ComfortStar Air Handler Heat Pump System
Model Numbers: AHU3-36-SG3(27T) / CPH3-36CD(O)(27G)
Certifications: AURI CERTIFIED, ENERGY STAR, ETL Intertek
System Overview
This document provides the submittal data sheet for the ComfortStar Air Handler Heat Pump System, detailing its specifications and performance characteristics.
Efficiency Ratings
Rating | Value |
---|---|
SEER2 | 17.3 |
EER2 | 11.7 |
HSPF2-4 | 10.2 |
COP | 3.60 |
Performance - Cooling
Cooling Capacity (Btu/hr)
Specification | Value |
---|---|
Rated Capacity | 36000 |
Min/Max Capacity | 7900~36800 |
Moisture Removal (L/h) | 3.92 |
Standard Operating Range (°F/°C) | -22~122 (-30~50) |
Rated Cooling Conditions | Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB |
Performance - Heating
Heating Capacity (Btu/hr)
Condition | Capacity / COP |
---|---|
1. @ 47°F Rated | 37000 |
2. @ 47°F Min/Max Capacity | 7500~38000 |
3. @ 17°F Rated | 23200 |
4. @ 5°F Rated: Capacity / COP | 32000 / 1.85 |
5. @ 5°F Max: Capacity | 32000 |
Standard Operating Range (°F/°C) | -22~75 (-30~24) |
1. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency | Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Indoor Unit Specifications
General
Specification | Value |
---|---|
ESP (in.W.G) | 0-0.8 |
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 1189 / 1083 / 971 / 865 / 865 |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | 48.5/48.5/45.5/31/31 |
Dimensions
Specification | Value (inch) | Value (mm) |
---|---|---|
Dimension (W×D×H) | 21.02 x 21.02 x 49.02 | 534×534×1245 |
Package (W×D×H) | 26.57 x 24.41 x 52.56 | 675×620×1335 |
Net/Gross Weight | 129/154 lbs | 58.7/69.8 kg |
Outdoor Unit Specifications
General
Specification | Value |
---|---|
Compressor Type | ROTARY |
Compressor Model | MTH356UKRC8FQL |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 1300 |
Refrigerant Oil | HAF68D1A |
Outdoor Air Flow (Max) (CFM) | 3002.0 |
Outdoor Noise Level (dBA) | 64 |
Dimensions
Specification | Value (inch) | Value (mm) |
---|---|---|
Dimension (W×D×H) | 37.24 x 16.14 x 31.89 | 946×410×810 |
Package (W×D×H) | 42.91 x 19.69 x 34.84 | 1090×500×885 |
Net/Gross Weight | 166.67/176.37 lbs | 75.6/80.0 kg |
Electrical Specifications
Specification | Value |
---|---|
Indoor Power Supply | 115/208/230V, 60Hz, 1Ph |
Indoor MCA | 6 A |
Indoor MOP | 15 A |
Outdoor Power Supply | 208/230V, 60Hz, 1Ph |
Outdoor MCA | 26 A |
Outdoor MOP | 30 A |
Communication Wiring | 18 AWG |
Compressor RLA | 3 A |
Outdoor Fan Motor RLA | 150 W |
Outdoor Fan Motor W | 4.5 A |
Indoor Fan Motor RLA | 375 W |
Indoor Fan Motor W | 3600 (870~4110) W |
System Power Input @ Cooling (W) | 3325 (535~3500) W |
System Power Input @ Heating (W) | MOCP: Max. over current protection (A) |
MCA: Min. circuit amps (A) | W: Fan motor rated output (W) |
RLA: Rated load amps (A) |
Piping Specifications
Specification | Value |
---|---|
Throttle type (Indoor) | EXV |
Throttle type (Outdoor) | EXV |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 246 (75) |
Max. Height Difference (ft/m) | 98 (30) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg) | 126.99 (3.6) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 65 (65) |
Connection Method | Flared |
Detailed Dimensions
Indoor Unit Dimensions
The indoor unit is a rectangular air handler designed for multi-position installation. It features access points for supply and return air, piping, condensate drains, and electrical wiring. Specific dimensions and clearance requirements for different model capacities (18k/24k, 30k/36k, 48k/60k) are provided in the table below.
