USER'S MANUAL

DuoVent 150 EC, DuoVent 200 EC, DuoVent 250 EC, DuoVent 315 EC, DuoVent 355 EC, DuoVent 400 EC

Duct redundancy fan unit in a sound-insulated casing

Contents

Safety Requirements

This user's manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about purpose, technical details, operating principle, design, and installation of the DuoVent 150/200/250/315/355/400 EC unit and all its modifications. Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.

All operations described in this manual must be performed by qualified personnel only, properly trained and qualified to install, make electrical connections and maintain ventilation units. Do not attempt to install the product, connect it to the mains, or perform maintenance yourself. This is unsafe and impossible without special knowledge.

Disconnect the power supply prior to any operations with the unit.

All user's manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.

Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.

Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation. The present user's manual should be carefully read before beginning works.

Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.

While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise.

Misuse of the unit and any unauthorised modifications are not allowed.

Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).

Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.

Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.

Do not close or block the intake or extract vents in order to ensure the efficient air flow.

Do not sit on the unit and do not put objects on it.

The information in this user's manual was correct at the time of the document's preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.

Never touch the unit with wet or damp hands.

Never touch the unit when barefoot.

BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES, READ THE RELEVANT USER MANUALS.

This unit is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety. Children should be supervised to ensure that they do not play with the unit.

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved

Cleaning and user maintenance shall not be made by children without supervision

Children shall not play with the appliance.

Connection to the mains must be made through a disconnecting device, which is integrated into the fixed wiring system in accordance with the wiring rules for design of electrical units, and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.

Ensure that the unit is switched off from the supply mains before removing the guard.

Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.

Fixing means for attachment to the ceiling such as hooks or other devices shall be fixed with a sufficient strength to withstand 4 times the weight of the appliance.

The mounting of the suspension system shall be performed by the manufacturer, its service agent or suitably qualified persons.

The appliance is to be installed so that the blades are more than 2.3m above the floor.

Disposal: The product must be disposed of separately at the end of its service life. Do not dispose of the unit as unsorted domestic waste.

Purpose

The duct redundancy fan unit in a sound-insulated casing is designed for supply and exhaust ventilation of domestic, public and industrial premises with high requirements to the noise level and with limited space for mounting. The fan unit is a component part and cannot be used for stand-alone operation. It is rated for continuous operation.

Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot and oil particles or environments favourable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).

Delivery Set

NameNumber
Fan unit1 pc.
User's manual1 pc.
Packing box1 pc.

Designation Key

DuoVent 315 EC

DuoVent - a series of sound-insulated double fan units for round air ducts.

Technical Data

The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to 80% at 25 °C. The maximum permissible concentration of solids and dust in the handled air is 10 mg/m³. The unit is rated as a Class I electrical appliance. The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.

Diagram Description: The diagrams show the overall and connecting dimensions of the fan unit. Key dimensions include L, L1, L2, L3, H, A, A1, A2, and ØD (spigot diameter).

ModelL [mm]L1 [mm]L2 [mm]L3 [mm]H [mm]A [mm]A1 [mm]A2 [mm]ØD [mm]Weight [kg]
DuoVent 150 EC97585074832162159354014928
DuoVent 200 EC97585074837579176371019939
DuoVent 250 EC110297987741780177372024953
DuoVent 315 EC12931170106853452010921065101031497
DuoVent 355 EC13341170106853452010921065101035497
DuoVent 400 EC135811941092546551118211541101399129

Technical specifications of the particular model are indicated on the unit casing.

Design and Operating Principle

The casing of the fan unit is made of galvanized steel. The fan unit is equipped with a removable bottom cover for easy installation and maintenance. It is attached with screws. Heat- and sound-insulation is made of non-flammable material. The round connecting spigots are rubber sealed.

Inside the fan unit, there are two mixed-type duct fans with energy-efficient motors. The fan motors have built-in controls. The low-noise motors with ball bearings with specially selected grease ensure maintenance-free operation of the fan.

When the unit is in operation, one of the fans is always running, with the second fan as a backup. Depending on the operation algorithm of the control automatics, the fans can be switched on alternately at different time intervals. This ensures uninterrupted ventilation: in case of failure of one fan, the second one automatically switches on. Switching modes is carried out using a controller, which is not included in the basic delivery set and must be ordered separately.

In order to prevent air backflow through a non-functioning fan, a swivel damper is installed inside the casing. When one of the fans is switched on, the damper rotates due to the air flow from the fan and closes the duct of the inoperative fan.

Diagram Description: The main design elements of the fan unit are illustrated. These include:

Mounting and Set-up

[Warning] Before mounting, make sure the casing does not contain any foreign objects (e.g., foil, paper).

