VENTS Fire Smoke Damper КПД/КПДУ User Manual
Introduction
This user manual is the primary operational document intended for familiarization of technical, service, and operating personnel. It contains information on the purpose, composition, principle of operation, construction, and installation of the КПД/КПДУ product(s) and all its modifications.
Technical and service personnel must have theoretical and practical training in ventilation systems and perform work in accordance with applicable labor protection regulations and construction norms and standards in force in the country.
Safety Requirements
- Before operating and installing the product, carefully read this user manual.
- During installation and operation, comply with the manual's requirements, as well as applicable local and national building, electrical, and technical norms and standards.
- Pay close attention to the warnings in the manual, as they contain information related to your safety.
- Failure to follow the rules and warnings in the manual may result in injury to the user or damage to the product.
- Keep the manual for the entire period of product use after reading it.
- When transferring operation to another user, ensure they also receive this manual.
- Before starting installation and operation, disconnect the product from the power supply.
- Handle the product with care during unpacking.
- Ensure the product is properly grounded.
- Follow safety procedures when working with power tools during installation.
- Do not alter the length of the power cord yourself.
- Do not kink the power cord.
- Avoid damaging the power cord.
- Do not place foreign objects on the power cord.
- Do not route the product's power cord near heating or hot equipment.
- Do not use damaged equipment or conductors when connecting the product to the power grid.
- Do not operate the product outside the temperature range specified in the manual.
- Do not operate the product in aggressive or explosive environments.
- Do not touch control devices with wet hands.
- Do not perform installation or maintenance with wet hands.
- Do not wash the product with water.
- Avoid water ingress into the electrical parts of the product.
- Keep children away from the product during operation.
- Disconnect the product from the power supply before maintenance.
- Do not store flammable or explosive substances near the product.
- Do not open the product while it is operating.
- Do not obstruct the air duct while the product is operating.
- Periodically check the mounting reliability during prolonged use.
- Do not sit on the product or place other objects on it.
- Use the product only for its intended purpose.
Disposal: AFTER THE END OF OPERATION, THE PRODUCT REQUIRES SEPARATE DISPOSAL. DO NOT DISPOSE OF THE PRODUCT WITH UNSORTED MUNICIPAL WASTE.
Purpose
The damper is designed for use in building smoke protection systems for removing combustion products from premises, corridors, halls, vestibules, etc. It can be used in emergency smoke ventilation systems for smoke removal according to building codes (e.g., DBN V.1.1-7) during fires to facilitate evacuation in the initial stages of a fire.
The КПД (single-blade) and КПДУ (multi-blade) fire smoke dampers with a fire resistance rating of 180 minutes at 600°C smoke temperature are manufactured according to TU U 29.1-30637114-015:2010.
Sales and Scope of Delivery
The product is sold through specialized and retail organizations.
Scope of Delivery
Item | Quantity |
Damper | 1 pc. |
User Manual | 1 pc. |
Packaging Box | 1 pc. |
Structure of Designation
Example designation: КПДУ -300x300-1-ΠΒ24-ΒΗ
- Series: Fire smoke damper
- КПД: Single-blade
- КПДУ: Multi-blade
- Passage Width, mm: (e.g., 300, 350, ..., 1400)
- Passage Height, mm: (e.g., 300, 350, ..., 1400)
- Number of Flanges: 1 (one), 2 (two)
- Actuator Type:
- ЕМ220/24: Electromagnet 220/24 V
- ПН24: NENUTEC actuator 24V (2-position)
- ПН230: NENUTEC actuator 230V (2-position)
- ПНП24: NENUTEC actuator 24V (spring-return)
- ПНП230: NENUTEC actuator 230V (spring-return)
- ПВ24: BELIMO actuator 24V (2-position)
- ПВ230: BELIMO actuator 230V (2-position)
- ПВП24: BELIMO actuator 24V (spring-return)
- ПВП230: BELIMO actuator 230V (spring-return)
- ПС24: SIEMENS actuator 24V (2-position)
- ПС230: SIEMENS actuator 230V (2-position)
- ПСП24: SIEMENS actuator 24V (spring-return)
- ПСП230: SIEMENS actuator 230V (spring-return)
- Actuator Location:
- СН (SN): External (except EM220/24)
- ВН (VN): Internal
Technical Specifications
The product is intended for use in enclosed spaces with ambient air temperature from +1°C to +45°C and relative humidity up to 80%. The damper is designed for operation in moderate (P) climate regions, placement category 3, according to DSTU 15150-69.
КПД and КПДУ dampers are manufactured in two modifications: with an electromagnet (can be installed vertically or horizontally) and with an actuator (installation orientation is independent of spatial orientation). The operating position of the dampers can be any in space. Characteristics are maintained with both vertical and horizontal damper blade orientation. Dampers are available in wall-mounted or ducted versions. They can be supplied with one or two flanges.
