ℹ️ Document Conversion Notice:
This document has been converted from PDF and formatted to fit this screen. Diagrams and images may be available only in the original here.
AprilAire Ventilation
Model 8145A Fresh Air Ventilator
Introduction and Compliance Statement
The AprilAire Model 8145A Fresh Air Ventilator is designed to introduce a precise amount of outdoor air into modern, efficiently designed homes. The installation involves ducting the ventilator's inlet to an outdoor air intake and its discharge to the HVAC system. Once connected, the unit is plugged in, the required ventilation amount is set, and desired temperature limits are selected.
When installed and configured correctly, the Model 8145A Fresh Air Ventilator meets the mechanical ventilation requirements of:
Energy Star Certified Homes
EPA Indoor airPLUS
2012-2018 International Residential Code (IRC)
2012-2018 International Energy Conservation Code (IECC)
California Energy Commission Title 24
ASHRAE Standard 62.2-2010
ASHRAE Standard 62.2-2013 & 2016
Specifications
Table 1: Specifications
External Static Pressure ("w.c.)
Airflow (CFM)
Efficacy (CFM/watt)
Voltage
0.0
210
5.2
120 VAC 1 phase 60 Hz
0.2
180
4.4
0.4
150
3.5
0.6
120
2.8
Figure 1: Dimensions (Inches)
Diagram showing the AprilAire Model 8145A Fresh Air Ventilator from multiple angles. Key features indicated are the inlet collar (6" diameter, round) and the outlet collar (6" diameter, oval). Dimensions for width, height, and depth are provided.
Safety Instructions
⚠️ WARNING
120 Volts may cause serious injury from electric shock. Disconnect electrical power before starting installation or servicing. Leave power disconnected until installation/service is completed.
Sharp edges may cause serious injury from cuts. Use care when cutting plenum openings and handling duct work.
⚠️ CAUTION
Read all instructions before beginning installation.
Improper installation may cause property damage or injury. Installation, service, and maintenance must be performed by a qualified service technician.
Installation
Install Electrical Outlet
Install a standard NEMA 5-15 receptacle suitable for the location, near where the ventilator will be installed. The ventilator comes equipped with a 6-foot power cord with a standard 3-prong plug.
Ventilator Location and Orientation
If the outlet of the ventilator is not ducted, or if small sections of collapsible duct (i.e., flex duct) are attached to the outlet, then the ventilator must be mounted in a location which minimizes interference with moving parts. Refer to the CAUTIONS above.
Figure 2: Clearances for Servicing. This diagram illustrates the necessary space around the ventilator for maintenance. It indicates 12 inches of clearance for filter access and 24 inches of clearance for fan access.
Choose a location for the ventilator that is within 6 feet of the outlet into which the ventilator will be plugged. Allow space for filter removal and service as shown in Figure 2.
The ventilator can be mounted in any orientation.
Mount the Ventilator
1. Select the appropriate brackets, large or small, for mounting the ventilator (see Figure 3). If mounting to the wall or hanging from joists, use the four small mounting brackets. If mounting on or in between the floor joists, install all four smaller brackets for 13" on center joists, or two small and two longer brackets for 16" on center joists.
Figure 3: Brackets. Shows different types of mounting brackets provided for installation.
2. Snap the brackets into the proper locations as shown in Figure 4. Use the mounting locations nearest the cover for mounting between floor joists or hanging from rafters. Use the mounting locations near the bottom of the unit for surface mounting (i.e., to a flat wall, ceiling surface, or bottom of joists).
Figure 4: Mounting Bracket Positioning. Illustrates how to position brackets for 'Between Joists', 'Hanging Installation', and 'Surface Mount' configurations.
3. Screw the ventilator brackets into joists or a strong platform using the #10 x 3/4" screws provided. The ventilator weighs approximately 15 pounds, so do not secure into drywall alone.
Mount Intake Hood
Install a weather-tight hood with a bird screen. Cut a hole in the exterior wall large enough to fit a 6" insulated flexible duct through with minimal compression of the insulation. Pull the duct through the hole and attach the flex duct to the collar of the hood. Use metal foil tape or a plastic zip-tie to secure the duct to the collar. Pull the insulation and vapor barrier over the duct and tape it to the collar.
IMPORTANT: The end of the insulation must be sealed to prevent condensation from forming inside the insulation. If a plastic zip-tie is used to secure the insulation to the hood collar, also tape the end to seal it against condensation problems.
Press the hood against the outside wall and secure in place with screws; seal around the perimeter of the hood with caulk.