[Warning] While installing the unit, ensure convenient access for subsequent maintenance and repair.

Duct fans are designed for use with round air ducts. The units are installed in the gap between the ducts. Installation is only possible in the horizontal position, taking into account the direction of air flow, which is indicated by an arrow on the casing.

Installation of DuoVent 150 EC, DuoVent 200 EC, and DuoVent 250 EC models is carried out at 4 points using the mounting brackets. The DuoVent 315 EC, DuoVent 355 EC and DuoVent 400 EC models each have 6 mounting brackets (refer to the "Technical data" section).

It is recommended to use anchor threaded rods with nuts to fix the fan unit to the ceiling. Fasteners for fan mounting are not included in the delivery set and should be ordered separately. When choosing fasteners, consider the material of the mounting surface as well as the weight of the fan unit (refer to the "Technical data" section).

Fasteners for unit mounting should be selected by the service technician.

The safety cables on the removable service panels can be moved to the opposite side of the casing for the convenience of service work, depending on the installation location of the fan unit.

Diagram Description: The diagram shows the mounting method using a threaded rod, vibration-absorbing insert, washer, and nuts.

Caution:

Connection to Power Mains

[Warning] Disconnect the power supply prior to any operations with the unit.

[Warning] Connection of the unit to power mains is allowed by a qualified electrician with a work permit for electrical units up to 1000 V after careful reading of the present user's manual.

The rated electrical parameters of the unit are given on the manufacturer's label.

[Warning] Any tampering with the internal connections is prohibited and will void the warranty.

Diagram Description: The figures show the terminal boxes and wiring diagrams for the fans. For DuoVent 150 EC, 200 EC, 250 EC, 315 EC, the wiring involves N (Blue), L (Brown), and grounding. For DuoVent 355 EC, 400 EC, wiring includes Yellow-green for ground, L (Brown), and N (Blue). Both types have connections for +10V (Red), TACH (White), CTR (Yellow), and GND (Blue) for external control devices.

Technical Maintenance

[Warning] Disconnect the unit from power supply before any maintenance operations!

[Warning] Make sure the unit is disconnected from power mains before removing the protection.

[Warning] Prior to commencing any technical maintenance, put up a prohibitory sign on the fan starting panel: "DO NOT SWITCH ON! MEN AT WORK!"

[Warning] Avoid liquid spills on the motor! Do not use aggressive solvents and sharp objects for cleaning!

Clean the product surfaces and the impeller of the fans inside the casing regularly (once in 6 months) from dust and dirt. Disconnect the fan unit from power mains prior to any maintenance operations.

Open the service panel of the fan unit and remove dust from the surfaces of the fans and impeller blades. Use a soft brush, cloth, vacuum cleaner, or compressed air for cleaning. Do not use water, aggressive solvents, or sharp objects as they may damage the impeller. It is forbidden to remove or change the location of the balancers on the impeller, as this can lead to increased level of vibration, noise, and reduce the service life of the unit.

During technical maintenance, make sure that there are no visible defects on the unit, the mounting brackets are securely fastened to the fan casing, and the unit is securely mounted.

Troubleshooting

ProblemPossible ReasonsTroubleshooting
The fan (-s) doesn't (don't) start.No power supply.Make sure the power supply line is connected correctly, otherwise troubleshoot a connection error.
Jammed motor.Disconnect the fan from power supply. Troubleshoot the motor jamming. Restart the fan.
The fan has overheated.Disconnect the fan from power supply. Eliminate the cause of overheating. Restart the fan.
Automatic circuit breaker tripping following the fan turning on.Excessive electric current consumption caused by a short circuit.Turn the fan off. Contact the Seller.
The fan impeller is soiled.Clean the impellers.
Noise, vibration.The fan or casing screw connection is loose.Tighten the screw connection of the fan or the casing against stop.
The ventilation system components (air ducts, diffusers, louvre shutters, grilles) are clogged or damaged.Clean or replace the ventilation system components (air ducts, diffusers, louvre shutters, grilles).

Storage and Transportation Regulations

Manufacturer's Warranty

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. It complies with Electromagnetic Compatibility (EMC) Directive 2014/30/EU, Low Voltage Directive (LVD) 2014/35/EU, and CE-marking Council Directive 93/68/EEC.

The manufacturer warrants normal operation of the unit for 24 months after the retail sale date, provided the user observes the transportation, storage, installation, and operation regulations. Should malfunctions occur during the guaranteed period due to the Manufacturer's fault, the user is entitled to get all faults eliminated by the manufacturer through warranty repair at the factory, free of charge. Warranty repair includes work specific to elimination of faults to ensure intended use within the guaranteed period. Faults are eliminated by replacement or repair of unit components.

