VENTS VKP/VKPI/VKPF/VKPFI User's Manual

Centrifugal rectangular duct fan

Table of Contents

Safety Requirements

All user's manual requirements, as well as the provisions of all applicable local and national construction, electrical, and technical norms and standards, must be observed when installing and operating the unit.

Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.

Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation and maintenance. The present user's manual should be carefully read before beginning works.

Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.

While mounting the unit, avoid compression of the casing. Deformation of the casing may result in motor jam and excessive noise.

Misuse of the unit and any unauthorized modifications are not allowed.

Do not expose the device to adverse atmospheric agents (rain, sun, etc.).

Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.

Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.

Do not close or block the intake or extract vents in order to ensure the efficient air flow.

Do not sit on the unit and do not put objects on it.

The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.

Never touch the unit with wet or damp hands.

Never touch the unit when barefoot.

The installation site of the fan must have protective elements that prevent foreign objects from entering the fan.

When starting, setting up, and operating the fan, the exhaust and supply spigots must be protected to prevent injury from the rotating parts of the fan.

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

The connection to the supply mains must be made through a means of disconnection, which is incorporated in the fixed wiring in accordance with the wiring rules, and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.

If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a safety hazard.

Ensure that the appliance is switched off from the supply mains before removing the guard.

WARNING: If there are any unusual oscillating movements, immediately stop using the appliance and contact the manufacturer, its service agent, or suitably qualified persons.

The replacement of parts of the safety suspension system device shall be performed by the manufacturer, its service agent, or suitably qualified persons.

Fixing means for attachment to the ceiling such as hooks or other devices shall be fixed with a sufficient strength to withstand 4 times the weight of the appliance.

The mounting of the suspension system shall be performed by the manufacturer, its service agent, or suitably qualified persons.

The appliance is to be installed so that the blades are more than 2.3m above the floor.

Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.

Disposal: The product must be disposed of separately at the end of its service life. Do not dispose of the unit as unsorted domestic waste.

Purpose

The unit should not be operated by children or persons with reduced physical, mental, or sensory capacities, or those without the appropriate training.

The unit must be installed and connected only by properly qualified personnel after the appropriate briefing.

The choice of unit installation location must prevent unauthorized access by unattended children.

The duct rectangular fan is designed for supply and exhaust ventilation of domestic, public, and industrial premises with high requirements to the noise level and with limited space for mounting.

The unit is rated for continuous operation.

The unit is a component part and is not designed for stand-alone operation.

Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot, and oil particles, or environments favorable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).

Delivery Set

NAME NUMBER
Fan 1 pc.
User's manual 1 pc.
Packing box 1 pc.

Designation Key

Designation example: VKP 4 E 500x300

Series:

Poles:

Phases:

Size of the rectangular duct (WxH) [mm]

Power

Voltage/Frequency [V/Hz]

Technical Data

The unit is designed for indoor application with the ambient temperature ranging from 0°C up to +45 °C and relative humidity up to 80%. The unit is rated as a Class I electrical appliance.

The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.

VKP/VKPI

2E 400x200 2E 500x250 4E 500x300 4D 500x300
50 60 50 60 50 60 50 60
Voltage [V] 1~220-240 1~220-240 1~220-240 3~400
Frequency [Hz] 50 60 50 60 50 60 50 60
Power [W] 138 200 305 380 140 175 136 165
Current [A] 0.60 0.88 1.32 1.65 0.57 0.73 0.34 0.53
Maximum air flow [m³/h] 930 1070 1720 1850 1700 1855 1380 1620
RPM [min⁻¹] 2600 2850 2550 2830 1390 1530 1360 1600
Sound pressure level at 3 m distance [dBA] 69/61* 71/63* 76/65* 78/67* 53/45* 55/46* 53/45* 55/46*
Transported air temperature [°C] -25...+45 -25...+45 -25...+45 -25...+50
Ingress protection rating of the unit IPX4 IPX4 IPX4 IPX4
Electric motor IP rating IP54 IP54 IP54 IP54

VKP/VKPI

4E 600x300 4D 600x300 4E 600x350 4D 600x350 4D 1000x500
50 60 50 60 50 60 50 60 50
Voltage [V] 1~220-240 3~400 1~220-240 3~400 3~400
Frequency [Hz] 50 60 50 60 50 60 50 60 50
Power [W] 220 310 230 235 470 700 510 750 380
Current [A] 0.9 1.38 0.52 0.53 2.37 3.15 1.41 1.44 0.7
Maximum air flow [m³/h] 2470 2510 2530 2630 2950 3515 2970 3410 2660
RPM [min⁻¹] 1400 1450 1360 1600 1370 1460 1415 1610 1235
Sound pressure level at 3 m distance [dBA] 55/47* 55/57* 53/46* 53/46* 67/59* 68/59* 64/55* 64/55* 63/55*
Transported air temperature [°C] -25...+45 -25...+45 -25...+70 -25...+65 -40...+80
Ingress protection rating of the unit IPX4 IPX4 IPX4 IPX4 IPX4
Electric motor IP rating IP54 IP54 IP54 IP54 IP54

