25 Interchange Way, Vaughan Ontario. L4K 5W3
Phone: 905.660.4655; Fax: 905.660.4113; Web: www.mircom.com
INSTALLATION AND MAINTENANCE INSTRUCTIONS MIX-4045 DUAL RELAY MODULE
About This Manual
This manual is included as a quick reference for installation. For further information on the use of this device with a FACP, please refer to the panel's manual.
Note: This manual should be left with the owner/operator of this equipment.
Module Description
The MIX-4045 Dual Relay module is designed to operate with a listed compatible intelligent fire system control panel. The module can control two independent circuits while using only one module address. The module provides two form C (SPDT) contacts rated at 2A @ 30VDC or 0.5A at 125VAC and a compatible panel can switch discrete contacts by code command. Circuit connections to the relay contacts are not supervised by the module. The module supports group activation capability for fast reaction time. The SLC and non-power limited connections are on opposite sides of the device for easy installation (no need to install an additional barrier). The address of each module is set using the MIX-4090 programmer tool and up to 240 units may be installed on a single loop. The module has a panel controlled LED indicator.
Mounting
Notice: You must disconnect power from the system before installing the module. If this unit is being installed in a system that is currently operational, it is necessary to inform the operator and the local authority that the system will be temporarily out of service.
The MIX-4045 module is intended to be mounted in a standard 4" square back-box (see Figure 2). The box must have a minimum depth of 2 1/8 inches. Surface mounted electrical boxes (BB-400) are available from Mircom.
Figure 1: Module Front
Diagram showing the front of the MIX-4045 module. It features a Programmer Interface section and a panel-controlled LED indicator.
Figure 2: Module Mounting
Diagram illustrating the module's mounting within a standard 4-inch square electrical box. The box is shown with the module installed inside.
Specifications
Specification | Value |
---|---|
Normal Operating Voltage | 15 to 30VDC |
Alarm Current | 3.1mA |
Standby Current | 1.5 mA |
Temperature Range | 32°F to 120°F (0°C to 49°C) |
Humidity | 10% to 93% Non-condensing |
Dimensions | 4 5/8"H x 4 1/4" W x 1 1/8" D |
Mounting | 4" square by 2 1/8" deep box |
Accessories | MIX-4090 Programmer, BB-400 Electrical Box |
Wiring range on all terminals | 22 to 12 AWG |
Wiring
Note: This device should be installed as per applicable requirements of the authorities having jurisdiction.
- Install the module wiring as indicated by the job drawings and appropriate wiring diagrams (see Figure 3 for an example of wiring for two connected devices).
- Use the programmer tool to set the address on the module as indicated on the job drawings.
- Mount the module in the electrical box as shown in Figure 2.
Figure 3: Sample Relay Wiring
Diagram showing sample wiring for the MIX-4045 Dual Relay Module. It illustrates connections from a panel or next device via SLC (SLCout+, SLCout-, SLCin+, SLCin-) to the module's terminals (C2, NO2, NC2, C1, NO1, NC1). The diagram also shows connections for a 24 V DC Supply to Common 1 (C1) and Common 2 (C2). Relay 1 (C1, NC1, NO1) and Relay 2 (C2, NC2, NO2) are depicted. The state of the load connection is shown for normal standby (load disconnected on alarm for NC1, load connected on alarm for NO2) and alarm conditions. Terminal wiring range is 22 to 12 AWG.