Trane TPEFYW027MA1W0A: Medium Static HVRF Ducted Indoor Unit
Manufacturer: Mitsubishi Electric Trane HVAC US LLC
General Features
- Dual set point functionality
- Multiple fan speed settings
- Auto fan mode
- 9-7/8" (250mm) high for low ceiling heights
- Built-in condensate lift; lifts to 27-9/16" (700 mm)
- Ducted fan coil supporting multiple configurations for flexible installation
- Hydronic based indoor coil
- Built-in Manual Air Vent
Specifications
Specification | Unit Type | System | BTU/H | TPEFYW027MA1W0A | |
---|---|---|---|---|---|
Cooling capacity (Nominal)¹ | BTU/H | 27,000 | |||
Heating capacity (Nominal)¹ | BTU/H | 30,000 | |||
Power source | Cooling | Voltage, Phase, Hertz | 208/230V, 1-phase, 60 Hz | ||
Power Consumption | Heating | kW | 0.142 | ||
Cooling | kW | 0.140 | |||
Current | Heating | A | 1.24/1.12 | ||
MCA | Cooling | A | 1.24/1.12 | ||
Maximum Overcurrent Protection (MOCP) | Heating | A | 2.88/2.88 | ||
Recommended Fuse Size | A | 15 | |||
External finish | A | 15 | |||
External Dimensions | In. [mm] | 43-5/16 x 28-7/8 x 9-7/8 [1,100 x 732 x 250] | |||
Net weight | Lbs [kg] | 67 [30] | |||
Heat exchanger | Type x quantity | Cross fin (Aluminum fin and copper tube) | |||
Fan | External Static pressure | Selectable; 0.14, 0.2, 0.28, 0.4, 0.6 In. WG; factory set to 0.2 In. WG | |||
Airflow rate | CFM | 618-742-883 | |||
Motor type | DC brushless motor | ||||
Motor Output | kW | 0.121 | |||
Motor FLA | A | 1.4 | |||
Sound pressure level (Measured in anechoic room) | dB(A) | 31-35-39 | |||
Air filter | In. [mm] | PP Honeycomb fabric (washable) | |||
Diameter of drain pipe | In. [mm] | O.D. 1-1/4 [32] | |||
Drain lift mechanism | 27-9/16 [700] | ||||
Connectable HBC Controller | CMB-WP-NU-AA, CMB-WP-NU-AB | ||||
Design Pressure | PSI (Mpa) | 145/1 | |||
Diameter of Water Pipe Connections (O.D.) | Supply Connection (O.D.) | mm | 22 | ||
Return Connection (O.D.) | mm | 22 | |||
Water Volume | Gallons (Liters) | 0.554 (2.1) |
Dimensions
Dimensions are provided in millimeters (mm) and inches (in.).
Model | A | B (Suspension bolt pitch) | C | D (Duct) | E | F | G |
---|---|---|---|---|---|---|---|
TPEFYW06,08,12MA1W0A | 660 (26) | 754 (29-11/16) | 800 (31-1/2) | 700 (27-9/16) | 600 (23-5/8) | 658 (25-15/16) | 7 |
TPEFYW15MA1W0A | 800 (31-1/2) | 954 (37-9/16) | 1000 (39-3/8) | 860 (33-7/8) | 800 (31-1/2) | 858 (33-13/16) | 9 |
TPEFYW18,24,27,30MA1W0A | 1000 (39-3/8) | 1154 (45-7/16) | 1200 (47-1/4) | 1060 (41-3/4) | 1000 (39-3/8) | 1058 (41-11/16) | 11 |
TPEFYW36MA1W0A | 1300 (51-3/16) | 1454 (57-1/4) | 1500 (59-1/16) | 1360 (53-9/16) | 1300 (51-3/16) | 1358 (53-1/2) | 14 |
TPEFYW48MA1W0A | 1500 (59-1/16) | 1654 (65-1/8) | 1700 (66-15/16) | 1560 (61-7/16) | 1500 (59-1/16) | 1558 (61-3/8) | 16 |
Diagram Description: The diagram shows the side, top, and bottom views of the indoor unit, illustrating dimensions for piping, air outlets, suspension points, and control boxes. Key dimensions include overall width, height, depth, and specific locations for water pipe connections and drain pipes.