VKP/VKPI

4D 600x350 4D 1000x500
50 60 50 60
Voltage [V] 3~400 Δ 3~400 Y 3~400
Frequency [Hz] 50 60 50 60 50
Power [W] 510 750 380 515 3800
Current [A] 1.41 1.44 0.7 0.93 6.6
Maximum air flow [m³/h] 2970 3410 2660 2730 15000
RPM [min⁻¹] 1415 1610 1235 1220 1360
Sound pressure level at 3 m distance [dBA] 64/55* 64/55* 63/55* 63/55* 70
Transported air temperature [°C] -40...+60 -40...+80 -40...+40 -25...+40
Ingress protection rating of the unit IPX4 IPX4 IPX4 IPX4
Electric motor IP rating IP54 IP54 IP54 IP54

* Parameters for a VKPI model.

Dimensions and Weight

VKP

Model Dimensions [mm] Weight [kg]
B B1 B2 H H1 H2 H3 L
VKP 2E 400x200 400 420 440 200 220 240 240 500 11.25
VKP 2E 500x250 500 520 540 250 270 290 290 640 17.88
VKP 4E 500x300 500 520 540 300 320 340 340 680 19.80
VKP 4D 500x300 500 520 540 300 320 340 340 680 19.80
VKP 4E 600x300 600 620 640 300 320 340 342 680 27.77
VKP 4D 600x300 600 620 640 300 320 340 342 680 27.77
VKP 4E 600x350 600 620 640 350 370 390 390 735 36.38
VKP 4D 600x350 600 620 640 350 370 390 390 735 36.38

VKP 4D 1000x500

Model Dimensions [mm] Weight [kg]
B B1 B2 H H1 H2 H3 L
VKP 4D 1000x500 1000 1020 1040 500 520 540 720 1150 126.0

VKPI

Model Dimensions [mm] Weight [kg]
B B1 B2 B3 H H1 H2 H3 L
VKPI 2E 400x200 400 420 440 500 200 220 240 360 500 24.5
VKPI 2E 500x250 500 520 540 600 250 270 290 410 640 27.6
VKPI 4E 500x300 500 520 540 600 300 320 340 460 680 37.2
VKPI 4D 500x300 500 520 540 600 300 320 340 460 680 37.2
VKPI 4E 600x300 600 620 640 700 300 320 340 460 680 43.5
VKPI 4D 600x300 600 620 640 700 300 320 340 460 680 43.5
VKPI 4E 600x350 600 620 640 700 350 370 390 530 735 56.2
VKPI 4D 600x350 600 620 640 700 350 370 390 530 735 56.2

Mounting and Set-up

Before mounting: Make sure the casing does not contain any foreign objects (e.g., foil, paper).

While installing: Ensure convenient access for subsequent maintenance and repair.

The fan can operate in any position.

When positioned under the ceiling, it is advisable to mount the fan with the motor cover downwards for easy access to the terminal box and the motor.

Check the fan power cables for integrity and make sure the impeller has smooth rotation prior to mounting.

Install flexible connectors on both sides of the fan.

Mount the fan in such a way that the arrow on the fan casing matches the air flow direction in the system.

The fan should always be installed on its own hangers so that it does not load the flexible connectors and the connected air ducts.

The most suitable mounting option is fixing the unit to the ceiling with anchors or suspending it on perforated metal plates.

Before mounting, apply a self-adhesive seal to the end surfaces of the fan.

Connect the fan to the air ducts with M8 bolts and nuts.

Since the fan belongs to Class 1 in terms of electrical hazard protection, proper grounding is a must: the PE terminal must be connected to the protective ground.

The fan design is constantly being improved, thus some models may be slightly different from those described in this manual.

Variant of Fan Mounting Between Segments of Rectangular Air Ducts

1. Standard mounting with a circuit breaker.

2. Mounting with flexible connectors.

3. Mounting with flexible connectors and a mounting bracket.

4. Mounting with a mounting bracket and flexible connectors.

Connection to Power Mains

Disconnect the power supply prior to any operations with the unit.