Install Ductwork
Install 6" diameter flexible, insulated duct from the round inlet collar of the unit to the intake hood and from the oval outlet collar of the unit to the HVAC system. Duct the outlet of the ventilator to the return side of the HVAC system (refer to Figure 5).
Figure 5: Ducting in Upflow and Horizontal HVAC Systems. Shows two typical installation scenarios: Attic Installation and Basement Installation. Both diagrams illustrate the fresh air intake hood with screen, fresh air intake duct, fresh air ventilator, filter, and connection to the furnace/air handler, with airflow indicated.
Wiring the Control to the HVAC System
NOTICE: Disconnect power to HVAC system during wiring to avoid electrical shorts.
1. Remove the control knob and cover as shown in Figure 6. Set aside in a safe place until all wiring has been completed.
Figure 6: Remove Control Knob and Cover. Illustrates the process of removing the control knob and cover from the ventilator unit.
2. Run a 4 or 5 conductor cable between the control and the HVAC system.
3. Wire to the HVAC system in accordance with Figure 7 or Figure 8.
Figure 7: Preferred - Ventilator Turns On the HVAC System Blower as Needed. This wiring diagram shows connections between the thermostat, ventilation control, and HVAC system control terminals for the preferred method.
Figure 8: Alternate - Ventilator Does Not Turn On the HVAC System Blower. This wiring diagram shows alternative connections for wiring the ventilator control to the HVAC system.
DO NOT REMOVE THE PRE-INSTALLED YELLOW OR BLACK WIRES WHEN WIRING TO THE HVAC SYSTEM.
Setup and Operation
Set Up
The control can be set up to prevent ventilation during the hottest or coldest periods of the day. When the outdoor temperature exceeds the high value or falls below the low value, ventilation will stop and additional ventilation will be brought in at a later time. Refer to START UP AND SEQUENCE OF OPERATION for details.
1. Turn the vent time setting knob to "OFF".
2. Remove the knob then remove the cover to adjust the high/low temperature limit.
3. Use a small flat head screwdriver to turn the potentiometer to select:
A - No limit, time only
B - 105°F high limit, 20°F low limit
C - 100°F high limit, 30°F low limit
D - 95°F high limit, 40°F low limit
Figure 9: Adjust High/Low Temperature Limit. Shows the control panel with the potentiometer adjustment for setting temperature limits.
Test
After all ducting and wiring is complete, plug in the ventilator, restore power to the HVAC system, and make sure the switch controlling the outlet into which the ventilator is plugged is turned on. Turn the thermostat to the OFF mode to ensure that wiring the HVAC system has been done correctly. Rotate the Vent Time setting knob to Test/Reset:
The display will show "--", the green "Active Ventilation" LED will blink.
The ventilator blower will start.
If the ventilator was properly wired to turn on the HVAC unit blower with ventilation, the HVAC blower will turn on.
After one minute, the test will end and the display will blink and show the firmware revision level. Return the knob to the OFF position until the desired Time Setting is determined.
Measure Delivered Airflow
1. Make sure the ventilator is plugged in and the integral control is wired to the HVAC system.
2. Use 1/4" flexible tubing to attach a pressure gauge set to "w.c." (sometimes shown as "in. w.g." or "in. H2O") to the inlet and outlet pressure ports on the ventilator. The pressure gauge should have as small a range as possible to get a meaningful measurement; a range of 1.0" w.c. should be sufficient. Connect the high or "+" port of the gauge to the outlet pressure port on the ventilator, and the low or "-" port of the gauge to the inlet pressure port on the ventilator. See Figure 10.
Figure 10: Measure Pressure at Inlet and Outlet Pressure Ports. Illustrates connecting a pressure gauge to the inlet (low port) and outlet (high port) of the ventilator.
3. Turn on the ventilator by turning the control knob to 60.
4. Use the label on the cover of the ventilator, or Table 2, to convert the pressure reading to delivered airflow. If the pressure reading falls between listed values, either use the lower value or interpolate between values: CFM = Lower Value + [(Higher Value – Lower Value) * 10 * (Pressure Reading – Lower Value Pressure)]. The following is an example:
a. Measured Pressure Reading is 0.34" w.c.
b. Table 2 lists 200 CFM @ 0.3" w.c. and 170 @ 0.4" w.c.
c. Either use 170 CFM or interpolate: CFM = 200 - [(200–170) * 10 * (0.34-0.3)] = 200 - [(30) * 10 * (0.04)] = 200 - 12 = 188 CFM. Interpolating will demonstrate higher delivered airflow, but requires a calculation to be done.
