ASCO H150, H300, H386 Series 600-1000 Ampere Transfer Switches: Composite Outline

General Notes

Cabling Notes

  1. All sizes supplied standard with mechanical (screw type) lugs. (See Amp Size Below)
    • Lug Material: Aluminum Alloy 6061-T6 with electro tin plated finish.
    • Screw Material: Aluminum Alloy 6262-T9 with electro tin plated finish.
    • UL Listed, CSA Certified.
    • Lug Screw Tightening Torque per UL 486B: 19 ft-lbs.
    • Suitable wire bending space is provided. (See Amp Size Below)
  2. Optional copper crimp lugs may be supplied. (See Amp Size Below)
    • Lug Material: High conductivity wrought copper finish, electro tin plated.
    • UL Listed, CSA Certified.
    • Lug mounting hardware tightening torque: (Refer to withstand current rating label provided on each transfer switch).
    • Suitable wire bending space is provided. (See Amp Size Below)
  3. Consult factory for other termination requirements.

Notes 600 Amp Switches

  1. Supplied with standard mechanical (screw type) lugs on the Normal, Emergency & Load Bus Stabs. One (1) lug per phase and neutral each suitable for connection of two (2) #2 -600MCM Cu/Al cable (See Note "E" below).
  2. E. Suitable wire bending space is provided for up to two (2) 600MCM cables per terminal per Table 373-6(b) of NFPA 70 of the NEC.
  3. Optional copper crimp lugs may be supplied. Up to two (2) two-hole, long barrel Cu crimp lugs rated for up to 600MCM. (Refer to crimp lug installation data provided with unit for full installation details).
  4. D. Suitable wire bending space is provided for up to two (2) 600MCM cables per terminal per Table 373-6(b) of NFPA 70 of the NEC.

Notes 800-1000 Amp Switches

  1. Supplied with standard mechanical (screw type) lugs on the Normal, Emergency & Load Bus Stabs. One (1) lug per phase and neutral each suitable for connection of four (4) 1/0 -750MCM Cu/Al cable (See Note "E" below).
  2. E. Suitable wire bending space is provided for up to four (4) 600MCM cables per terminal per Table 373-6(b) of NFPA 70 of the NEC.
  3. Optional copper crimp lugs may be supplied. Up to four (4) two-hole, long barrel Cu crimp lugs rated for up to 600MCM. (Refer to crimp lug installation data provided with unit for full installation details).
  4. D. Suitable wire bending space is provided for up to four (4) 600MCM cables per terminal per Table 373-6(b) of NFPA 70 of the NEC.

Dimensional Outline

This section details the physical dimensions and views of the ASCO transfer switch enclosures.

Left Side View (With Door)

Enclosure dimensions: 34.00 inches (width) x 72.00 inches (height) x 19.66 inches (depth, typical).

Features:

Front View (Without Door)

Internal view showing components. Dimensions:

Right Side View (With Door)

Enclosure dimensions: 34.00 inches (width) x 20.00 inches (height) x 11.00 inches (depth, typical).

Features:

Bottom View

Enclosure dimensions:

Revision History

Rev Description Date Drawn By Checked Approved
A ISSUED 5/14/01 DJB BK WK
A SEE ECN 157637 5/14/01 BWH WK 5/14/01
A SEE ECN 158035 6/25/01 BWM WK 6/25/01
B SEE ECN 158984 10/01 BK BK 10/01

Project Information

Project Name: COMPOSITE OUTLINE

Model Series: H150-H300-H386 SERIES TS "H" 600-1000 AMP TYPE 1

Drawn By: DJB (5/14/01)

Checked By: BK (5/15/01)

Final Approval: WK (3/15/01)

Manufacturer: ASCO POWER TECHNOLOGIES, LP. Florham Park, New Jersey 07932 U.S.A.

Manufacturing Tolerances: To be in accordance with ASCO specification -055-003 for plastic parts. -0.055.

Computer Generated Drawing.

Third Angle Projection.

Property of ASCO Power Technologies. Use permitted for our work only. All rights of design or invention are reserved.

PDF preview unavailable. Download the PDF instead.

713208 Acrobat Distiller 4.0 for Windows

Related Documents

Preview ASCO H150, H300, H386 Series 600-1000 Amp Transfer Switches Composite Outline
Technical outline and general notes for ASCO H150, H300, and H386 series automatic transfer switches, rated for 600-1000 Amperes. Includes enclosure details, cabling notes, and switch specifications.
Preview ASCO Series H386 Non-Automatic Transfer Switch Wiring Diagrams and Specifications
Technical document detailing wiring diagrams, field connections, general notes, features, and catalog number explanations for ASCO Series H386 Non-Automatic Transfer Switches (600-1200 Amperes).
Preview ASCO Series 300 Automatic Transfer Switches: Enclosure Outlines and Mounting Diagrams
Technical specifications and mounting diagrams for ASCO Series 300 Automatic Transfer Switches, detailing enclosure types (Type I, 3R, 4, 12) and dimensions for amp ratings from 30 to 800 amps.
Preview ASCO Series H150, H300, H386 Transfer Switches: Outline and Mounting Data (600-1200 Amps)
Detailed outline and mounting specifications for ASCO Series H150, H300, and H386 automatic transfer switches, covering 600 to 1200 Amp ratings. Includes dimensional data, cabling information, enclosure requirements, and control panel mounting details.
Preview ASCO Series 300 Automatic Transfer Switch Dimensions and Mounting Data (600-800 Amp)
Technical specifications, outline drawings, and mounting dimensions for ASCO Series 300 Automatic Transfer Switches (ATS) rated 600 through 800 Amperes. Includes general notes, terminal information, and control panel cutout details.
Preview ASCO 300 Series Automatic Transfer Switches: Outline and Mounting Dimensions
Detailed outline and mounting dimensions for ASCO 300 Series Automatic Transfer Switches, 30 through 200 Amperes, Open Type, 2 & 5 Pole, with and without Neutral. Includes general notes and dimensional tables for unit size and panel cutouts.
Preview ASCO Series 300 Automatic Transfer Switches: Composite Enclosure Outline and Mounting Data
Detailed technical specifications, outline, and mounting diagrams for ASCO Series 300 Automatic Transfer Switches, covering 2600 through 4000 AMP models. Includes general notes, dimensions, and enclosure details.
Preview ASCO Series 300 Automatic Transfer Switches Operator's Manual
Comprehensive operator's manual for ASCO Series 300 Automatic Transfer Switches (ATS), covering models from 30 to 400 amps. This guide details installation, operation sequences, testing procedures, maintenance, adjustments, and control features for reliable emergency and standby power applications.