Characteristic | With Electromagnet | With Actuator (NENUTEC, BELIMO, SIEMENS) | ||||||
220/24V | 24V | 230V | 24V (2-pos) | 230V (2-pos) | 24V (spring) | 230V (spring) | ||
Fire Resistance Limit, min | 180 | 180 | 180 | 180 | 180 | 180 | 180 | |
Nominal Voltage, V/50 Hz | ~220/24 | 24 | 230 | 24 | 230 | 24 | 230 | |
Rated Power, max, VA (depending on actuator) | 200/100 | 10 | 10 | 9/18 | 12/15 | 4/6/10 | 6.5/9/12.5 | |
Protection Degree | IP54 | IP54 | IP54 | IP54 | IP54 | IP54 | IP54 | |
Power Consumption (holding blades in position), W, max (depending on actuator) | 3.5 | 3.5 | 2/2.5 | 2/2.5 | 1 | 1 | 0.7/1.4/2 | 0.9/2/3 |
Power Consumption (returning blades to position), W, max (depending on actuator) | 8.2 | 5.2 | 7/10 | 7/10 | 7.5/13 | 5/8 | 2.5/4/7 | 3/4.5/8 |
Blade Movement Time to Operating Position, sec, max | 2 | 60 | 60 | 60 | 60 | 60 | 60 | |
Blade Return Time to Initial Position, sec, max | 150 | 150 | 150 | 150 | 150 | 150 |
Structure and Principle of Operation
The manufacturer reserves the right to install various actuators that ensure the stated technical parameters of the dampers.
In the closed position, the damper ensures tight contact of the blades with the housing's seating surfaces. The housing is the main load-bearing structure of the damper, with one or two connection flanges on its end surfaces (depending on the version).
The smoke exhaust damper is closed in its normal (standby) position, with its blades flush with the passage cross-section.
When power is supplied to the electromagnet, the blade opens via a spring, after which a limit switch breaks the circuit and disconnects the electromagnet from the power supply. The blade returns to its initial position manually.
In the actuator version, the blade automatically moves to the normal (standby) position when power is supplied to the actuator. In case of fire, a control signal from fire alarms, automatic fire suppression systems, or other sources de-energizes the actuator, and its return spring moves the damper to the open position. The position of the blades can be monitored via indicator lights connected to the actuator's contacts.
If the power supply is disconnected (not due to fire) and then reconnected, the damper blades automatically return to the normal (standby) position.
In the two-wire control version, the damper blades are moved to the OPEN or CLOSED position by an external control signal that applies voltage to the actuator's terminals.
Possible Variants of VENTS Dampers
The following sections describe various configurations of the VENTS dampers, including those with electromagnets and actuators, and with single or double flanges.
VENTS КПД Damper with Electromagnet (220 or 24 V)
Description: Diagrams show the КПД damper with an internal electromagnet. It is available in single-flange (for wall/ceiling mounting) and double-flange (for ducted installation) configurations. For both configurations, after a test or emergency activation, the blades can only be returned to the initial position manually.
VENTS КПД Damper with Actuator (230 or 24 V), External Actuator
Description: Diagrams illustrate the КПД damper with an external actuator. Available with single-flange (for wall/ceiling mounting, any orientation) and double-flange (for ducted installation, any orientation). For dampers with a 2-position actuator, blades move to OPEN/CLOSED via external signal. For spring-return actuators, blades return automatically after test/emergency activation upon power restoration.
VENTS КПД Damper with Actuator (230 or 24 V), Internal Actuator
Description: Diagrams show the КПД damper with an internal actuator. Available with single-flange (for wall/ceiling mounting, any orientation) and double-flange (for ducted installation, any orientation). Similar operation to the external actuator version regarding 2-position and spring-return mechanisms.
VENTS КПДУ Damper with Electromagnet (220 or 24 V)
Description: Diagrams show the multi-blade КПДУ damper with an internal electromagnet. Available in single-flange (for wall/ceiling mounting) and double-flange (for ducted installation) configurations. Blades return manually after test/emergency activation.
VENTS КПДУ Damper with Actuator (230 or 24 V), External Actuator
Description: Diagrams illustrate the multi-blade КПДУ damper with an external actuator. Available with single-flange (for wall/ceiling mounting, any orientation) and double-flange (for ducted installation, any orientation). Operation is similar to the КПД external actuator version.
VENTS КПДУ Damper with Actuator (230 or 24 V), Internal Actuator
Description: Diagrams show the multi-blade КПДУ damper with an internal actuator. Available with single-flange (for wall/ceiling mounting, any orientation) and double-flange (for ducted installation, any orientation). Operation is similar to the КПД internal actuator version.
