80020671902Throwaway(8) 20x24x2
GDK24020250,000240,00080009.813240,000/194,000320,000/259,000380,000/307,80020671902Throwaway(8) 20x24x2
EDK30025280,000266,00090001013.2240,000/194,000320,000/259,000380,000/308,00021031938Throwaway(8) 20x24x2
GDK30025280,000266,00090009.813240,000/194,000320,000/259,000380,000/307,80021031938Throwaway(8) 20x24x2

(a) Units are AHRI Certified to AHRI Standard 340-360 (I-P). Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°F entering wet bulb with minimum external static pressure as determined by rating standard.

(b) For 17.5T high heat option, input rate will de-rate from downflow to horizontal.

(c) Optional field-installed and factory MERV 13 filters available.

Table 3: Unit MCA and MOP Electrical Data (Standard Indoor Fan Motor - Cooling or Gas Heat)

E/GDKVoltsMinimum Circuit Ampacity(a)Maximum Fuse Size or Maximum Circuit Breaker
180208-23070100
4603545
5752840
210208-23091125
4604460
5753650
240208-230104125
4605170
5753950
300208-230121150
4605880
5754350

(a) Values do not include power exhaust values.

Table 4: Unit Indoor Fan Data

E/GDKVoltsStandard HP - RPMOversized HP - RPM
180208-230/33 - 17505 - 3450
460/35 - 34507.5 - 3450
575/35 - 34507.5 - 3450
210208-230/35 - 34507.5 - 3450
460/37.5 - 345010 - 1750
575/37.5 - 345010 - 1750
240208-230/37.5 - 345010 - 1750
460/37.5 - 345010 - 1750
575/37.5 - 345010 - 1750
300208-230/37.5 - 345010 - 1750
460/37.5 - 345010 - 1750
575/37.5 - 345010 - 1750

Unit Dimensions and Clearances

Illustration of a Trane Foundation Packaged Rooftop Unit.

The following diagram illustrates the unit dimensions and clearance requirements.

Diagram illustrating unit dimensions and clearance zones. Labels include: UL (Unit Length), UW (Unit Width), UH (Unit Height), SL (Supply Length), SW (Supply Width), RL (Return Length), RW (Return Width), CL (Curb Length), CW (Curb Width). Clearances are marked as C1, C2, C3, C4, C5.

Diagram showing clearance directions C1 through C5 relative to the unit.

Table 5: Unit Dimensional Data (15 to 25 Tons)

DimensionValue (inches)
Unit Length UL123 1/8
Unit Width UW86 15/16
Unit Height UH58 5/8
Clearance C160
Clearance C248
Clearance C336
Clearance C468
Clearance C572
Curb Length CL117 3/16
Curb Width CW81
Supply Length SL(a)28 9/16
Supply Width SW(a)69 1/2
Return Length RL(a)22 1/4
Return Width RW(a)77

(a) Dimensions are for curb openings and not duct inserts. Reference the product catalog for duct insert dimensions.

Curb Compatibility Matrices

Table 6: Curb Compatibility Matrix - Gas Heat(a)

Foundation TonsFoundation Model No.Carrier Model No.
15G*K18048TJD016, 48TJE016, 48TJF016, 48HJD017, 48HJF017, 48TMD016, 48TMF016, 48DP016, 48DR016
17.5G*K21048TJD020, 48TJF020, 48TMD020, 48TMF020, 48DP020
20G*K24048TJD024, 48TJE024, 48TJF024, 48TMD025, 48TMF025, 48HJD025, 48HJF025
25G*K30048TJD028, 48TJE028, 48TJF028, 48TMD028, 48TMF028

(a) Data is subject to change. Data pulled from publicly available data via competitive websites.

Table 7: Curb Compatibility Matrix - Electric Heat(a)

Foundation TonsFoundation Model No.Carrier Model No.
15E*K18050TJ016, 50TM016, 50DP016, 50HJ017
17.5E*K21050DP020, 50TJ020, 50TM020
20E*K24050TJ024, 50TM025, 50HJ025
25E*K30050TJ028, 50TM028

(a) Data is subject to change. Data pulled from publicly available data via competitive websites.

Models: EDK180, GDK180, EDK210, GDK210, EDK240, GDK240, EDK300, GDK300, EDK180 Foundation Packaged Rooftop Units, EDK180, Foundation Packaged Rooftop Units, Packaged Rooftop Units, Rooftop Units, Units

PDF preview unavailable. Download the PDF instead.

RT-PRC127A-EN 09152024 Adobe PDF Library 17.0

Related Documents

Preview Trane Foundation™ Packaged Rooftop Units: Installation, Operation, and Maintenance Guide
Comprehensive guide for Trane Foundation™ Packaged Rooftop Units (15-25 Tons, Cooling Only with Electric Heat). Covers installation, operation, maintenance, safety warnings, and technical specifications for models like EDK180-300.
Preview Trane Foundation Series 3-5 Ton Packaged Rooftop Units: Quick Reference Guide
Quick reference guide for Trane Foundation Series 3 to 5 Ton packaged rooftop units, covering cooling and gas/electric models. Includes performance, electrical, fan, and dimensional data.
Preview Trane Foundation Series Packaged Rooftop Units: Cooling and Gas/Electric 15-25 Tons Quick Reference
A quick reference guide for Trane Foundation Series packaged rooftop units, covering cooling and gas/electric models from 15 to 25 tons. Includes specifications, options, and compatibility data.
Preview Trane & American Standard Priority Series Packaged Gas/Electric HVAC Units: Installation, Operation, and Maintenance Manual
Comprehensive guide for Trane and American Standard Priority Series 2-5 Ton Packaged Gas/Electric HVAC units (R-454B refrigerant). Covers installation, operation, maintenance, safety, and specifications for models like 5YCZ5024A, 5YCZ5030A, 5YCZ5036A, 5YCZ5042A, 5YCZ5048A, and 5YCZ5060A.
Preview Trane Foundation 3-5 Ton Packaged Rooftop Units Quick Reference Guide
Quick reference guide for Trane Foundation 3 to 5 Tons Packaged Rooftop Units, covering cooling and gas/electric performance data, options, and unit dimensions.
Preview Trane 15 SEER Convertible Single Packaged Heat Pump Product Data
Comprehensive product data, specifications, optional equipment, and wiring information for Trane's 15 SEER Convertible Single Packaged Heat Pump units, covering models 4WCY5024A1000A through 4WCY5060A1000A.
Preview Trane Precedent™ Rooftop Air Conditioners | eFlex™ Technology Product Catalog
Explore the Trane Precedent™ series of packaged rooftop air conditioners, featuring eFlex™ Technology for cooling and gas/electric applications. This catalog details units from 3 to 10 tons (60 Hz), highlighting advanced controls, performance specifications, and key features for light commercial HVAC needs.
Preview Trane Foundation™ Packaged Rooftop Air Conditioners Installation, Operation, and Maintenance Guide
This comprehensive manual provides essential guidance for the installation, operation, and maintenance of Trane Foundation™ Packaged Rooftop Air Conditioners. Designed for cooling-only applications with electric heat, these units are available in capacities ranging from 15 to 25 tons, operating at 60 Hz.