Mircom MIX-4045 Dual Relay Module Installation and Maintenance Instructions
Mircom
25 Interchange Way, Vaughan Ontario. L4K 5W3
Phone: 905.660.4655; Fax: 905.660.4113; Web: www.mircom.com

INSTALLATION AND MAINTENANCE INSTRUCTIONS MIX-4045 DUAL RELAY MODULE

About This Manual

This manual is included as a quick reference for installation. For further information on the use of this device with a FACP, please refer to the panel's manual.

Note: This manual should be left with the owner/operator of this equipment.

Module Description

The MIX-4045 Dual Relay module is designed to operate with a listed compatible intelligent fire system control panel. The module can control two independent circuits while using only one module address. The module provides two form C (SPDT) contacts rated at 2A @ 30VDC or 0.5A at 125VAC and a compatible panel can switch discrete contacts by code command. Circuit connections to the relay contacts are not supervised by the module. The module supports group activation capability for fast reaction time. The SLC and non-power limited connections are on opposite sides of the device for easy installation (no need to install an additional barrier). The address of each module is set using the MIX-4090 programmer tool and up to 240 units may be installed on a single loop. The module has a panel controlled LED indicator.

Mounting

Notice: You must disconnect power from the system before installing the module. If this unit is being installed in a system that is currently operational, it is necessary to inform the operator and the local authority that the system will be temporarily out of service.

The MIX-4045 module is intended to be mounted in a standard 4" square back-box (see Figure 2). The box must have a minimum depth of 2 1/8 inches. Surface mounted electrical boxes (BB-400) are available from Mircom.

Figure 1: Module Front

Diagram showing the front of the MIX-4045 module. It features a Programmer Interface section and a panel-controlled LED indicator.

Figure 2: Module Mounting

Diagram illustrating the module's mounting within a standard 4-inch square electrical box. The box is shown with the module installed inside.

Specifications

SpecificationValue
Normal Operating Voltage15 to 30VDC
Alarm Current3.1mA
Standby Current1.5 mA
Temperature Range32°F to 120°F (0°C to 49°C)
Humidity10% to 93% Non-condensing
Dimensions4 5/8"H x 4 1/4" W x 1 1/8" D
Mounting4" square by 2 1/8" deep box
AccessoriesMIX-4090 Programmer, BB-400 Electrical Box
Wiring range on all terminals22 to 12 AWG

Wiring

Note: This device should be installed as per applicable requirements of the authorities having jurisdiction.

  1. Install the module wiring as indicated by the job drawings and appropriate wiring diagrams (see Figure 3 for an example of wiring for two connected devices).
  2. Use the programmer tool to set the address on the module as indicated on the job drawings.
  3. Mount the module in the electrical box as shown in Figure 2.

Figure 3: Sample Relay Wiring

Diagram showing sample wiring for the MIX-4045 Dual Relay Module. It illustrates connections from a panel or next device via SLC (SLCout+, SLCout-, SLCin+, SLCin-) to the module's terminals (C2, NO2, NC2, C1, NO1, NC1). The diagram also shows connections for a 24 V DC Supply to Common 1 (C1) and Common 2 (C2). Relay 1 (C1, NC1, NO1) and Relay 2 (C2, NC2, NO2) are depicted. The state of the load connection is shown for normal standby (load disconnected on alarm for NC1, load connected on alarm for NO2) and alarm conditions. Terminal wiring range is 22 to 12 AWG.

Models: MIX-4045 Dual Relay Module, MIX-4045, Dual Relay Module, Relay Module, Module

File Info : application/pdf, 2 Pages, 1.30MB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676768794

References

Acrobat Distiller 19.0 (Windows)

Related Documents

Preview Mircom MIX-4090 Device Programmer: Installation and Maintenance Guide
Comprehensive guide for installing and maintaining the Mircom MIX-4090 Device Programmer, detailing its features, operation, address programming, and parameter reading for MIX-4000 series fire alarm devices.
Preview Mircom FX-400 Fire Alarm Control Panel Installation and Operation Manual
This Installation and Operation Manual provides comprehensive guidance for the Mircom FX-400 Addressable Fire Alarm Control Panel (FACP). It details system features, component compatibility, wiring diagrams, configuration options, operational procedures, and troubleshooting tips for ensuring effective fire safety system deployment.
Preview Mircom FX-400 Addressable Fire Alarm Control Panel
Mircom FX-400 is an addressable fire alarm control panel ideal for small to medium-sized installations. This document outlines its features, specifications, and compatible components, including remote annunciators, input modules, and cabinets.
Preview Mircom FX-400 Addressable Fire Alarm Control Panel
Mircom FX-400 is an addressable fire alarm control panel suitable for small to medium applications. This document outlines its features, specifications, and compatible system components.
Preview Mircom FX-3500 Fire Alarm Control Panel Installation and Operation Manual
Comprehensive guide for the installation and operation of the Mircom FX-3500 Addressable Fire Alarm Control Panel, detailing system components, wiring, configuration, and features for effective fire safety.
Preview Mircom MIX-4010 Photoelectric Smoke Detector Installation and Maintenance Guide
Comprehensive installation and maintenance instructions for the Mircom MIX-4010 and MIX-4010-ISO Photoelectric Smoke Detectors, including specifications, wiring diagrams, and operational notes.
Preview Mircom MIX-M501MAP Monitor Module Installation and Maintenance Guide
Installation and maintenance instructions for the Mircom MIX-M501MAP Monitor Module, detailing specifications, mounting, wiring, and general description for fire alarm systems.
Preview Mircom MIX-M501MAPA Monitor Module Installation and Maintenance Instructions
Installation and maintenance guide for the Mircom MIX-M501MAPA Monitor Module, detailing specifications, general description, compatibility, mounting, and wiring.