Diagrammatic Representation of Dimensions: The following diagrams provide detailed dimensional information (B, H, flange extensions, mounting hole sizes) for various configurations of КПД and КПДУ dampers with electromagnets and actuators, including single and double flange options.
Additional Options
Additional equipment for installation is sold separately and can be purchased at the customer's request.
Smoke Exhaust Grille RD
The smoke exhaust grille can be used to fully cover the internal cavity of the damper from external view, especially where strict decorative requirements are absent. It also protects the damper and its actuator from unauthorized access. The grille features one row of fixed 45° air louvers. It can be made of galvanized steel, carbon steel with special coating (M), stainless steel (N), or aluminum.
Anti-Vandal Mesh
Used to protect the actuator from possible external influences.
Decorative Aluminum Grille
For enhanced design requirements, a decorative grille made of aluminum can be supplied. It also features fixed 45° louvers and is treated with polymer coating or anodized for atmospheric protection.
Mounting Frame
Facilitates damper installation in wall openings, provides additional rigidity, and prevents damper deformation during mounting. Installation is done directly with self-tapping screws to the mounting frame flange.
Installation and Connection
⚠️ Before installation, ensure the housing is free of foreign objects, such as film or paper.
⚠️ During installation, ensure minimal access to the unit for servicing or repair.
Dampers are not intended for installation in air ducts and channels of premises with fire and explosion hazard categories A and B, in local exhaust systems for removing fire hazardous mixtures, or in systems containing media aggressive to ordinary carbon steels, or media with sticky and fibrous materials.
Fire dampers are intended only for installation in systems that are regularly cleaned to prevent the formation of combustible deposits.
Installation of the damper in a fire-resistant enclosing structure must be carried out according to DBN V.1.1-7-2003. The fire resistance of the seal must not be lower than that of the enclosing structure.
Installation Recommendations:
- For Vertical Structural Elements: Diagrams show mounting configurations for vertical walls and shafts, indicating clearance requirements and the use of sealing materials.
- For Horizontal Structural Elements: Diagrams illustrate mounting in horizontal structures like ceilings, showing placement and clearances.
- For Ducted Installation: Diagrams depict installation within air ducts, showing connections and required space.
Important Note on Installation: When preparing the damper for installation, it is crucial to brace the damper housing with wooden spacers to prevent possible warping, twisting, or deformation of the housing geometry, which could lead to blade jamming and loss of functionality. After the damper is built into the smoke shaft, fire wall, or ceiling, and the sealant has fully cured, remove the wooden spacers. The blades should then open freely without friction.
Ground the damper, connect the electromagnet or actuator (depending on the model) to the automatic fire suppression system, and test the damper's operation.
Electrical Connection
⚠️ BEFORE PERFORMING ANY WORK ON THE PRODUCT, THE POWER SUPPLY MUST BE DISCONNECTED.
CONNECTION OF THE PRODUCT TO THE MAINS MUST BE CARRIED OUT BY A QUALIFIED ELECTRICIAN AUTHORIZED FOR WORK WITH ELECTRICAL INSTALLATIONS UP TO 1000 V, AFTER STUDYING THIS USER MANUAL.
Nominal electrical parameters of the product are indicated on the manufacturer's label.
The product is designed for connection to a single-phase AC power grid with a voltage of 220 V/24 (50 Hz). The КПДУ or КПД damper should be powered from a central fire extinguishing control panel using a cable with copper conductors (8x0.5 mm²) according to the schematic diagram connected to terminal block X1.
Electrical Connection Diagram for КПД/КПДУ Damper with Electromagnet
Description: Diagram shows wiring for a damper with an electromagnet (YA1), limit switches (SQ1), and control buttons (SB1). Terminal block X1 is shown with connections for power (L, N, PE), limit switches (1C, 2C, 4C, 5C), and electromagnet control (PK, SB1, SA1).
Electrical Connection Diagram for КПД/КПДУ Damper with Spring-Return Actuator
Description: Diagram illustrates the connection for a damper with a spring-return actuator. It shows the electric motor (M) and a contact group. Terminals 1 and 2 are for power supply (neutral and phase for closing). Terminals S1-S6 are for limit switches signaling end positions.
Electrical Connection Diagram for КПД/КПДУ Damper with 2-Position Actuator
Description: Diagram shows wiring for a damper with a 2-position actuator. It includes the electric motor (M) and a contact group. Terminals 1 and 2,3 are for power supply (neutral and phase for closing/opening). Terminals S1-S6 are for limit switches signaling end positions.
Operation Sequence: When the contact of the automatic fire suppression system (PK) is closed, the damper electromagnet (YA1) is activated, opening the blade. This releases the limit switch (SQ1) plunger, which breaks the circuit and disconnects the electromagnet from the power supply. Button SB1 is used for manual blade opening.
