General Notes
- Enclosures constructed in accordance with UL Standard 508, or UL 50.
- Standard finish: Light Grey ANSI #61.
- Width, height, and depth dimensions on Figure 1 are outside dimensions.
- The transfer switch unit is mounted on the inside back surface and the accessory control panel mounted on the inside door surface. The control panel is connected to the transfer switch panel by a wire harness with two (2) quick disconnect plugs.
- An operator's manual is furnished with each automatic transfer switch. Refer to this publication prior to installation and operation of the switch.
Notes
- Type 1 enclosure. Free standing. Floor mounted. 12 gauge formed frame construction.
- NEC standard gauge pan type door with lockable handle.
- Recommended clearances: Front: 36 inches.
- Unit is designed for combination top and bottom cable entry. The standard switch configuration is for top entry emergency & load and bottom entry normal.
- No knockouts are provided.
- Single door hinged on right for 2600/3000 AMP. Two door for 4000 AMP.
Enclosure Dimensions and Details
Figure 1: Enclosure Outline
The enclosure is depicted with a front view and a side view. The front view shows a two-door design for the 4000 AMP model, featuring a handle location and conduit areas at the top and bottom. The side view illustrates key dimensions labeled A, B, C, D, E, F, and G, with a conduit area indicated. A plan view shows a dimension 'H' and a diameter 'H DIA.' for conduit entry.
Dimensions Table (Without Optional ACC. 28)
AMP | FIG. SIZE NO. | Dimension A (Inches) | Dimension B (Inches) | Dimension C (Inches) | Dimension D (Inches) | Dimension E (Inches) | Dimension F (Inches) | Poles |
---|---|---|---|---|---|---|---|---|
2600/3000 | 2 | 37.00 (939.8) | 91.00 (2311.4) | 60.00 (1524.0) | 54.00 (1371.6) | 3.00 (76.2) | 31.00 (787.4) | 3 |
4000 | 2 | 46.00 (1168.4) | 91.00 (2311.4) | 72.00 (1828.8) | 66.00 (1676.4) | 3.00 (76.2) | 42.00 (1066.8) | 3 |
Dimensions Table (With Optional ACC. 28)
AMP | FIG. SIZE NO. | Dimension A (Inches) | Dimension B (Inches) | Dimension C (Inches) | Dimension D (Inches) | Dimension E (Inches) | Dimension F (Inches) | Poles |
---|---|---|---|---|---|---|---|---|
2600/3000 | 3 W/ACC.28 | 37.00 (939.8) | 91.00 (2311.4) | 60.00 (1524.0) | 54.00 (1371.6) | 3.00 (76.2) | 31.00 (787.4) | 3 W/ACC.28 |
4000 | 3 W/ACC.28 | 46.00 (1168.4) | 91.00 (2311.4) | 72.00 (1828.8) | 66.00 (1676.4) | 3.00 (76.2) | 42.00 (1066.8) | 3 W/ACC.28 |
Approximate Shipping Weight
AMP | FIG. SIZE NO. | Poles | Approximate Shipping Weight (LBS/KG) |
---|---|---|---|
2600/3000 | 2 | 3 | 2150 (976) |
4000 | 2 | 3 | 2580 (1171) |
2600/3000 | 3 W/ACC.28 | 3 | 2230 (1012) |
4000 | 3 W/ACC.28 | 3 | 2680 (1217) |
Product Identification
This document details the Composite Enclosure Outline and Mounting Diagram for 3 Pole Automatic Transfer Switches (with or without Neutral) from 2600 through 4000 AMP, specifically the ASCO® Series 300.
Manufacturer: Automatic Switch Co., Florham Park, New Jersey 07932.
Document Number: DS 497148-002.
Manufacturing tolerances are in accordance with ASCO Procedure MP-1-003. For plastic parts, refer to MP-1-055.