Daikin FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System

Submittal Data Sheet

Overview and Warranty

This document provides submittal data for the Daikin FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System.

Warranty Information: Complete warranty details are available from your local dealer or at www.daikincomfort.com. To receive the 12-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec. For commercial applications, the limited warranty period is 5 years.

Efficiency Ratings

CoolingHeating
SEER18
EER12.5
HSPF9.0
COP3.50

Performance Data

Cooling (Btu/hr)

ParameterValue
Rated (Min/Max)21,200 (5,500 / 24,000)
Sensible @ AHRI15,760
Moisture Removal gal/h1.2
Standard Operating Range50°F – 115°F
Extended Operating Range*-4°F – 115°F
Rated Cooling ConditionsIndoor: 80°F Dry Bulb/67°F Wet Bulb
Outdoor: 95°F Dry Bulb/75°F Wet Bulb

*With field settings and wind baffle

Heating (Btu/hr)

ConditionValue
1: @ 47° Rated (Min/Max)24,000 (5,800 / 27,600)
2: @ 17° Rated14,400
3: @ 5° Max10,720
Operating Range5°F – 65°F
1: Rated Heating ConditionsIndoor: 70°F Dry Bulb/60°F Wet Bulb
Outdoor: 47°F Dry Bulb/43°F Wet Bulb
2: Rated Heating ConditionsIndoor: 70°F Dry Bulb/60°F Wet Bulb
Outdoor: 17°F Dry Bulb/15°F Wet Bulb
3: Rated Heating ConditionsIndoor: 70°F Dry Bulb/60°F Wet Bulb
Outdoor: 5°F Dry Bulb/5°F Wet Bulb

Indoor Unit Specifications

Airflow Rate (cfm)

CoolingHeating
HighMediumHighMedium
713579745604
Low512403470420
Super Low

Sound (dBA)

HighMediumLowSuper Low
H / M / L / SL53 / 45 / 39 / 3453 / 43 / 37 / 34

Dimensions (H x W x D) (in)

11-5/8 x 39 x 10-3/8

Weight (Lbs)

27

Outdoor Unit Specifications

Compressor

Hermetically Sealed Swing Type

Refrigerant

R-410A

Refrigerant Oil

PVE (FVC50K)

Airflow Rate (cfm)

CoolingHeating
HighSuper LowHighSuper Low
2,1011,7621,8931,585

Sound Power Level (dBA)

55

Dimensions (H x W x D) (in)

28-5/16 x 34-1/4 x 12-5/8

Weight (Lbs)

108

Electrical Specifications

Parameter208/60/1230/60/1
System MCA (Minimum Circuit Amps)18.318.3
System MFA (Maximum Fuse Amps)2020
Compressor RLA (Rated Load Amps)12.012.0
Outdoor fan motor FLA (Full Load Amps).38.38
Outdoor fan motor W (Watts)5858
Indoor fan motor FLA (Full Load Amps).30.30
Indoor fan motor W (Watts)4646

Note: MFA: Maximum fuse amps, MCA: Minimum circuit amps (A), FLA: Full load amps (A), RLA: Rated load amps (A), W: Fan motor rated output (W).

Piping Specifications

ParameterValue
Liquid (in)1/4
Gas (in)5/8
Drain (in)5/8
Max. Interunit Piping Length (ft)98.4
Max. Interunit Height Difference (ft)65.625
Chargeless (ft)32.8
Additional Charge of Refrigerant (oz/ft).21

Dimensional Data - Indoor Unit (FTX24NMVJU)

Diagram Description: The indoor unit diagram shows the unit's front, side, and bottom views. It details the location of the signal receiver, operation lamp, timer lamp, indoor unit on/off switch, room temperature thermistor, terminal block, and drain hose connection. It also illustrates the adjustable flaps for airflow direction control, showing angles for up/down movement (automatic) and right/left movement (manual). Mounting plate dimensions and wall hole requirements are also depicted.

Dimensions (approximate):

Piping Connections: Liquid line: 1/4 inch (6.4mm) Copper Tubing. Gas line: 5/8 inch (15.9mm) Copper Tubing. Drain hose: I.D. 9/16 inch (14mm), O.D. 5/8 inch (16mm).

Wall Hole: Standard locations for wall holes are shown, including a 2-3/8 inch (60mm) hole for embedded piping and a 3-1/8 inch (80mm) hole.

