Product Overview
This document provides the submittal data for the Daikin FTX24AXVJU / RX24AXVJU, a 2-Ton Wall Mounted Heat Pump System.
Complete warranty details are available from your local dealer or at www.daikincomfort.com. To receive the 12-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec. If the product is installed in a commercial application, the limited warranty period is 5 years.
Efficiency Ratings
Cooling | Heating | |||
---|---|---|---|---|
SEER | EER | HSPF | COP | |
19 | 12.2 | 9.0 | 3.45 |
Performance Data
Cooling (Btu/hr)
Value | |
---|---|
Rated (Min/Max) | 21,200 (5,500 / 24,000) |
Sensible @ AHRI | 15,670 |
Moisture Removal gal/h | 0.67 |
Standard Operating Range | 50°F - 115°F |
Extended Operating Range* | -4°F - 115°F |
Rated Cooling Conditions: | Indoor: 80°F DB/67°F WB Outdoor: 95°F DB/75°F WB |
*With field settings and wind baffle
Heating (Btu/hr)
Value | |
---|---|
1: @ 47° Rated (Min/Max) | 23,600 (5,800 / 27,600) |
2: @ 17° Rated | 15,300 |
Operating Range | 5°F - 65°F |
1: Rated Heating Conditions: | Indoor: 70°F DB/60°F WB Outdoor: 47°F DB/43°F WB |
2: Rated Heating Conditions: | Indoor: 70°F DB/60°F WB Outdoor: 17°F DB/15°F WB |
Indoor Unit Specifications
Cooling | Heating | |||||||
---|---|---|---|---|---|---|---|---|
H | M | L | SL | H | M | L | SL | |
Airflow Rate (cfm) | 716 | 605 | 467 | 395 | 716 | 605 | 467 | 395 |
Sound (dBA) H / M / L / SL | 53 / 45 / 39 / 34 | 53 / 43 / 37 / 34 |
Dimensions (H x W x D) (in): 11-11/16 x 39-1/2 x 11-1/3
Weight (Lbs): 31
Outdoor Unit Specifications
Compressor | Hermetically Sealed Swing Type |
Refrigerant | R-410A |
Factory Charge (Lbs) | 3.86 |
Refrigerant Oil | PVE (FVC50K) |
Airflow Rate (cfm) | Cooling: 1,908 Heating: 1,908 |
Sound Pressure Level (dBA) | 55 |
Dimensions (H x W x D) (in): 27-13/32 x 36-5/8 x 13-13/16
Weight (Lbs): 106
Electrical Specifications
208/60/1 | 230/60/1 | |
---|---|---|
System MCA | 16.4 | 16.4 |
System MFA | 20.0 | 20.0 |
Compressor RLA | 16.0 | 16.0 |
Outdoor fan motor FLA | 1.0 | 1.0 |
Outdoor fan motor W | 128 | 128 |
Indoor fan motor FLA | .50 | .50 |
Indoor fan motor W | 35 | 35 |
Key: MFA: Max. fuse amps, MCA: Min. circuit amps (A), FLA: Full load amps (A), RLA: Rated load amps (A), W: Fan motor rated output (W)
Piping Specifications
Value | |
---|---|
Liquid (in) | 1/4 |
Gas (in) | 5/8 |
Drain (in) | 3/4 |
Max. Interunit Piping Length (ft) | 98.4 |
Max. Interunit Height Difference (ft) | 65.625 |
Chargeless (ft) | 32.8 |
Additional Charge of Refrigerant (oz/ft) | .21 |
Dimensional Data - Indoor Unit
The indoor unit is depicted from multiple views: Front, Side, and Top. The Front View highlights key components: the UP DOWN FLAP, the INDOOR UNIT ON-OFF SWITCH, the SIGNAL RECEIVER, and the ROOM TEMPERATURE THERMISTOR. The Model Name Plate is also indicated. Dimensions are provided in inches (mm).
Dimensional Data - Outdoor Unit
The outdoor unit's dimensions are detailed and labeled with letters A through Q. Values are provided in both inches and millimeters.
Dimension | A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Inches | 27-13/32 | 36-5/8 | 2-19/32 | 15/32 | 13-13/16 | 1-1/16 | 15/32 | 24 | 6-7/8 | 5-23/32 | 3-1/32 | 2-31/32 | 13/16 | 5-19/32 | 5/16 | 17/32 | 13-31/32 |
(mm) | (696) | (930) | (66) | (12) | (351) | (27) | (12) | (610) | (175) | (145) | (77) | (75) | (21) | (142) | (8) | (13) | (355) |
Optional Accessories
Indoor Unit Accessories
Included | Part Number | Description |
---|---|---|
BRP072A43 | Wireless Interface Adaptor | |
AZAI6WSCDKB | DKN Residential Cloud Wi-Fi Adaptor for Single- and Multi-Zone System (S21) | |
AZAI6WSPDKC | DKN Plus Interface | |
BRC51D61 | Wired Remote Controller Kit (32.8ft cable included) | |
BRC944B2 | Wired Remote Controller | |
BRCW901A08 | Wired Remote Controller Cable - 25ft | |
BRCW901A03 | Wired Remote Controller Cable - 10ft | |
DACA-CP1-1 | Inline Condensate Pump (Fits inside all Daikin wall & floor mount units) | |
DACA-CP4-1 | External Condensate Pump |
Outdoor Unit Accessories
Included | Part Number | Description |
---|---|---|
DACA-WB-1 | Powder-Coated Wall-Mounted Bracket | |
KPW063B4E | Air Adjustment Grille | |
KEH063A4EA | Daikin BML Drain Pan Heater Large (incl. RX_AXVJU) |