R. STAHL 8530/1-MCB-STA102-C0.5-000-2 Line Protection Circuit Breaker
Article Number: 293963
Product Description
The R. STAHL 8530 series line protection circuit breakers offer excellent current limitation during short circuits with a high switching capacity of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity to upstream fuses. The components are modularly designed and available in 1 to 4 pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).
Key features include:
- Disconnecting function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or extension of systems due to modular design
- Simple plug-in mounting on a DIN rail in Ex e enclosures
- Fixed magneto-thermal releases
- Ergonomic control lever for safe operation and shutdown
- Padlockable (accessories) to prevent re-operation during maintenance
Technical Characteristics
Explosion Protection
Feature | Specification |
---|---|
Area of application (zones) | 1, 2 |
Area of application (zones) Note | Usable in Zone 21 / 22 with protection by Ex tb / tc enclosure |
IECEx gas certificate | IECEx FMG 19.0029U |
IECEx protection against gas explosion | Ex db eb IIC Gb |
ATEX gas certificate | FM19ATEX0191U |
ATEX protection against gas explosion | II 2 G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Certificate of conformity | Certificate of conformity (ATEX) |
Electrical Characteristics
Feature | Specification |
---|---|
Rated operational voltage AC | 230/400 V |
Rated service current | 0.5 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 10⁴ |
Mechanical service life | 2 x 10⁴ |
1st auxiliary function | None |
Voltage 1st auxiliary function AC | - |
Max. current 1st auxiliary function | - |
2nd auxiliary function | None |
Max. voltage 2nd auxiliary function DC | - |
Tripping characteristic | C |
Number of poles | 2 poles |
Mechanical Characteristics
Feature | Specification |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Housing material | Thermoplastic |
Minimum connection cross-section | 1.5 mm² |
Maximum connection cross-section | 25 mm² |
AWG connection cross-section min. | 16 AWG |
AWG connection cross-section max. | 4 AWG |
Connection cross-section 2 min. | 1.5 mm² |
Connection cross-section 2 max. | 10 mm² |
AWG connection cross-section 2 min. | 16 AWG |
AWG connection cross-section 2 max. | 8 AWG |
Tightening torque min. | 2 N·m |
Tightening torque max. | 3 N·m |
Connection cross-section Note | Connection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16/10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) Authorized combination possibilities of connection cross-sections are indicated in the operating instructions. |
Width | 65 mm [2.56 in] |
Length | 165 mm [6.5 in] |
Length in inches | 6.5 in |
Mounting depth | 138.3 mm [5.44 in] |
Mounting depth inches | 5.44 in |
Weight | 1 kg [2.205 lb] |
Mounting / Installation
Feature | Specification |
---|---|
Tightening torque | 2-3 N·m |
Tightening torque in lbf·in | 17.7 ... 26.6 lbf·in |
Auxiliary contact tightening torque | 0.4–0.6 N·m |
Auxiliary contact tightening torque lbf·in | 3.5 ... 5.3 lbf·in |
Technical Drawings and Diagrams
Tripping Characteristic Curve C: The document includes a graph illustrating the tripping characteristic curve 'C' for the circuit breaker, showing the relationship between multiples of the rated current (I/In) and tripping time in seconds for both AC and DC.
Dimensional Drawings: Detailed dimensional drawings are provided in millimeters and inches, showing the overall width, length, and mounting depth of the circuit breaker. These include:
- Overall width: 65 mm [2.56 in]
- Overall length: 165 mm [6.50 in]
- Mounting depth: 138.30 mm [5.44 in]
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.
Description | Article Number |
---|---|
Quadruple locking device | 227232 |
Fixing Kit
A fixing kit for attaching the component to a mounting plate without a DIN rail.
Description | Article Number |
---|---|
Fixing kit for attaching the component to the mounting plate without a DIN rail | 276618 |
Cylinder Lock
For locking (shackle Ø 3).
Description | Article Number |
---|---|
For locking (shackle Ø 3) | 107115 |
General Information
Ambient Conditions:
- Ambient temperature: -40 °C ... 70 °C [-40°F ... +158°F]
- Ambient temperature note: Ambient temperatures different from the above are available upon request based on current certificates.
Note: Technical specifications, dimensions, weights, construction types, and delivery possibilities are subject to change. Figures are for indicative purposes only.