Dimension | 18k/24k (inch/mm) | 30k/36k (inch/mm) | 48k/60k (inch/mm) |
---|---|---|---|
A. Model Height | 45 / 1143 | 49 / 1245 | 53 / 1346 |
B. Model Width | 17-1/2 / 445 | 21 / 534 | 24-1/2 / 622 |
C. Supply Air Opening Width | 15-5/8 / 397 | 19-1/8 / 486 | 22-5/8 / 575 |
D. Return Air Opening Width | 15-1/8 / 384 | 18-5/8 / 473 | 22-1/8 / 562 |
E. Model Depth | 21 / 534 | 21 / 534 | 21 / 534 |
F. Supply Air Opening Depth | 10-1/4 / 260 | 10-1/4 / 260 | 10-1/4 / 260 |
G. Return Air Opening Depth | 18-3/4 / 476 | 18-3/4 / 476 | 18-3/4 / 476 |
H. Supply Air Opening Clearance | 15/16 / 24 | 15/16 / 24 | 15/16 / 24 |
I. Return Air Opening Side Clearance | 1-1/4 / 32 | 1-1/4 / 32 | 1-1/8 / 28 |
J. Return Air Opening Front Clearance | 1-1/2 / 38 | 1-5/8 / 41 | 1-5/8 / 41 |
K. Return Air Opening Back Clearance | 5/8 / 16 | 5/8 / 16 | 3/4 / 19 |
Outdoor Unit Dimensions
The outdoor unit is a compact condenser unit designed for external placement. Its dimensions and piping connection sizes are detailed below.
Specification | Value |
---|---|
Overall Dimensions (W×H×D) | Approx. 40-1/2 (1030mm) × 37-1/4 (946mm) × 26-1/2 (673mm) |
Side View Dimensions (W×H×D) | Approx. 31-7/8 (810mm) × 16-1/8 (410mm) × 17-7/8 (455mm) |
Base View Dimensions (W×D) | Approx. 37-1/4 (946mm) × 26-1/2 (673mm) |
Piping Connections (diameter) | Liquid: R3/8 (R10), Gas: R1/4 (R6) |
Outdoor Unit Installation Clearance Requirements
Proper installation requires specific clearances around the outdoor unit to ensure adequate airflow and efficient operation. The following clearances are recommended:
- Front and sides: 20 inches (500mm) or more if clear.
- Sides/Rear: 20 inches (500mm) or more if any two sides (left, right, rear) are clear.
- Front/Sides: 4 inches (100mm) or more.
- Rear: 14 inches (350mm) or more.
Note:
The unit meets all spatial requirements shown in the Installation Clearance Requirements above.
Indoor Unit Fan Performance
This section describes the fan performance characteristics of the indoor unit, illustrating the relationship between external static pressure and airflow rate at various speed settings.
- The graph displays Airflow Rate (CFM) on the Y-axis against External Static Pressure (in.w.c.) on the X-axis.
- The X-axis ranges from 0 to 0.8 in.w.c.
- The Y-axis ranges from 0 to 1400 CFM.
- The graph shows multiple lines representing different fan speed settings: SH (Super High), H (High), M (Medium), and L (Low).
- As external static pressure increases, the airflow rate generally decreases across all speed settings. The 'SH' setting provides the highest airflow, followed by 'H', 'M', and 'L'.
Key Features
- Multi-position installation: horizontal (left or right), vertical (up or down).
- Aluminum Coil.
- Constantly Air Flow system up to 0.80 In.W.G.
- 1 inch R4.2 fiberglass free insulation reduces condensation and boosts efficiency (optional).
- Optional Auxiliary heat kit up to 25kW.
- Easy Maintenance.
- Multiple control options available:
- Two-way communication wired controller with built-in WiFi: AWC-8P-LC-WIFI.
- Wireless remote controller.
- Third-Party 24V Thermostat.
- Adaptive Control System.
- High efficiency up to 19 SEER2, 12.5 EER2, 10.3 HSPF2.
- 100% heat output at -4°F*.
- Chassis heater and crankcase heater equipped as standard.
*For 36K model, rated cooling capacity/heating capacity at -4°F = 100%