European Technical Assessment ETA-21/0678

Issued by: ETA-Danmark A/S

Date of Issue: 2021/08/17

General Part

Technical Assessment Body

ETA-Danmark A/S, designated according to Article 29 of Regulation (EU) No 305/2011.

Product Identification

Trade name of the construction product: fischer FFSC Fire Stop Compound

Product family: Fire Stopping, Fire Sealing & Fire Protective Products. Fire Retardant Products

Manufacturer: fischerwerke GmbH & Co. KG

Address: Klaus-Fischer-Straße 1, DE-72178 Waldachtal

Telephone: +49 7443 12-0

Internet: www.fischer.de

Manufacturing plant: fischerwerke GmbH & Co. KG

Document Details

Content: 19 pages including 2 annexes.

Issued in accordance with: Regulation (EU) No 305/2011.

Basis: EAD 350454-00-1104 Firestopping and fire sealing products, Penetration Seals.

This version replaces: -

1 Technical Description of the Product

fischer FFSC Fire Stop Compound is a gypsum-based mortar material used to reinstate the fire resistance performance of floor and wall constructions where apertures for multiple services have been provided.

It is supplied as a dry material and is mixed with water to the required ratio prior to installation.

When mixed, fischer FFSC Fire Stop Compound is self-supporting in floors and walls up to a maximum of 1100mm x 1100mm. Temporary shuttering is required to support the wet weight of the compound.

2 Specification of The Intended Use In Accordance With The applicable European Assessment (EAD)

The intended use of fischer FFSC Fire Stop Compound is to reinstate the fire resistance performance of rigid wall and floor constructions penetrated by various cables and metallic pipes.

Elements of Construction for Penetration Seals

Rigid Floors: Must have a minimum thickness of 150 mm and comprise concrete, aerated concrete or masonry with a minimum density of 650 kg/m³.

Rigid Walls: Must have a minimum thickness of 150 mm and comprise concrete, aerated concrete or masonry with a minimum density of 650 kg/m³.

The supporting construction must be classified in accordance with EN 13501-2 for the required fire resistance period.

Service Penetrations

fischer FFSC Fire Stop Compound may be used to provide a penetration seal with cables, cable trays, and insulated metallic pipes (details in Annex B).

The total cross-sectional area of services (including insulation) should not exceed 60% of the penetration area.

Services in floors shall be supported at a maximum of 450mm from the exposed face.

Services in walls shall be supported at a maximum of 150mm from both faces of the wall.

Working Life

The provisions in this assessment are based on an assumed working life of 25 years, provided conditions for packaging, transport, storage, installation, use, and repair are met. These indications are for product selection guidance and not a guarantee.

Use Category

Type Z1: Intended for internal conditions with humidity equal to or higher than 85% RH, excluding temperatures below 0°C, without exposure to rain or UV.

3 Performance of The Product And References To The Methods Used For Its Assessment

BWRCharacteristicAssessment of characteristic
2Safety in case of fireReaction to fire: See Clause 1.1
Resistance to fire: See clause 1.2
3Hygiene, Health and the EnvironmentDangerous substances: See clause 2.1
4Safety and accessibility in useDurability and serviceability: See clause 3.1
5Protection against noiseAirborne sound insulation: See clause 4.1
6Energy, Economy and Heat Retention-

3.1 Safety in case of fire

3.1.1 Reaction to fire

No performance assessed.

3.1.2 Resistance to fire

fischer FFSC Fire Stop Compound has been tested in accordance with EN 1366-3 and classified in accordance with EN 13501-2 (as given in Annex B).

Seals may only be penetrated by services described in Annex B; other parts or support constructions must not penetrate the seal.

The service support construction must be fixed to the building element containing the penetration seal or a suitable adjacent element. For floors, the unexposed side must not impose additional load on the seal in case of fire. Unexposed face support must be maintained for the required fire resistance period.

In floors, seals must be installed over a shutter capable of supporting the mortar's weight; the shutter should remain in place.

Cables should be insulated with minimum 45kg/m³ Rockwool Duct Wrap, minimum 25mm thick, 500mm long to the unexposed face.