The warranty repair does not include:

To benefit from warranty repair, the user must provide the unit, the user's manual with the purchase date stamp, and payment paperwork certifying the purchase. The unit model must match the one stated in the user's manual. Contact the Seller for warranty service.

The manufacturer's warranty does not apply to the following cases:

[Important] Following the regulations stipulated herein will ensure a long and trouble-free operation of the unit.

[Important] User's warranty claims shall be subject to review only upon presentation of the unit, the payment document, and the user's manual with the purchase date stamp.

Certificate of Acceptance, Seller Information, Installation Certificate, Warranty Card

This section contains forms for the Certificate of Acceptance, Seller Information, Installation Certificate, and Warranty Card. These forms are intended to be filled out by the seller, installer, and customer to document the unit's delivery, installation, and warranty status.

Certificate of Acceptance: Includes fields for Unit Type, Model, Serial Number, Manufacture Date, and Quality Inspector's Stamp.

Seller Information: Includes fields for Seller, Address, Phone Number, E-mail, and Purchase Date. A statement confirms acceptance of the unit delivery and warranty terms.

Installation Certificate: Includes fields for Company name, Address, Phone Number, Installation Technician's Full Name, and Installation Date. A statement confirms installation according to local and national codes and that the unit operates normally.

Warranty Card: Includes fields for Unit Type, Model, Serial Number, Manufacture Date, Purchase Date, Warranty Period, and Seller.

Models: DuoVent 200 EC, DuoVent 150 EC, DuoVent 355 EC, DuoVent 400 EC, Duct Redundancy Fan Unit in a Sound-Insulated Casing, DuoVent 200 EC Duct Redundancy Fan Unit in a Sound-Insulated Casing, Redundancy Fan Unit in a Sound-Insulated Casing, Sound-Insulated Casing

File Info : application/pdf, 16 Pages, 1.25MB

PDF preview unavailable. Download the PDF instead.

v256en a4 stkr 03 preview

References

Adobe PDF Library 15.0 Adobe InDesign 15.1 (Windows)

Related Documents

Preview VENTS VK EC Centrifugal Fan User's Manual: Installation, Operation, and Maintenance
This user's manual provides detailed guidance on the VENTS VK EC centrifugal fan, covering its purpose, technical data, installation, operation, maintenance, and warranty. Essential for ensuring safe and efficient ventilation system performance.
Preview VENTS TT PRO EC Inline Mixed-Flow Fans User's Manual
Comprehensive user's manual for VENTS TT PRO EC inline mixed-flow fans, covering delivery set, technical specifications, installation, operation, maintenance, troubleshooting, and warranty. Designed for efficient ventilation in heated premises.
Preview VENTS Stream EC Serie: Schallisolierte Rohrventilatoren – Technische Daten & Anwendung
Entdecken Sie die VENTS Stream EC Serie, schallisolierte Rohrventilatoren mit EC-Motoren für effiziente und geräuscharme Be- und Entlüftung in Gewerbe- und Industrieräumen. Technische Spezifikationen und Anwendungsbereiche.
Preview Посібник користувача вентиляторів VENTS TT PRO EC
Детальний посібник користувача для канальних вентиляторів змішаного типу VENTS TT PRO EC. Охоплює встановлення, експлуатацію, технічне обслуговування та усунення несправностей. Включає інформацію про моделі, підключення та гарантію.
Preview VENTS TT PRO EC Inline Mixed-Flow Fan User Manual
Comprehensive user manual for the VENTS TT PRO EC series of inline mixed-flow fans, covering installation, operation, maintenance, troubleshooting, and warranty information.
Preview Посібник користувача вентиляторів VENTS ICF та ICF EC
Детальний посібник користувача для вентиляторів VENTS серій ICF та ICF EC. Охоплює призначення, технічні характеристики, монтаж, підключення, експлуатацію, технічне обслуговування та усунення несправностей. Містить важливі заходи безпеки.
Preview VENTS Boost Series Inline Mixed-Flow Fan User's Manual
Comprehensive user's manual for VENTS Boost 315, Boost 355, and Boost 400 inline mixed-flow fans. Covers safety requirements, technical data, mounting and setup, electrical connections, maintenance, troubleshooting, and warranty information.
Preview Посібник користувача VENTS A37 (KVENT Medium) для систем вентиляції AirVents
Детальний посібник користувача для системи автоматичного керування VENTS A37 (KVENT Medium) для систем вентиляції AirVents. Охоплює технічні характеристики, встановлення, підключення, експлуатацію та усунення несправностей.