Connection of the unit to power mains is allowed by a qualified electrician with a work permit for the electric units up to 1000 V after careful reading of the present user's manual.

The rated electrical parameters of the unit are given on the manufacturer's label.

Depending on the fan type, it is rated for connection either to single-phase AC 230 V/50/60 Hz or three-phase AC 380-400 V/50/60 Hz power mains.

The connection must be made using durable, insulated, and heat-resistant conductors (cables, wires).

The external lead-in must be equipped with a circuit breaker built into the stationary wiring to disconnect all the mains phases. The QF external circuit breaker location must ensure free access for quick shutdown of the fan.

The trip current must be in compliance with current consumption.

The recommended rated current of the circuit breaker and the conductor cross-section for various types of fans are shown in the table. The given conductor cross-sections are for reference only.

The actual conductor cross-section selection must be based on its type, the maximum permissible heating, insulation, length, and installation method (in the air, pipes, or inside walls).

The recommended type of circuit breakers is D or C, but with replacement to D or to a higher rating in case of tripping because of frequent start-ups.

The recommended circuit breaker rated current and conductor cross section

Model Rated current of the circuit breaker [A] Recommended cable, n x S, where n is the number of wires, and S is the cross section [mm²]
VKP, VKPI 2E 400x200 3 3 x 0.75
VKP, VKPI 2E 500x250 6 3 x 0.75
VKP, VKPI 4E 500x300 2 3 x 0.75
VKP, VKPI 4D 500x300 2 5 x 0.75
VKP, VKPI 4E 600x300 4 5 x 0.75
VKP, VKPI 4D 600x300 2 5 x 0.75
VKP, VKPI 4E 600x350 10 3 x 1
VKP, VKPI 4D 600x350 4 5 x 0.75
VKP 4D 1000x500 20 5 x 1.5
VKPF, VKPFI 4E 400x200 4 3 x 0.75
VKPF, VKPFI 4D 400x200 2 5 x 0.75
VKPF, VKPFI 4E 500x250 10 3 x 1
VKPF, VKPFI 4D 500x250 4 5 x 0.75
VKPF, VKPFI 4E 500x300 4 3 x 0.75
VKPF, VKPFI 4D 500x300 2 5 x 0.75
VKPF, VKPFI 4E 600x300 10 3 x 1.5
VKPF, VKPFI 4D 600x300 6 5 x 0.75
VKPF, VKPFI 4E 600x350 6 3 x 2.5
VKPF, VKPFI 4D 600x350 3 5 x 1.0
VKPF, VKPFI 4D 700x400 20 5 x 1.5
VKPF, VKPFI 4D 800x500 10 5 x 1.5
VKPF, VKPFI 6D 800x500 10 5 x 1.0
VKPF, VKPFI 6D 900x500 3 5 x 1.5
VKPF, VKPFI 6D 1000x500 40 5 x 2.5

Wiring Diagrams

Wiring diagrams are provided for various VKP/VKPI/VKPF/VKPFI fan configurations, including single-phase and three-phase motors.

Diagram 1: VKP/VKPI 2E 400x200, 2E 500x250, 4E 500x300, 4E 600x300, 4E 600x350 units with a single-phase motor.

Diagram 2: VKP/VKPI 4D 500x300 (first option) with a three-phase motor.

Diagram 3: VKP/VKPI 4D 500x300 (second option), VKP/VKPI 4D 600x300 units with a three-phase motor.

Diagram 4: VKP/VKPI 4D 600x350 units with a three-phase motor.

Diagram 5: VKPF, VKPFI fans with a single-phase motor.

Diagram 6: VKPF, VKPFI fans with a three-phase motor.

* X1 - terminal block, QF – automatic circuit breaker (not included in the delivery set).

Asynchronous Electric Motor Starting Methods

There are several methods for starting asynchronous squirrel-cage electric motors. The most common methods are: direct-on-line (DOL), with a soft starter (SS), or with a frequency converter (FC).

Direct-on-line starting

In case of direct-on-line starting (i.e., by connecting the motor to the electric mains with a simple line contactor), the motor starting time significantly increases due to high inertia of the impeller, which, in turn, results in high in-rush starting currents in the circuit. These currents of long duration may cause voltage slumps (especially if the feed line section falls short of the requirements), which may affect load operation.

The in-rush current consumed by an electric motor in case of DOL starting is 5-8 times larger than the rated value (or even 10-14 times larger in some rare instances). It should be noted that the torque developed by the motor also significantly exceeds the rated value.

