Salus RT510RF Thermostat Installation Manual
1. RXRT510 Receiver Installation
Unscrew the backplate of the RXRT510 receiver to make the wiring connections. After that, switch the receiver ON.
Receiver Terminals:
Terminal | Description |
---|---|
NO | Switch Terminal |
COM | Common Switch Terminal |
L | Mains Live (230VAC) |
N | Mains Neutral |
Electrical Diagram:
[Diagram showing connections: NO to COM, L to L, N to N]
Button Description for RXRT510 Receiver
Button | Function |
---|---|
ON | The receiver is enabled, ready for use. |
OFF | The receiver is disabled, will not function. |
AUTO | The receiver will switch on and off automatically, as operated by the thermostat. |
MANUAL | Providing ON is selected, the receiver will switch on continuously, overriding the thermostat. |
[Image of receiver buttons: ON/OFF slider, AUTO/MANUAL slider]
Note: Please make sure to first wire up and turn on the receiver. After that insert the batteries.
2. RT510RF Thermostat
Insert 2 AA batteries into the thermostat.
Power up
After power up, the thermostat resets. During system reset, all LCD icons are displayed for 2 seconds, and the keys are locked. Then, all keys are unlocked, and the thermostat is initialized. The software version is shown. The typical reset display is shown below.
[Image of thermostat display showing reset status with icons and temperature]
The following tables show the default settings of the RT510 thermostat after Power on, or after the Reset button is pressed:
Function | Program | Weekday (M to F) | Weekend (SA to SU) |
---|---|---|---|
Operation Mode | Normal m | Time: 6:00am, Setpoint Temp: 21.0°C | Time: 8:00am, Setpoint Temp: 21.0°C |
Room Temperature | 22.0°C, within 5 s | Time: 8:00am, Setpoint Temp: 19.0°C | Time: 10:00am, Setpoint Temp: 19.0°C |
Clock | 12:00 | Time: 12:00pm, Setpoint Temp: 19.0°C | Time: 12:00pm, Setpoint Temp: 19.0°C |
AM/PM indicator | AM | Time: 2:00pm, Setpoint Temp: 19.0°C | Time: 2:00pm, Setpoint Temp: 19.0°C |
Program | Default fa | Time: 6:00pm, Setpoint Temp: 19.0°C | Time: 6:00pm, Setpoint Temp: 19.0°C |
Setpoint Temperature | Default fa | Time: 10:00pm, Setpoint Temp: 14.0°C | Time: 10:00pm, Setpoint Temp: 14.0°C |
Program Number | 1 | Time: 10:00pm, Setpoint Temp: 14.0°C | Time: 10:00pm, Setpoint Temp: 14.0°C |
SET indicator | Off | ||
PROG indicator | Off | ||
Frost Protection indicator | Off | ||
Heat indicator | Off | ||
Low-Battery Warning indicator | Off, to be seconds | ||
Output Relay | Off |
DIP Switch Settings
The DIP switches are on the rear of your thermostat and change the temperature accuracy (span) from +/-0.5°C to +/-0.25°C, and the programmes to 5-2 or 24h. Changing the Span DIP Switch (2) may cause your boiler to operate more frequently. The DIP switches are located on the back of the thermostat.
[Image showing DIP switch configurations: 24H +/-0.25 C, 5-2 +/-0.5 C]
Button Functions
Key | Function |
---|---|
❄️ | Press once to activate Frost Mode |
✈️ | Press for 3 seconds to activate Holiday Mode. |
+Hr | Press once to activate/deactivate Boost function |
⌂ | Press once to enter/exit Permanent Override function. |
⬆️ | Increase button |
⬇️ | Decrease button |
SELECT | Select the clock or programme settings |
SET | Press to confirm your settings |
⚪ | 1. Press once to enter in Test Mode for RT510RF 2. Press for 3 seconds to enter/exit Pairing Mode for RT510RF |
+⬆️⬇️ | Press the buttons for 3 seconds to enter Installer Mode |
SELECT SET | Press the buttons for 3 seconds to enter Clock Settings |
LCD Functions
[Image of thermostat LCD with numbered indicators]
- 1: Current day of the program
- 2: Current time
- 3: Temperature unit
- 4: AM/PM
- 5: Frost Mode ON
- 6: Holiday Mode ON
- 7: Temporary/Permanent Override
- 8: Heating Mode ON
- 9: Low battery
- 10: Boost Mode ON
- 11: Current temperature
- 12: Current program
Pair the RT510RF and RXRT510
Ensure the thermostat and receiver are paired. Use the Pairing or Testing procedure to check communication. The Pairing procedure sets up communication between them.
Pairing procedure
Note: Turn the receiver off and on again (ON-OFF-ON). The red LED will start flashing.
