ComfortStar Air Handler Heat Pump System

SUBMITTAL DATA SHEET

Model Numbers: CPH3H-36CD(O) (37A) / AC3-3636A-SG3 (32W)

Efficiency

MetricValue
SEER215.2
EER210.2
HSPF24
COP3.10

Performance of Cooling

ParameterValue
Rated Capacity36000 Btu/hr
Min/Max Capacity11400~39000 Btu/hr
Moisture Removal4.3 L/h
Standard Operating Range-22~122°F (-30~50°C)
Rated Cooling ConditionsIndoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB

Performance of Heating

ParameterValue
Rated Capacity (@ 47°F)37000 Btu/hr
Min/Max Capacity (@ 47°F)11,500~46,000 Btu/hr
Rated Capacity (@ 17°F)29000 Btu/hr
Capacity / COP (@ 5°F)31000 / 1.8
Max Capacity (@ 5°F)31000 Btu/hr
Standard Operating Range-22~75°F (-30~24°C)
Rated Heating Conditions (1)Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB
Rated Heating Conditions (2)Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB
Heating Conditions (Compressor Operating at Max. Frequency)Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB

Indoor Specifications

SpecificationValue (inch)Value (mm)
Dimension (W×D×H)14-1/2 x 21 x 23-5/16368 x 533 x 592
Package (W×D×H)17-1/2 x 25-3/8 x 26445 x 645 x 660
Net/Gross Weight57 / 65 lbs25.8 / 29.4 kg

Outdoor Specifications

SpecificationValue
Compressor TypeTWIN-ROTARY
Compressor ModelEKPQ420D1UMUA
RefrigerantR454B
Refrigerant Oil Charge1460 mL
Refrigerant OilVG75
Outdoor Air Flow (Max)3,002 CFM
Outdoor Noise Level64 dBA
Dimension (W×D×H)38-9/16 x 16-3/8 x 38-3/8 inch (980 x 415 x 975 mm)
Package (W×D×H)45-1/16 x 19-11/16 x 42-1/2 inch (1145 x 500 x 1080 mm)
Net/Gross Weight204 / 235 lbs (92.6 / 106.7 kg)

Electrical

ParameterValue
Indoor Power Supply24V, 60Hz, 1Ph
Indoor MCA-
Indoor MOP-
Outdoor Power Supply208/230V, 60Hz, 1Ph
Outdoor MCA29 A
Outdoor MOP30 A
Communication WiringAWG 20-2
Compressor RLA-
Outdoor Fan Motor RLA20.5 A
Outdoor Fan Motor W2.4 W
Indoor Fan Motor RLA-
Indoor Fan Motor W-
System Power Input @ Cooling3530W (800~3250W)
System Power Input @ Heating3500W (800~4,540W)
MCA (Min. circuit amps)-
RLA (Rated load amps)-
MOCP (Max. over current protection)-
W (Fan motor rated output)-

Piping

ParameterValue
Throttle type (Indoor)EXV
Throttle type (Outdoor)EXV
Liquid Size9.52mm (3/8in)
Gas Size19mm (3/4in)
Max. Piping Length246 ft (75 m)
Max. Height Difference98 ft (30 m)
Max. Pre-charged Length24.6 ft (7.5 m)
Refrigerant Pre-charged Amount126.99 oz (3.6 kg)
Additional Charge of Refrigerant0.7 oz/ft (65 g/m)
Connection MethodFlared

Features

Dimensions and Installation

Indoor Unit Dimensions

Diagrams illustrate the front, side, and top views of the indoor unit, showing overall dimensions and the location of refrigerant pipe joints and drain connections. A table provides specific dimensions (A, B, C, D, E, F) for various models: MVBM-24AB18TN10, MVBM-36AB24TN10, MVBM-36CB24TN10, MVBM-36DB24TN10, MVBM-60CB28TN10.

Outdoor Unit Dimensions

Diagrams show the front, side, and top views of the outdoor unit, indicating dimensions and connection points for refrigerant pipes and installation bolts.

Outdoor Unit Installation Clearance

A diagram illustrates the required clearances around the outdoor unit for proper operation and maintenance. Recommended clearances include 20 inches (500mm) or more when front and sides of the unit are clear, 4 inches (100mm) or more on the sides and rear, and 14 inches (350mm) or more on one side. The unit meets all specified spatial requirements.

PDF preview unavailable. Download the PDF instead.

Submittal CPH3H-36CDO-37A-AC3-3636A-SG3-32W 20250625

Related Documents

Preview ComfortStar Air Handler Heat Pump System Submittal Data Sheet - CPH3H-36CD(O) / AC3-3636B-SG3
Comprehensive submittal data sheet for the ComfortStar CPH3H-36CD(O) (37A) and AC3-3636B-SG3 (32X) Air Handler Heat Pump System, detailing efficiency, performance, electrical, piping, and dimensional specifications.
Preview ComfortStar CPH3H-36CD(O)/CWM3-36-SG3 Air Handler Heat Pump System Submittal Data Sheet
Detailed submittal data sheet for the ComfortStar CPH3H-36CD(O) and CWM3-36-SG3 Air Handler Heat Pump System, including specifications, performance data, dimensions, electrical, and piping information.
Preview ComfortStar CPH3H-36CD(O) Air Handler Heat Pump System Data Sheet
Detailed submittal data sheet for the ComfortStar CPH3H-36CD(O) and CPK3-36-SG3 Air Handler Heat Pump System, including specifications, performance data, and dimensions.
Preview ComfortStar Split Duct Air Conditioner: Owner's Manual & Installation Guide
This comprehensive manual from ComfortStar details the installation, operation, and maintenance of their split horizontal-vertical duct air conditioning units (AC3 series). It includes vital safety information, unit specifications, troubleshooting tips, and wiring guidance for models such as AC3-1824A-SG3.
Preview ComfortStar Air Handler Heat Pump System Submittal Data Sheet AHU3-36-SG3 CPH3-36CD
Detailed submittal data sheet for the ComfortStar AHU3-36-SG3 / CPH3-36CD Air Handler Heat Pump System, including efficiency ratings, performance specifications, dimensions, electrical, and piping information.
Preview ComfortStar CPH3-18CD(O) (27N) / CWM3-18-SG3 Air Handler Heat Pump System Submittal Data Sheet
Detailed submittal data sheet for the ComfortStar CPH3-18CD(O) (27N) / CWM3-18-SG3 Air Handler Heat Pump System, including efficiency ratings, performance specifications, dimensions, electrical data, piping information, and features.
Preview ComfortStar BAH5-30-15 Heat Pump System Submittal
Submittal document for the ComfortStar BAH5-30-15 Heat Pump System, detailing unit dimensions, electrical specifications, performance data (EER2, SEER2, HSPF2), and operational ranges for HVAC professionals.
Preview ComfortStar SEF3-SG3 Series Air Handler Installation Manual
This installation manual from ComfortStar provides comprehensive guidance for installing the SEF3-SG3 Series Air Handler Air Conditioners. It details safety precautions, product overview, installation steps, refrigerant piping, wiring, air evacuation, and test run procedures to ensure proper setup and operation.