Upon energization, the motor operates as a transformer with a squirrel-cage secondary winding formed by the rotor cage with a very low resistance.

The rotor develops high induced current, causing a rush of current in the feed line.

The startup torque during starting averages 0.5-1.5 of the rated torque value.

Despite such advantages as simple construction, high startup current, quick start, and low cost, direct-on-line systems are suitable only in the following cases:

Soft start. SS starting.

A soft starter gradually increases the voltage supplied to the motor – from the initial to the rated value. This starting system can be used to meet the following goals:

Regulation by limiting the current sets the maximum in-rush current equal to 300-400% (or 250% in some rare instances) of the rated current and reduces torque characteristics. This type of regulation is especially suited for turbomachinery such as centrifugal pumps and fans.

Regulation by variation of torque optimizes the torque during startup and reduces in-rush current in the circuit. These conditions are suitable for mechanisms with constant load resistance.

This type of soft starting may differ in the implementation pattern:

Soft start. FC starting.

During the starting, the FC raises the frequency from 0 Hz to the electrical mains frequency (50 or 60 Hz). As the frequency is increased gradually, the motor can be assumed to operate at its rated speed for a given frequency value. Furthermore, on the assumption that the motor runs at its rated speed, the nominal torque should be immediately available, whereas the current will be approximately equal to the rated value.

This starting system is used for speed control and regulation and can be used in the following cases:

The aforementioned starting system can be used for all types of mechanisms.

Problems associated with DOL starting

The problems caused by DOL starting may be divided into two groups:

  1. An abrupt start causes mechanical shock, jolts in the mechanism, shock removal of free play, etc.
  2. A heavy start cannot be completed.

Let us review three variations of a heavy start:

  1. The feed line performance is barely sufficient or insufficient to maintain the induced current.
    Typical symptoms: Upon starting, the circuit breakers at the system input are tripped; the lights, certain relays, and contactors go off, and the supply generator shuts down.
    Solution: In the best-case scenario, an SS device may help reduce the in-rush current to 250% of the motor rated current. If this is insufficient, an FC is necessary.
  2. The motor cannot start the mechanism with DOL starting.
    Typical symptoms: The motor fails to turn or "freezes" at a certain speed, which is maintained until actuation of the protection suite.
    Solution: This problem may not be solved with an SS device. The motor develops insufficient shaft torque. However, this problem can be addressed by using an FC, but each case may be different.
  3. The motor spins up the mechanism with authority, but fails to reach the rated rotation speed.
    Typical symptoms: The input automatic circuit breaker is tripped during spin-up. This often happens with heavy-weight fans with a considerable rotation speed.
    Solution: Such problems may be addressed with an SS device, but not with 100% certainty. The closer the motor speed to the rated value during the actuation of the protective equipment, the higher the chances of success. The use of an FC in this case helps solve the problem fundamentally.

Standard switching equipment (automatic circuit breakers, contactors, and motor starters) is not designed to withstand prolonged overloads normally causing the fan to shut down automatically. DOL starting that continues for a long period of time.

Using switching equipment with a higher maximum current rating renders the electric motor protection system less sensitive. As a result, the switching equipment will not be able to detect motor overload in time due to a high current sensing threshold.

Such problems as mentioned above can only be addressed by utilizing a soft starter or a frequency converter to start the fan.

Important: Make sure that the fan impeller rotates in the direction marked by the arrow on the fan casing. If necessary, change the impeller rotation direction by altering the phase sequence on the electric motor terminals.

Technical Maintenance

Disconnect the unit from power supply before any maintenance operations!

Prior to performing any technical maintenance and repair, disconnect the fan from the electric mains and wait until its rotating parts come to a complete stop.

The technical maintenance includes periodic cleaning of the surfaces from accumulated dust and dirt.

Use a soft brush or compressed air to remove dust from metal surfaces of the fan. Use a vacuum cleaner to remove dust from the sound-insulating surface.

The impeller blades require thorough cleaning once in 6 months.

Detach air ducts from the fan before starting maintenance works.

Clean the impeller blades with a soft cloth wetted in mild water detergent solution. Avoid liquid dripping on the motor.

Wipe the fan surfaces dry after cleaning.

While cleaning the fan, make sure the balance counterweights are not shifted and the impeller is not misaligned.

Troubleshooting

Problem Possible reasons Troubleshooting
The fan does not run. No power supply. Check the automatic circuit breaker.
Check the electric connections.
Noisy operation. Impeller imbalance. Clean the impeller.

Storage and Transportation Regulations

Store the unit in the manufacturer's original packaging box in a dry, closed, ventilated premise with a temperature range from +5 °C to +40 °C and relative humidity up to 70%.

Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.

Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.

Follow the handling requirements applicable for the particular type of cargo.

The unit can be carried in the original packaging by any mode of transport, provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.

Avoid sharp blows, scratches, or rough handling during loading and unloading.

Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.

Manufacturer's Warranty

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. VENTS hereby declares that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council, and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.

The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date, provided the user's observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer's fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.

The warranty repair does not include:

To benefit from warranty repair, the user must provide the unit, the user's manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user's manual. Contact the Seller for warranty service.

The manufacturer's warranty does not apply to the following cases:

Note: Following the regulations stipulated herein will ensure a long and trouble-free operation of the unit. User's warranty claims shall be subject to review only upon presentation of the unit, the payment document, and the user's manual with the purchase date stamp.

Certificate of Acceptance

Unit Type: Centrifugal rectangular duct fan

Model: VKP

Serial Number:

Manufacture Date:

Quality Inspector's Stamp:

This is to certify acceptance of the complete unit delivery with the user's manual. The warranty terms are acknowledged and accepted.

Customer's Signature:

Seller's Stamp:

Seller Information

Seller:

Address:

Phone Number:

E-mail:

Purchase Date:

Installation Certificate

The VKP unit is installed pursuant to the requirements stated in the present user's manual.

Company name:

Address:

Phone Number:

Installation Technician's Full Name:

Installation Date:

Signature:

The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical, and technical codes and standards. The unit operates normally as intended by the manufacturer.

Signature:

Installation Stamp:

Warranty Card

Unit Type: Centrifugal rectangular duct fan

Model: VKP

Serial Number:

Manufacture Date:

Purchase Date:

Warranty Period:

Seller:

Seller's Stamp:

Models: VKP, VKPI, VKPF, Centrifugal Rectangular Duct Fan, Rectangular Duct Fan, Duct Fan, Centrifugal Fan, Fan

File Info : application/pdf, 24 Pages, 3.75MB

PDF preview unavailable. Download the PDF instead.

v07en a4 04 preview4

References

Adobe PDF Library 15.0 Adobe InDesign CC 2015 (Windows)

Related Documents

Preview Vents D Axial Fan User's Manual
Comprehensive user's manual for the Vents D axial fan, covering delivery set, installation, operation, technical maintenance, troubleshooting, and manufacturer's warranty. Includes technical specifications and safety guidelines.
Preview VENTS Boost Series Inline Mixed-Flow Fan User Manual
Comprehensive user manual for VENTS Boost series inline mixed-flow fans (Boost 150, 200, 250), covering safety, installation, operation, maintenance, and troubleshooting.
Preview VENTS Boost Series Inline Mixed-Flow Fan User's Manual
Comprehensive user's manual for VENTS Boost 315, Boost 355, and Boost 400 inline mixed-flow fans. Covers safety requirements, technical data, mounting and setup, electrical connections, maintenance, troubleshooting, and warranty information.
Preview VENTS TT Series Centrifugal Inline Fan User Manual | Installation & Operation Guide
Comprehensive user manual for VENTS TT series centrifugal inline fans. Covers installation, operation, maintenance, troubleshooting, and warranty for models including TT 100, TT 125, TT 150, TT 160, TT 250, TT 315, TT XXX T, TT XXX U/U1/U2(n), and TT XXX P. Features technical specifications and safety guidelines for optimal ventilation system performance.
Preview VENTS DuoVent EC User Manual - Installation, Operation, and Maintenance
Comprehensive user manual for VENTS DuoVent EC duct redundancy fan units, covering installation, technical data, operation, maintenance, troubleshooting, and warranty information.
Preview Посібник користувача вентиляторів VENTS ICF та ICF EC
Детальний посібник користувача для вентиляторів VENTS серій ICF та ICF EC. Охоплює призначення, технічні характеристики, монтаж, підключення, експлуатацію, технічне обслуговування та усунення несправностей. Містить важливі заходи безпеки.
Preview VENTS TT PRO EC Inline Mixed-Flow Fans User's Manual
Comprehensive user's manual for VENTS TT PRO EC inline mixed-flow fans, covering delivery set, technical specifications, installation, operation, maintenance, troubleshooting, and warranty. Designed for efficient ventilation in heated premises.
Preview VENTS CBF DC Centrifugal Ceiling Fan User Manual
Comprehensive user manual for VENTS CBF DC series centrifugal ceiling extract fans, covering installation, operation, technical data, maintenance, and troubleshooting for models like CBF 110 DC and CBF 150 DC.