Components for system solutions
MCB Miniature circuit breaker
8530/1-MCB-STA103-C16-500-4 Art. No. 293900
Product Features
- Isolation function in accordance with EN60947-2
- Energy limitation class 3
- Simple replacement or expansion of system thanks to modular circuit breaker design
- Simple installation - snaps onto the mounting rail in Ex e enclosures
- Non-adjustable thermal and magnetic releases
- Ergonomically shaped operating lever for safe switching on and off
- Padlocks (Accessories) provide protection against being switched on again during maintenance work
MY R. STAHL 8530A [Explosive atmosphere protection]
R. STAHL 8530 series miniature circuit breakers are overcurrent devices with good current limiting for short circuits and high switching capacity (10, 15, or 25 kA). They offer low load on cables and high selectivity for upstream fuses. The components have a modular design and are available in 1- to 4-pole versions for rated currents of 0.5-63 A. The maximum installation capacity is 4.5 subunits.
Technical Data
Explosion Protection
- Application range (zones): 1, 2
- Application range (Zone) note: For use in Zone 21/22 when protected by Ex tb/tc enclosure
- IECEX gas certificate: IECEx FMG 19.0029U
- IECEx gas explosion protection: Ex db eb IIC Gb
- ATEX gas certificate: FM19ATEX0191U
- ATEX gas explosion protection: II 2 G Ex db eb IIC Gb
- Certificates: ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
- Declaration of conformity: Certificate of conformity (ATEX)
Electrical Data
Rated operational voltage AC | 230/400 V |
Rated operational current | 16 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | Auxiliary contact 1 change-over contact + fault signal contact 1 change-over contact |
1st auxiliary function for AC rated voltage | 230 V |
1st auxiliary function for rated current max. | 2 A |
2nd auxiliary function | without |
2nd auxiliary function voltage max. DC | - |
Tripping characteristic | C |
No. of poles | 3-pole |
Ambient Conditions
- Ambient temperature: -40 °C ... 70 °C
- Ambient temperature: -40 °F ... 158 °F
- Ambient temperature note: Deviating ambient temperatures based on current certificates available on request
Mechanical Data
- Degree of protection (IP) (IEC 60529): IP2X
- Enclosure material: Thermoplast
- Connection cross section min.: 1.5 mm²
- Connection cross-section max.: 25 mm²
- Connection cross-section AWG min.: 16 AWG
- Connection cross-section AWG max.: 4 AWG
- Connection cross-section 2 min.: 1.5 mm²
- Connection cross-section 2 max.: 10 mm²
- Connection cross-section 2 AWG min.: 16 AWG
- Connection cross-section 2 AWG max.: 8 AWG
- Min. aux. cont. con. cr.-sect.: 0.5 mm²
- Max. aux. cont. conn. cr.-sec.: 4 mm²
- Min. aux. co. con. cr.-se. AWG: 18 (unece.unit.AWG)
- Connection cross-section of auxiliary contact AWG max.: 14 (unece.unit.AWG)
- Min. tightening torque: 2 N·m
- Max. tightening torque: 3 N·m
- Connection cross-section note: 2-conductor connection (upper and lower chamber at the same time): upper and lower chamber max. 16/10 mm² (A maximum difference of one cross section may be clamped between the upper and lower chamber.) The permitted combinations of connection cross-sections can be found in the operating instructions.
Dimensions
- Width: 110 mm (4.33 in)
- Length: 165 mm (6.5 in)
- Mounting depth: 138.3 mm (5.44 in)
- Weight: 1.8 kg (3.969 lb)
Mounting / Installation
- Tightening torque: 2-3 N·m (17.7 to 26.6 lbf·in)
- Tightening torque auxiliary contact: 0.4–0.6 N·m (3.5 to 5.3 lbf·in)
Technical Drawings
Tripping Curve: The document includes a tripping curve graph showing the relationship between multiple of rated current and tripping time for tripping characteristic C, for both AC and DC.
Dimensional Drawings: The document provides detailed dimensional drawings of the circuit breaker, including front, side, and top views, with dimensions in millimeters and inches. It also shows the arrangement for 3-pole with auxiliary contacts.
Accessories
4-way locking device
A lock-out/tag-out hasp for individually locking the component using up to four cylinder locks.
- Art. No.: 227232
Cylinder lock
- For closing (bracket Ø 3)
- Art. No.: 107115
Fastening set
A fastening set for fastening the component on the mounting plate without a DIN rail.
- Art. No.: 276618
Note: R. STAHL reserves the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.