Pipes should be insulated with minimum 150kg/m³ Rockwool H&V Pipe Section, minimum 50mm thick, 500mm long to the unexposed face (CI).

Pipes must be perpendicular to the seal surface.

It is assumed that compressed air systems are switched off by other means in case of fire. The function of pipe seals in pneumatic dispatch or pressurised air systems is guaranteed only when these systems are shut off.

The assessment does not cover the destruction of the seal or abutting building elements by forces from temperature changes during fire; this must be considered in piping system design.

The approval does not address risks from leakage of dangerous liquids or gases due to pipe failure.

The durability assessment does not account for the effect of substances permeating through the pipe on the seal.

Classifications relate to C/U (capped inside / un-capped outside the furnace) for insulated metallic pipes. Refer to national regulations for further information.

3.2 Health, hygiene and the environment

3.2.1 Dangerous Substances

The applicant declares that fischer FFSC Fire Stop Compound does not contain any substance of high concern regarding REACH Regulations and complies with requirements referenced at http://ec.europa.eu/enterprise/construction/cpd-ds/index.cfm.

Additional requirements applicable to products within its scope may exist based on transposed European legislation and national laws.

3.3 Safety and accessibility in use

3.3.1 Durability and serviceability

fischer FFSC Fire Stop Compound was tested according to EOTA Technical Report - TR024 for type Z1 use category. Test results demonstrate suitability for penetration seals in internal conditions with humidity equal to or higher than 85% RH, excluding temperatures below 0°C, without exposure to rain or UV.

3.4 Protection against noise

3.4.1 Airborne noise Insulation

The test results provided a single number rating of Rw (C;Ctr) = 47(-1;-3)dB.

4 Assessment And Verification Of Constancy Of Performance (AVCP) System

The AVCP system applied, according to decision 1999/454/EC, is System 1.

ProductsIntended use/sAVCP System
Fire stopping and fire sealing productsFor fire compartmentation and / or fire protection or fire performanceSystem 1

5 Technical Details Necessary For The Implementation of The AVCP System

Technical details for the AVCP system implementation are laid down in the control plan deposited at ETA-Danmark A/S prior to CE marking.

Issued in Copenhagen on 2021-08-17 by Thomas Bruun, Managing Director, ETA-Danmark

Annex A: Reference Documents

  • EN 13501-1: Fire classification of construction products and building elements – Part 1: Classification using test data from reaction to fire tests.
  • EN 13501-2: Fire classification of construction products and building elements – Part 2: Classification using test data from fire resistance tests.
  • EOTA TR 024: Characterisation, Aspects of Durability and Factory Production Control for Reactive Materials, Components and Products.

Annex B: Resistance to Fire Classification of fischer FFSC Fire Stop Compound

B.1 Rigid floor constructions (minimum 150 mm thickness)

B1.1 Penetration seal (100mm depth, maximum seal size 1100mm x 1100mm)

Penetration Seal: Metallic pipes (insulated) penetrating through a rigid floor construction. fischer FFSC Fire Stop Compound applied flush with the upper surface of the floor, sealing around services and gaps.

Pipes Insulation: Minimum 150kg/m³ Rockwool H&V foil faced mineral insulation, 50mm thick, projecting 450mm from the unexposed surface of the floor.

Construction Details (B1.1):

A cross-section illustrating a rigid floor construction with a penetration. The floor slab is 150mm thick blockwork. A metallic pipe, insulated with 50mm thick Rockwool H&V foil faced mineral insulation, passes through the floor. The fischer FFSC Fire Stop Compound seals the penetration. Shuttering material is shown supporting the seal during curing. The insulation projects 450mm from the unexposed surface.

B 1.1.1 Separation of openings (minimum 200 mm)

The following table details classifications for copper and cast iron pipes:

ServicesClassification
Copper and cast iron pipe 18-107mm diameter and 0.8-1.5mm wall thickness, insulated with Rockwool H&V wrapE 240 C/U and C/C
EI 30 C/U and C/C

A graph illustrates allowable combinations of pipe diameter and wall thickness for E240 and EI30 classifications.