[Diagram showing receiver ON/OFF/AUTO/MANUAL states during pairing]
Testing procedure
[Diagram showing thermostat display and button presses for testing]
[Diagram showing receiver ON/OFF/AUTO/MANUAL states during testing]
[Thumbs up emoji indicating successful test]
Installer Mode
Access Installer Mode for advanced settings like frost setpoint, temperature offset, and temperature increments. Follow the steps below:
dxx | Function | Parameter | Description | Default value |
---|---|---|---|---|
d01 | Temperature display increments | 0.1 or 0.5°C | Select temperature display increments | 0.5°C |
d02 | Temperature offset | +/-3.0°C | Calibrate your thermostat temperature | 0.0°C |
d03 | Frost setpoint | 5.0-17.0°C | Set the Frost Point temperature | 5.0°C |
[Diagram showing steps to enter Installer Mode and adjust settings]
Operations
The RT510RF is user-friendly with minimal controls and an intuitive interface. The backlit LCD provides clear status indications.
Setting the time
[Diagram showing steps to set the time on the thermostat]
Follow similar steps to set the Day. Press SET to save options and return to the main screen.
Programming the RT510RF
Create personalized programs: 5-2 days or daily. Use DIP Switches to select.
RT510RF | ||
---|---|---|
5-2 Days Programme Weekdays: 6 sets of time/channel Weekends: 6 sets of time/channel Total: 12 settings/week |
24h Programme 24h: 6 sets of time/channel Total: 42 settings/week |
[Diagram showing steps to program the thermostat for 5-2 days or 24h]
Repeat steps for programs 2-6. Press SET to confirm changes and return to the Main Screen.
Note: Move the DIP Switch to 24h for individual programs. Follow 5-2 days program instructions.
Review the Setpoint temperature
When no button is pressed, the thermostat shows the actual room temperature. To review the setpoint temperature, follow these steps:
[Diagram showing steps to review setpoint temperature]
Functions
Actual room temperature vs. Setpoint (desired) temperature
[Diagram showing comparison of actual and setpoint temperatures]
Temporary Override
When active, the setpoint temperature changes until the next program starts.
[Diagram showing steps for temporary override]
Note: To exit temporary override, wait 3 seconds until the set temperature stops flashing or press SET once.
Permanent Override
[Diagram showing steps to activate and set temperature for permanent override]
The Override sign will appear on the main screen.
Note: To exit temporary override, wait 3 seconds until the set temperature stops flashing or press SET once.
Boost Function
Boost can be activated in Normal, Temporary, or Permanent Override modes. It cannot be set in Frost or Holiday Mode. Boost mode allows overriding the thermostat by setting a period and setpoint temperature.
a. Boost Function in Normal Mode
[Diagram showing steps for Boost Function in Normal Mode]
Note: RT510RF works in Boost Mode for up to 9 hours. After Boost time, it returns to Normal Mode following the schedule.
b. Boost Function in Permanent Override Mode
[Diagram showing steps for Boost Function in Permanent Override Mode]
c. Boost Function in Temporary Override Mode
[Diagram showing steps for Boost Function in Temporary Override Mode]
Note: RT510RF works in Boost Mode for up to 9 hours. After Boost time, it returns to Permanent Override Mode.
d. Boost Function in Frost/Holiday Mode
[Diagram showing Frost mode ON and Holiday mode ON]
Note: Boost function is canceled in Frost/Holiday Mode. Boost cannot be activated in Frost or Holiday Mode.
Frost Function
Frost function allows turning Frost protection ON or OFF. The default frost setpoint is 5°C. You can change this using Installer Mode parameters (d03). If room temperature is lower than the frost setpoint, the thermostat automatically enters Frost mode ON.
Follow the steps below for setting up the Frost Mode:
[Diagram showing steps to set Frost Mode ON and OFF]
Holiday Function
Holiday function turns off the relay, blocking heat calls. If room temperature is lower than the frost setpoint, Frost Mode will be activated.
Follow the steps below to set the Holiday Mode:
[Diagram showing steps to set Holiday Mode ON and OFF]
Other Functions
Backlight
The backlight turns on when keys are pressed and stays on for approximately 5 seconds after the last key press, except during settings changes (Clock, Programme, Temporary Override), where it remains illuminated. The backlight will not illuminate if the RT510RF battery is low.
Battery Status
The RT510RF monitors battery voltage. A low battery indicator (around 2.6V) will display when voltage is low. Replace batteries promptly to avoid operating problems. The device uses internal memory to back up settings for 30 seconds during battery changes.
Reset Function
Sleep Mode
Pressing UP and DOWN keys together enters SLEEP mode. All functions pause to save battery, except the clock. The LCD display is blank, and all output is turned off. Press any key to wake up and cancel SLEEP mode.
[Diagram showing steps to enter Sleep Mode]
Reset to Factory Settings
The Reset Button restores default factory settings, deleting all previous entries. This should only be done by an installer.
[Diagram showing steps to perform a factory reset using the reset button]