Maintenance
⚠️ PRODUCT MAINTENANCE IS PERMITTED ONLY AFTER DISCONNECTING IT FROM THE POWER SUPPLY. ENSURE THE PRODUCT IS DISCONNECTED FROM THE POWER SUPPLY BEFORE REMOVING ANY COVERS.
Damper maintenance involves preventive inspections and functional checks. The frequency of maintenance should comply with the established schedules for the fire protection complex of the facility.
Perform maintenance with the automatic fire suppression system circuit disconnected; set the SA toggle switch to the "power off" position.
Preventive inspections include necessary repair and restoration work, as well as cleaning the internal parts of the damper (if debris is present).
Functional Checks:
- Electromagnet version: Check by supplying voltage to the electromagnet; the damper blades should open.
- Spring-return version: Check by disconnecting the power supply.
- Two-position actuator version: Check by supplying a control signal.
Troubleshooting
Problem | Likely Cause | Solution |
Blade jamming, incomplete opening. | Damper installed in an enclosing structure with housing distortion. | Reinstall the damper, ensuring flatness and uniform diagonal cross-section (deviation not exceeding 3 mm). |
Jamming due to dust or foreign objects in the damper passage. | Clean the damper passage of dust or foreign objects. | |
Electromagnet does not activate when power is supplied from the automatic fire suppression system or when the opening button is pressed. | SA toggle switch is in the "power off" position. | Set the SA toggle switch to the "power on" position. |
Storage and Transportation Rules
Store the product in its original packaging in a ventilated room at temperatures from +5°C to +40°C and relative humidity not exceeding 70%. Air containing corrosive vapors and impurities that can damage insulation and seals is prohibited.
Use appropriate lifting equipment for loading/unloading operations to prevent product damage. Follow handling requirements for such cargo.
Transport the product by any means of transport, provided it is protected from atmospheric precipitation and mechanical damage. Transport is allowed only in the working position.
Loading and unloading should be done without sudden jolts or impacts.
Before initial startup after transportation in low temperatures, the product must be kept at operating temperature for at least 3-4 hours.
Manufacturer's Warranty
The manufacturer provides a warranty period of 24 months from the date of sale, provided the user adheres to the transportation, storage, installation, and operation rules.
In case of product malfunctions due to manufacturing defects within the warranty period, the user is entitled to free repair. Warranty repair involves correcting defects to ensure the product's intended use during the warranty period, through replacement or repair of components.
Warranty does not cover:
- Periodic maintenance.
- Product installation/disassembly.
- Product adjustment.
For warranty repair, the user must provide the product, the user manual with the sales date noted, and the proof of purchase document. The product model must match the model specified in the user manual.
For warranty service in Ukraine, contact the Manufacturer: LLC "Ventilation Systems", Ukraine, 01054, Kyiv, M. Kotsyubynskyi St., 1. Tel.: +380 44 401 62 90, e-mail: service@vents.com.ua. Information on equipment shipping for warranty repair in Ukraine is available at: https://vents.ua/service-support/.
The manufacturer's warranty does not apply in the following cases:
- Failure to provide the product in complete set as per the manual, including user disassembly of components.
- Product model or marking mismatch with data on packaging and in the manual.
- Untimely product maintenance.
- Damage to the product's housing or internal parts.
- Unauthorized modifications or alterations to the product's design.
- Use of components or parts not provided by the manufacturer.
- Product misuse.
- User violation of installation rules.
- User violation of operating rules.
- Connecting the product to a power grid with voltage different from that specified in the manual.
- Product failure due to power surges.
- User performing self-repair.
- Repair performed by unauthorized persons.
- Expiration of the warranty period.
- User violation of transportation rules.
- User violation of storage rules.
- Malicious actions by third parties towards the product.
- Product failure due to force majeure circumstances (fire, flood, earthquake, war, military actions of any kind, blockade).
- Absence of seals, if provided for by the manual.
- Failure to provide the user manual with the sales date noted.
- Absence of proof of purchase document.
Adhere to the requirements of this user manual to ensure long, uninterrupted product operation.
Warranty claims will be considered after the user provides the product, warranty card, proof of purchase, and the user manual with the sales date noted.
Certificates
Acceptance Certificate
Product Type: Fire smoke damper
Model:
Serial Number:
Date of Manufacture:
Inspector's Stamp:
Seller Information
Store Name:
Address:
Phone:
E-mail:
Date of Purchase:
I have received the product in full комплектація with the user manual, have been informed of the warranty conditions, and agree.
Buyer's Signature:
[Space for seller's stamp]
Installation Certificate
Product:
Installed and connected to the electrical grid according to the requirements of this user manual.
Company Name:
Address:
Phone:
Installer's Full Name:
Installation Date:
Signature:
Installation work complies with all applicable local and national building, electrical, and technical norms and standards. I have no remarks regarding the product's operation.
Signature:
[Space for installer's stamp]