B 1.1.2 Separation of openings (minimum 200 mm)

The following table details classifications for steel pipes:

ServicesClassification
Steel pipe 40 - 165mm diameter and 3 - 5mm wall thickness, insulated with Rockwool H&V wrapE 240 C/U and C/C EI 120 C/U and C/C

A graph illustrates allowable combinations of pipe diameter and wall thickness for E240 and EI120 classifications.

B2.1 Penetration seal (cables, 100mm depth, maximum seal size 1100mm x 1100mm)

Penetration Seal: Cables (insulated) penetrating through a rigid floor construction. fischer FFSC Fire Stop Compound applied flush with the upper surface of the floor, sealing around services and gaps.

Cables Insulation: Minimum 150kg/m³ Rockwool H&V foil faced mineral insulation, 50mm thick, projecting 450mm from the unexposed surface of the floor.

Construction Details (B2.1):

A cross-section illustrating a rigid floor construction with cable penetrations. The floor slab is 150mm thick blockwork. A cable tray/ladder supports insulated cables. The cables are insulated with 25mm thick Rockwool Ductwrap insulation. The fischer FFSC Fire Stop Compound seals the penetration. Shuttering material is shown supporting the seal during curing. The insulation projects 450mm from the unexposed surface.

B 2.1.1 Separation of openings (minimum 200 mm)

ServicesClassification
Electrical cables, maximum 80mm diameter, insulated with Rockwool DuctwrapEI 120
Non-sheathed wire, maximum 24mm diameter, insulated with Rockwool DuctwrapE 240
EI60
Telecomm cable, maximum 21mm diameter in bundles up to 100mm diameter, insulated with Rockwool Ductwrap. Seal thickness 100mmEI60

B 2.2.1 Penetration seal (cables, 150mm depth, maximum seal size 1100mm x 1100mm)

Penetration Seal: Cables (insulated) penetrating through a rigid floor construction. fischer FFSC Fire Stop Compound applied flush with the upper surface of the floor, sealing around services and gaps.

Cables Insulation: Minimum 150kg/m³ Rockwool H&V foil faced mineral insulation, 50mm thick, projecting 450mm from the unexposed surface of the floor.

Construction Details (B2.2.1):

A cross-section illustrating a rigid floor construction with cable penetrations. The floor slab is 150mm thick blockwork. A cable tray supports insulated cables. The cables are insulated with 25mm thick Rockwool Ductwrap insulation. The fischer FFSC Fire Stop Compound seals the penetration. Shuttering material is shown supporting the seal during curing. The insulation projects 450mm from the unexposed surface.

B2.2.2 Separation of openings (minimum 200 mm)

ServicesClassification
Telecom cable maximum 21mm diameter in bundles up to 100mm diameter, insulated with Rockwool Ductwrap. Seal thickness 150mmEI 180

B.3 Rigid wall constructions (minimum 150 mm thickness)

B 3.1 Penetration seal (100mm depth, maximum seal size 1100mm x 1100mm)

Penetration Seal: Metallic pipes (insulated) penetrating through a rigid wall construction. fischer FFSC Fire Stop Compound applied flush with the upper surface of the wall, sealing around services and gaps.

Pipes Insulation: Minimum 150kg/m³ Rockwool H&V foil faced mineral insulation, 50mm thick, projecting 450mm from the unexposed surface of the floor.

Construction Details (B3.1):

A cross-section illustrating a rigid wall construction with a penetration. The wall is 150mm thick blockwork. A metallic pipe, insulated with 50mm thick Rockwool H&V pipe insulation, passes through the wall. The fischer FFSC Fire Stop Compound seals the penetration. "Unistrut" channels support the pipe at 150mm and 450mm from the fire seal. Shuttering material is shown supporting the seal during curing.

B 3.1.1 Separation of openings (minimum 200 mm)

The following table details classifications for copper and cast iron pipes:

ServicesClassification
Copper and cast iron pipe 18-107mm diameter and 0.8-1.5mm wall thickness, insulated with Rockwool H&V wrapE 240 C/U and C/C EI 30 C/U and C/C

A graph illustrates allowable combinations of pipe diameter and wall thickness for E240 and EI30 classifications.

