ASCO Series 300 Automatic Transfer Switches: 600-800 Amp Outline and Mounting Dimensions
Product Overview
This document provides composite outline and mounting dimensions for ASCO Series 300 Automatic Transfer Switches (ATS) rated for 600 through 800 Amperes. It covers both 2 and 3-pole configurations, with or without a neutral pole.
General Dimensions and Specifications
The following table details various dimensions (in inches and millimeters) for the transfer switch unit:
Dimension | A1 | A2 | B | C | D1 | D2 | E | F | G | H | J | K | M | N | P | R | S | T | W | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Value (in) | 0.249 | 0.252 | 19.25 | 22.75 | 25.00 | 11.00 | 18.37 | 21.87 | 0.43 | 489.0 | 577.8 | 635.0 | 279.4 | 466.6 | 555.5 | 10.9 | 190.5 | 31.8 | 174.5 | 88.9 | 44.5 |
Diameter (in) | Ø12.7 |
Mounting Hole Details:
- HOLE B-: Diameter 7.50 inches. Suggested mounting: 0.250-20 x 1.50 inch long Penn captive stud (e.g., FH-0420-24-ZI).
- HOLE C-: Diameter 1.25 inches. Suggested mounting: 0.163-0.166 diameter for 0.164-32 x 0.313 inch long Penn captive stud (e.g., FH-832-5-ZI).
Terminal Specifications:
- UL listed solderless screw type terminals for external power connections.
- Wire size range: #2 AWG to 600 MCM (Aluminum/Copper).
Mounting Bolt Suggestion: 3/8-16 x 1 1/2 inch length minimum, quantity 8.
Approximate Shipping Weight: (Includes standard transfer switch and controls)
- 2 Poles: 135 lbs (62 kg)
- 3 Poles: 145 lbs (66 kg)
- 4 Poles: 155 lbs (71 kg)
General Notes
- For two-pole switches, omit the center pole (F-1).
- When installing, connect Normal, Emergency, and Load conductors to similarly marked terminals.
- All internal connections are made at the factory.
- Maintain a minimum electrical clearance of 1.00 inch (25.4 mm) between live metal parts and grounded metal.
- Mount the transfer switch unit on the inside back surface and the control panel(s) on the inside door surface.
- The control panel connects to the transfer switch panel via a wire harness with two (2) quick disconnect plugs. The standard harness length is 50.00 inches (1270.0 mm). An extension harness (ACC. 37B) is available, adding 72 inches (1828 mm). Note: ACC. 37B must be specified at the time of order.
- For Type 1 enclosures, use the four (4) clearance corner holes or studs as required, per Detail "A"-1. For Type 3R, 4, & 12 enclosures, use all studs or holes, per Detail "A"-2. A gasket is provided for Type 3R, 4, & 12 enclosures.
- An Operator's Manual is furnished with each Automatic Transfer Switch. Refer to this publication prior to installation and operation of the switch.
Control Panel Mounting and Cutout Details
Control Panel Mounting Data:
Diagram shows a control panel with suggested mounting hole locations and dimensions for the control panel itself. Key dimensions include a width of 9.5 inches (241.3mm) and height of 7.6 inches (193.7mm) for the panel, with specific mounting hole placements.
Suggested Mounting:
- Hole B: Diameter for 0.250-20 x 1.50 long Penn captive stud (e.g., FH-0420-24-ZI).
- Hole C: Diameter for 0.163-0.166 for 0.164-32 x 0.313 long Penn captive stud (e.g., FH-832-5-ZI).
Mounting Instruction: Capture the grounding strap at the lower left corner of the control panel with mounting hardware on the mounting stud.
Controls (Cutout) Detail "A":
This section provides detailed cutout dimensions for control panels based on enclosure type. Specific dimensions are provided for hole placement and overall cutout size.
- Note 1: Cutout Detail "A"-1 is for Type 1 enclosures.
- Note 2: Cutout Detail "A"-2 is for Type 3R, Type 12, and Type 4 enclosures.
Suggested Mounting for Detail "A":
- Hole 'A': Diameter for 0.137-0.140, 0.138-32 x 0.625 long Penn Engineering & Mfg. Co. self-clinching captive stud (Part No. FH-632-8-ZI).
Document Information
Drawing Number: DS 613316-003
Revision History:
- A: 145236, YZ, 7/8/97
- B: ECN 145463, YZ, 8/97
- C: ECN 157034, TR, 3/30/01
Manufacturer: ASCO Power Technologies, LP, Florham Park, New Jersey 07932 U.S.A.