Table 2: Delivered Airflow Corresponding to Measured Pressure at Ventilator Pressure Ports
Measured Pressure ("w.c.)
Delivered Airflow (CFM)
0.1
255
0.2
225
0.3
200
0.4
170
0.5
145
0.6
115
0.7
90
Determine Ventilation Time Setting
Calculating Airflow Requirement
1. The MINIMUM ventilation requirement is calculated using ASHRAE 62.2-2010.
ASHRAE Airflow in CFM = [House Area in Sq. Ft. x 0.01] + [(Number of Bedrooms +1) x 7.5]
NOTE: Use 'Number of Bedrooms + 1' or 'Number of Occupants', whichever is larger.
2. Table 3 shows the calculated airflow values to the nearest 5 CFM.
3. Record the required CFM.
Table 3: CFM Required
House Sq. Ft.
Number of Bedrooms
2
3
4
5
6
7
1000
35
40
50
55
65
70
1500
40
45
55
60
70
75
2000
45
50
60
65
75
80
2500
50
55
65
70
80
85
3000
55
60
70
75
85
90
3500
60
65
75
80
90
95
4000
65
70
80
85
95
100
4500
70
75
85
90
100
105
5000
75
80
90
95
105
110
Measure Ventilation Air (CFM) Delivery Rate and Select Vent Time
1. Measure the outdoor air flow (CFM) through the duct that is bringing in only outdoor air.
2. Use the CFM Delivered along with the CFM required to find the Cycle Time per hour setting from Table 4. For example, if the ventilator is providing 120 CFM, and the requirement is 70 CFM, set the time to 35 minutes.
3. Use the control knob to set the vent time to the determined minutes per hour. NOTE: knob can be set halfway between printed numbers to achieve 5 minute increments.
Table 4: Cycle Time Setting (Minutes) for Airflow Delivered vs. Airflow Required for 1 Hour Cycle
CFM Delivered
CFM Required
20
30
40
50
60
70
80
90
100
110
60
20
30
40
50
60
80
15
25
30
40
45
55
60
100
15
20
25
30
35
40
50
55
60
120
15
15
20
25
30
35
40
45
50
55
140
15
15
15
20
25
30
35
40
45
50
160
15
15
15
20
25
25
30
35
40
45
180
15
15
15
20
20
25
30
30
35
40
200
15
15
15
15
20
25
25
30
30
35
220
15
15
15
15
20
20
20
25
30
30
Start Up and Sequence of Operation
Set the Ventilation Time knob to the setting that was determined in the previous section. The ventilator will turn on with the HVAC equipment for the set number of minutes during the one-hour cycle period. If the HVAC equipment does not turn on enough, the ventilator will turn on, and will turn on the HVAC system blower if wired to do so, at the end of the one-hour cycle period to ensure the desired ventilation time is met. The first time it turns on, it will stay on for five minutes to get an accurate air temperature measurement. If the air temperature is within the range that is set (see SET UP), the ventilator will turn on for the amount of time selected within the one-hour cycle period.
If the air temperature is outside of the set range, then no additional ventilation will occur for another hour, and the cycle period will automatically adjust to four hours. When the ventilator starts again, it will sample the air temperature and if in range, will meet the set amount of ventilation during the four-hour cycle period. For example, if the Vent Time was set to 25 minutes per hour and the first time the ventilator came on it measured an air temperature above the high limit setting, it would turn off after five minutes. The control will automatically change the cycle period to four hours and work to provide the additional 95 total minutes of ventilation (25 min/hr * 4 hours = 100 minutes, minus the five minutes of the first air sampling) during the four-hour cycle period.
If the air temperature is still out of range, the control will automatically switch to an 8-hour cycle period, then a 12-hour cycle period and finally a 24-hour cycle period. During 8, 12 and 24 hour cycle periods, the total ventilation time increases to compensate for ventilation effectiveness as defined in ASHRAE Standard 62.2-2010. When the cycle period automatically adjusts to 24-hours, the control will turn on ventilation to meet the requirements even if the temperature is outside of the set limits.
Filter Cleaning
Normally, the fresh air filter will need to be removed and cleaned every six months, but check it after the first three months following installation to determine if more or less frequent cleaning will be necessary. After cleaning the filter inside the ventilator, clean off the screen at the fresh air intake hood on the outside of the house. The most common cause of reduced ventilation is a clogged air intake hood.
To clean the ventilator filter (see Figure 11):
Flex the outside edges of the filter door to disengage it from the housing.
Lift the filter door to remove the filter from the ventilator.