B 3.1.2 Separation of openings (minimum 200 mm)

The following table details classifications for steel pipes:

ServicesClassification
Steel pipe 40 - 165mm diameter and 3 - 5mm wall thickness, insulated with Rockwool H&V wrapE 240 C/U and C/C EI 120 C/U and C/C

A graph illustrates allowable combinations of pipe diameter and wall thickness for E240 and EI120 classifications.

B 3.2 Penetration seal (cables, 100mm depth, maximum seal size 1100mm x 1100mm)

Penetration Seal: Cables (insulated) penetrating through a rigid wall construction. fischer FFSC Fire Stop Compound applied flush with the upper surface of the wall, sealing around services and gaps.

Cables Insulation: Minimum 150kg/m³ Rockwool H&V foil faced mineral insulation, 50mm thick, projecting 450mm from the unexposed surface of the floor.

Construction Details (B3.2):

A cross-section illustrating a rigid wall construction with cable penetrations. The wall is 150mm thick blockwork. A cable tray supports insulated cables. The cables are insulated with 25mm thick Rockwool Ductwrap insulation. The fischer FFSC Fire Stop Compound seals the penetration. "Unistrut" channels support the cable tray at 150mm and 450mm from the fire seal. Shuttering material is shown supporting the seal during curing.

B 3.2.1 Separation of openings (minimum 200 mm)

ServicesClassification
Electrical cables, maximum 80mm diameter, insulated with Rockwool DuctwrapE 180
EI120
Non-sheathed wire, maximum 24mm diameter, insulated with Rockwool DuctwrapE 240
EI180
Telecomm cable, maximum 21mm diameter in bundles up to 100mm diameter, insulated with Rockwool Ductwrap. Seal thickness 100mmEI180
Steel cable trays and cable ladders up to 500mm wide, insulated with Rockwool DuctwrapEI90

PDF preview unavailable. Download the PDF instead.

ZD ETAB 21-0678 EN V1 Microsoft Word til Microsoft 365

Related Documents

Preview Independent Technical Assessment of fischer HybridPower 10x90 Fire Resistance
This report presents the independent technical assessment of the fischer HybridPower 10x90 anchor system's performance under fire exposure, evaluated against EAD 330232-01-0601 and EAD 330284-00-0601-v01. It details fire resistance for various load conditions and failure modes in concrete.
Preview fischer FIS EM Plus: Epoxy Mortar for Adhesive Anchoring Systems
Comprehensive installation guide and technical specifications for the fischer FIS EM Plus epoxy adhesive anchoring system, detailing applications, performance data, and installation procedures for concrete and rebar connections.
Preview Fischer FIS V Plus Injection Mortar: Technical Data, Specifications, and Installation Guide
Comprehensive technical specifications, installation instructions, and product details for the Fischer FIS V Plus chemical injection mortar system, including data on concrete and masonry applications, rebar connections, and various product variants.
Preview Fischer FIS EP Injection System: Declaration of Performance and Technical Assessment
Official Declaration of Performance (DoP) and European Technical Assessment (ETA) for the Fischer FIS EP injection system, a bonded fastener for concrete applications. Details technical specifications, installation guidelines, and performance data for construction professionals.
Preview Fischer Pipe Clamps FRS Series: Product Overview and Technical Data
A comprehensive guide to Fischer's FRS, FRS zl, and FRS A2/A4 pipe clamps, detailing their applications, advantages, properties, and technical specifications for secure pipe fixing in various environments.
Preview fischer Bolt Anchor FBN II HDG: European Technical Assessment ETA-18/0101
Detailed technical assessment for the fischer Bolt Anchor FBN II HDG, covering product description, specifications, intended use, performance data, installation, and durability for use in uncracked concrete.
Preview fischer FRS-FP Fire Protection Coating: Technical Datasheet and Application Guide
Comprehensive technical datasheet for fischer FRS-FP, a waterborne intumescent fire protection coating. Includes characteristics, technical data, system components, processing instructions, and approvals.
Preview Fischer Sliding Hanger SB: Lightweight Pipe Support with Fire Test Report
Discover the Fischer Sliding Hanger SB, a lightweight and robust sliding element for pipeline systems. Featuring fire test reports (R 120, R 30 MLAR), adjustable axial length, and durable steel construction with zinc plating, it ensures secure and efficient pipe mounting in dry interior environments.