Indoor Unit Accessories
Category | Item | Model Number |
---|---|---|
Control Interface | Deluxe Wired MA Remote Controller | TAR-41MAAU |
Simple MA Remote Controller | TAC-YT53CRAU-J | |
Wired Remote Controller | Smart ME Remote Controller - Backlit touchscreen | TAR-U01MEDU-K |
Touch MA Controller | TAR-CT01MAU-SB | |
Wireless MA Remote Controller | TAR-FL32MA-E | |
Wireless Remote Controller | Wireless Remote Controller | PAR-SL101A-E |
Condensate | Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended] | X87-721 |
Blue Diamond (MaxiBlue Advanced) Mini Condensate Pump w/ Reservoir & Sensor (110V) up to 48,000 BTU/H [recommended] | X87-711 | |
Blue Diamond (MegaBlue Advanced) Condensate Pump w/ Reservoir & Sensor | X87-835 | |
Blue Diamond Alarm Extension Cable-6.5 Ft. | C13-192 | |
Blue Diamond MultiTank - collection tank for use with multiple pumps | C21-014 | |
Blue Diamond Sensor Extension Cable 15 Ft. | C13-103 | |
Drain Pan Level Sensor/Control | SS610E | |
Sauermann Condensate Pump | S130-230 | |
Control Interface | 3-Pin Connector | CN24RELAY-KIT-CM3 |
Connector and wire for Operation status/error using CN51 | PAC-715AD | |
Disconnect Switch (30A/600V/UL) [fits 2" X 4" utility box] - White | PAC-725AD | |
Filter Box | Filter Box with MERV 13 Filter | TAZ-MS303W |
HBC Controller | Hybrid VRF Main BC 16 Port | TCMBM1016VA11N4 |
Hybrid VRF Main BC 8 Port | TCMBM0108VA11N4 | |
Hybrid VRF Sub BC 16 Port | TCMBS1016VB11N4 | |
Hybrid VRF Sub BC 8 Port | TCMBS0108VB11N4 | |
HVRF Accessories | (2x) Isolation Ball Valve and (2x) 22mm Compression Fitting | KIT2-NA10883-CAL |
25mm Isoflow Multi, 25m Coil w/ 1" Titan | 13630061001-REH | |
25mm PVDF SDR11 Sleeve (Box QTY 50) | 11803271001-REH | |
25mm SDR11 Coupling (Bag QTY 10) | 11690101001-REH | |
25mm SDR11 Elbow (Bag QTY 10) | 11691261001-REH | |
25mm SDR11 x 3/4" FPT Fitting (Bag QTY 1) | 15012451001-REH | |
25mm SDR11 x 3/4" MPT Fitting(Bag QTY 10) | 15012461001-REH | |
25mm x 25mm x 25mm SDR11 Tee (Bag QTY 10) | 11690561001-REH | |
25mm x 25mm x 25mm SDR11 Tee(Bag QTY 10) | 15012471001-REH | |
40mm Isoflow Multi, 5m Stick w/ 1.5" Titan | 13630071001-REH | |
40mm PVDF SDR11 Sleeve (Box QTY 25) | 11803291001-REH | |
40mm SDR11 Coupling (Bag QTY 5) | 11690151001-REH | |
40mm SDR11 Elbow (Box QTY 1) | 11691301001-REH | |
40mm SDR11 x 3/4" MPT Fitting (Box QTY 1) | 15012481001-REH | |
40mm x 40mm x 25mm SDR11 Tee (Bag QTY 1) | 11690691001-REH | |
Compact Discal AAV w/ Hydroscopic Cap and Drain Plug | KIT3-NA10884-CAL | |
Copper Press Tailpieces (3/4") | KIT5-NA10881-CAL | |
Drain Valve w/ Brass NPT T-Fitting | KIT4-NA10885-CAL | |
RAUTOOL A-Light2 Kombi Tool KIT | 11094491001-REH |