Use water to rinse the filter and shake the excess moisture off the filter.
Replace the filter in the ventilator and press the outside edges of the filter door to snap it in place.
Figure 11: Filter Access. Illustrates how to open the filter door and remove the filter from the ventilator.
Internal Schematics and Warranty
Internal Schematics
Figure 12: Model 8145A Internal Schematic. This diagram shows the internal electrical connections of the ventilator, including the blower motor, run capacitor, damper motor, and power PCB assembly. It also details the ventilation control terminals (R, C, Used, Not Used, ODT, W, G, VENT, GF).
CAPPED RED & WHITE WIRES ARE LOCATED INSIDE THE FILTER DOOR TO POWER THE CONTROL (R & C TERMINALS) FROM THE POWER PCB ASSEMBLY. USE ONLY IF THE VENTILATON CONTROLLER WILL NOT BE WIRED TO THE HVAC SYSTEM.
Limited Warranty
Your AprilAire® Fresh Air Ventilator is expressly warranted for five (5) years from date of installation to be free from defects in materials or workmanship. AprilAire's exclusive obligation under this warranty shall be to supply, without charge, a replacement for any component which is found to be defective within such five (5) year period and which is returned not later than thirty (30) days after said five (5) year period by you to either your original supplier or to AprilAire, Madison, Wisconsin 53701, together with the model number and installation date of the ventilator.
THIS WARRANTY SHALL NOT OBLIGATE APRILAIRE FOR ANY LABOR COSTS AND SHALL NOT APPLY TO DEFECTS IN WORKMANSHIP OR MATERIALS FURNISHED BY YOUR INSTALLER AS CONTRASTED TO DEFECTS IN THE VENTILATOR ITSELF.
IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED IN DURATION TO THE AFORESAID FIVE YEAR PERIOD. APRILAIRE'S LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, OTHER THAN DAMAGES FOR PERSONAL INJURIES, RESULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED. THIS LIMITED WARRANTY IS VOID IF DEFECTS(S) RESULT FROM FAILURE TO HAVE THIS UNIT INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR. IF THE LIMITED WARRANTY IS VOID DUE TO FAILURE TO USE A QUALIFIED CONTRACTOR, ALL DISCLAIMERS OF IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON INSTALLATION.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages so the above exclusion or limitations may not apply to you.
This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Warranty Registration
Visit us online at aprilaire.com to register your AprilAire product. If you do not have online access, please mail a postcard with your name, address, phone number, email address, product purchased, model number, date of purchase, and dealer name and address to: AprilAire, P.O. Box 1467, Madison, WI 53701.
Your warranty registration information will not be sold or shared outside of this company.
aprilaire 8145a article 1604089115201405 en ii Adobe PDF Library 16.0.7 Adobe InDesign 17.2 (Macintosh)
Related Documents
AprilAire V42SNA Fresh Air Ventilator Installation and Operating Instructions Comprehensive installation and operating guide for the AprilAire V42SNA Fresh Air Ventilator, covering setup, wiring, testing, and troubleshooting for optimal home ventilation. Includes specifications, safety warnings, and warranty information.
Aprilaire 8192A Fresh Air Ventilator with Dehumidification Specification Sheet Specification sheet for the Aprilaire 8192A Fresh Air Ventilator with Dehumidification. Details include airflow, capacity, energy efficiency, dimensions, features, benefits, and recommended controls for improved indoor air quality and humidity management.
Aprilaire Model 8142 Fresh Air Ventilator Specification Sheet Detailed specifications, features, benefits, and installation guidelines for the Aprilaire Model 8142 Fresh Air Ventilator with backdraft damper, designed to improve indoor air quality and meet energy efficiency standards.
Aprilaire Fresh Air Ventilation Product Guide: Improve Home Air Quality Discover Aprilaire's advanced fresh air ventilation systems, including ventilators, controllers, and ERVs. Enhance indoor air quality, manage humidity, and meet building codes with Aprilaire's energy-efficient solutions for residential and multi-family homes.
AprilAire E100V/8190FF Ventilating Dehumidifier Specification Sheet Detailed specifications, features, and benefits of the AprilAire E100V Ventilating Dehumidifier, designed to improve indoor air quality by removing excess moisture from outdoor air and meeting key ventilation standards.
AprilAire E100V/8190FF Ventilating Dehumidifier Specification Sheet Detailed specifications, features, and benefits of the AprilAire E100V Ventilating Dehumidifier and 8190FF Ventilation Plenum, designed for enhanced indoor air quality and humidity control in residential settings.