Dimensional Data - Outdoor Unit (RX24NMVJU)

Diagram Description: The outdoor unit diagram presents front, side, and top views. It highlights the handle, brand name plate, foundation bolt holes (M8 or M10), ground terminal, service port, stop valve cover, terminal strip cover, liquid and gas stop valves, drain outlet, electric wire intake, and outdoor air thermistor. The outdoor air thermistor location is shown. Crucial clearances for air passage and maintenance are specified. It also indicates the wall height limitation on the air outlet side.

Dimensions (approximate):

Piping Connections: Liquid stop valve: 1/4 inch (6.4mm) Copper Tubing. Gas stop valve: 5/8 inch (15.9mm) Copper Tubing. Drain outlet: For connection with drain joint, I.D. 5/8 inch (15.9mm) hose.

Mounting: Includes 4-holes for foundation bolts.

Optional Accessories

Indoor Unit Accessories

IncludedPart NumberDescription
BRP072A43Wireless Interface Adapter (S21 Adapter Included)
DACA-TS1-1Daikin ENVi Intelligent Thermostat Kit (Adaptor Required)
BRC944B2-A08Wired Remote Controller kit (Adaptor Required)
BRCW901A08Wired Remote Controller Cord - 8m (Included in above kit)
DACA-BRCW901P10Remote Controller Cable, Plenum Rated, 10 ft
DACA-BRCW901P25Remote Controller Cable, Plenum Rated, 25 ft
KRP980B2Adaptor for wired remote controller (18 & 24)
KAF970A45Titanium apatite photocatalytic air-purifying filter WITH frame
KAF970A46Titanium apatite photocatalytic air-purifying filter WITHOUT frame
DACA-CP1-1Inline Condensate Pump (Fits inside all Daikin wall & floor mount units)
DACA-CP4-1External Condensate Pump
KRP928BB2S + KRP980B2Interface adaptor for DIII-NET

Outdoor Unit Accessories

IncludedPart NumberDescription
DACA-WB-1Powder-Coated Wall-Mounted Bracket
KPW063A4Air direction adjustment grille (18 & 24)
KEH063A4EDaikin BML Drain Pan Heater Large RX18,24 & RXN18,24
KKG063A42Back protection wire net (18 & 24)
KKG063A43Side protection wire net (18 & 24)
KKP937A4Drain Plug for OD Unit

PDF preview unavailable. Download the PDF instead.

FTX24NMVJU-RX24NMVJU-Submittal-Sheet Microsoft Word 2010 Microsoft Word 2010

Related Documents

Preview Daikin FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System Submittal Data Sheet
Detailed submittal data sheet for the Daikin FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System, including specifications, performance data, electrical requirements, and piping information.
Preview Daikin FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System Specifications
Detailed submittal data sheet for the Daikin FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System, including efficiency, performance, electrical, piping, and optional accessory specifications.
Preview Daikin FTX24AXVJU / RX24AXVJU 2-Ton Wall Mounted Heat Pump System Submittal Data Sheet
Detailed submittal data sheet for the Daikin FTX24AXVJU / RX24AXVJU 2-Ton Wall Mounted Heat Pump System, including efficiency, performance, electrical, and piping specifications.
Preview Daikin FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System Submittal Data Sheet
Detailed technical specifications, performance data, electrical requirements, piping information, dimensional drawings, and optional accessories for the Daikin FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System.
Preview Daikin FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System Specifications
Comprehensive submittal data sheet detailing the specifications, performance, dimensions, electrical requirements, and optional accessories for the Daikin FTX24NMVJU / RX24NMVJU 2-Ton Wall Mounted Heat Pump System.
Preview Daikin FTX24NMVJURX24NMVJU 2.0-Ton Wall Mounted Unit Submittal Data Sheet
Technical specifications and performance data for the Daikin 2.0-Ton Wall Mounted Unit, model FTX24NMVJURX24NMVJU, detailing features, benefits, system performance, and dimensional information for both indoor and outdoor units.
Preview Daikin 2.0-Ton Wall Mounted Unit FTX24NMVJURX24NMVJU Submittal Data Sheet
Comprehensive submittal data sheet for the Daikin 2.0-Ton Wall Mounted Unit (FTX24NMVJURX24NMVJU), detailing features, benefits, system performance specifications, and dimensional information for indoor and outdoor units.
Preview Daikin 2.0-Ton Wall Mounted Unit FTX24NMVJURX24NMVJU Submittal Data Sheet
Technical specifications and submittal data for the Daikin 2.0-Ton Wall Mounted Unit (FTX24NMVJURX24NMVJU), including features, benefits, system performance, and dimensional drawings.