This document provides a composite outline and dimensional information for ASCO H150, H300, and H386 Series automatic transfer switches, rated for 600-1000 Amperes, Type 3R/4/12 enclosures.
The outline illustrates various views of the transfer switch enclosure, including:
- Left Side View (With Door): Shows the overall dimensions and external features. Key dimensions include a height of 72.00 inches (Box O.D.), a depth of 19.09 inches, and a width of 34.00 inches (Enclosure). A ground buss for 600 Amps is noted as "Top Only", while a ground buss for 800-1000 Amps is located at "Both Top and Bottom".
- Front View (Without Door): Displays the internal layout of the switchgear. It shows the main load lugs, neutral connections, and terminal blocks (TB) for field connections, specifically for H150/H300 models. Dimensions include a height of 72.00 inches (Box O.D.) and a depth of 19.09 inches.
- Right Side View: Shows the enclosure from the right. Key dimensions include a height of 75.00 inches (Total O.D.) and a depth of 19.09 inches. This view highlights the location of user controls and indicators, and field connections terminal block (TB) for H386 models.
- Front View (With Door): Similar to the front view without the door, showing the internal components.
- Bottom View: Details the bottom of the enclosure, indicating a conduit area with dimensions 29.0 x 14.0 inches. It also shows mounting hole locations (4 PLC's with diameter 0.56 inches) and leg height (3.00 inches). Minimum door clearance is 34.00 inches.
The enclosure is described as free-standing, floor-mounted, constructed from 12-gauge formed frame. The door is hinged on the right side with clamps and a lockable handle on the left. The standard finish is ASA 61 Gray polyester powder, with other ANSI colors available upon consultation.
General Notes
- Type 3R/4/12 enclosure. Free standing. Floor mounted. 12 gauge formed frame construction.
- Door hinged on right side. Door clamps and lockable handle on left.
- Finish: ASA 61 Gray, polyester powder standard. Other ANSI colors available, consult factory.
- UL Recognized.
- Recommended Clearances: Front: 34 inches.
- The standard switch configuration is for top lugs (Emergency and Load) and bottom lugs (Normal).
- Neutral Configurations:
- H300-A: Full rated solid (copper bus) neutral connection for each source and the load is provided standard. Optionally, a switched neutral pole may be provided as specified by the catalog number. (B) indicates a switched neutral pole.
- H386: An optional full rated neutral connection for each source and the load may be provided when equipped. It is in one of the following formats as specified by the catalog number: Neutral Type: A. Solid (copper bus) neutral, B. Switched neutral pole.
- Remove bottom knockouts for Type 3R.
Cabling Notes
- All sizes supplied standard with mechanical (screw type) lugs. (See Amp Size below)
- Lug Material: Aluminum Alloy 6061-T6 with electro tin plated finish.
- Screw Material: Aluminum Alloy 6262-19 with electro tin plated finish.
- UL Listed, CSA Certified.
- Lug screw tightening torque per UL 486B: 19 ft-lbs.
- Suitable wire bending space is provided. (See Amp Size below)
- Optional copper crimp lugs may be supplied. (See Amp Size below)
- Lug Material: High conductivity wrought copper finish, electro tin plated.
- UL Listed, CSA Certified.
- Lug mounting hardware tightening torque: Refer to withstand current rating label provided on each transfer switch.
- Suitable wire bending space is provided. (See Amp Size below)
- Consult factory for other termination requirements.
Notes 600 Amp Switches
- Supplied with standard mechanical (screw type) lugs on the Normal, Emergency & Load bus stabs. One (1) lug per phase and neutral each suitable for connection of two (2) #2 -600MCM CU/AL cable (see note "E" below).
- Suitable wire bending space is provided for up to two (2) 600MCM cables per terminal per Table 373-6(b) of NFPA 70 of the NEC.
- Optional copper crimp lugs may be supplied. Up to two (2) two-hole, long barrel CU crimp lugs rated for up to 600MCM (Refer to crimp lug installation data provided with unit for full installation details).
- Suitable wire bending space is provided for up to two (2) 600MCM cables per terminal per Table 373-6(b) of NFPA 70 of the NEC.
Notes 800-1000 Amp Switches
- Supplied with standard mechanical (screw type) lugs on the Normal, Emergency & Load bus stabs. One (1) lug per phase and neutral each suitable for connection of four (4) 1/0 -750MCM CU/AL cable (see note "E" below).
- Suitable wire bending space is provided for up to four (4) 600MCM cables per terminal per Table 373-6(b) of NFPA 70 of the NEC.
- Optional copper crimp lugs may be supplied. Up to four (4) two-hole, long barrel CU crimp lugs rated for up to 600MCM (Refer to crimp lug installation data provided with unit for full installation details).
- Suitable wire bending space is provided for up to four (4) 600MCM cables per terminal per Table 373-6(b) of NFPA 70 of the NEC.